| 2018-12-28 08:08:08 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18120042 |
| | REVIEWED: DECEMBER 28, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | [FBC 107.5.3]STATE THE AMOUNT OF AFFECTED AREA. |
| | |
| | [FBC 404.2.4]MANEUVERING CLEARANCES. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY |
| | WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE |
| | FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE |
| | OR HINGE SIDE CLEARANCE. |
| | PLEASE STATE THE EXEMPTION THAT ALLOWS FOR OFFICE DOORS |
| | TO NOT MEET SECTION 404.2.4, OR UPDATE PLANS TO COMPLY. |
| | I?M REFERENCING TABLE 404.2.4.1 FIGURES F AND J. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |