| 2019-02-28 11:54:02 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120027 |
| | 12/17/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL |
| | EXISTS. THE 3M FIRE BARRIER DUCT WRAP IS A |
| | FIRE-RESISTANT WRAP THAT IS USED TO FIRE RATE |
| | COMMERCIAL KITCHEN GREASE DUCTS, AND IS A LISTED AND |
| | LABELED AS A FIELD APPLIED GREASE DUCT ENCLOSURE |
| | MATERIAL IN ACCORDANCE WITH THE ASTM E2336 STANDARD- |
| | SEE SUBMITTED PRODUCT SPECS AND SECTION 506.3.11.2 FBC |
| | M WHICH STATES "THE SURFACE OF THE DUCT SHALL BE |
| | CONTINUOUSLY COVERED ON ALL SIDES FROM THE POINT AT |
| | WHICH THE DUCT ORIGINATES TO THE OUTLET TERMINAL", AND |
| | "PARTIAL APPLICATION OF A FIELD-APPLIED GREASE DUCT |
| | ENCLOSURE SHALL NOT BE INSTALLED FOR THE SOLE PURPOSE |
| | OF REDUCING CLEARANCES TO COMBUSTIBLES AT ISOLATED |
| | SECTIONS OF GREASE DUCT". |
| | 1) REFER TO SECTION FBC M SECTION 506.5.1.2 IN-LINE FAN |
| | LOCATION. REVISE THE PLAN AND DETAILS TO SHOW |
| | COMPLIANCE. WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED |
| | TO IN-LINE FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE |
| | LOCATED IN A ROOM OR SPACE HAVING THE SAME |
| | FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE. ACCESS |
| | SHALL BE PROVIDED FOR SERVICING AND CLEANING OF FAN |
| | COMPONENTS. SUCH ROOMS OR SPACES SHALL BE VENTILATED IN |
| | ACCORDANCE WITH THE FAN MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 2) COMMENT #2 PRINTED BELOW STILL EXISTS. PLEASE |
| | CONSULT WITH THE CAPTIVEAIRE ENGINEER AND ENGINEER OF |
| | RECORD TO PROVIDE EITHER TEMPERED MAKEUP AIR, OR |
| | CALCULATIONS TO PROVE THE ADDED COOLING LOADS OF THE |
| | MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC |
| | SYSTEM. FOR CLARIFICATION THE MAKEUP AIR FOR THE HOOD |
| | IS BEING PROVIDED BY KSF-1 NOT THE DOAS WHICH IS |
| | PROVIDING OUTSIDE AIR FOR OCCUPANTS |
| | 2) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE. |
| | REVISE THE PLAN AND DETAILS TO SHOW COMPLIANCE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 3) COMMENT #3 STILL EXISTS. M-101 SHOWS TWO MAKEUP AIR |
| | SUPPLY DROPS INTO THE HOOD- H-1 SHOWS 4 DROPS. |
| | 3) SHEETS H-1 & M-101: THE EXHAUST DUCT CONFIGURATIONS |
| | AND DUCT SIZES ON THE TWO PLANS DO NOT MATCH. THE KEF |
| | IS MISLABELED KSF ON H-1. |
| | |
| | 4) COMMENT #4 STILL EXISTS. THE H-1 PLAN SHOWS A |
| | MINIMUM 1/8" SLOPE FOR THE GREASE DUCT. SECTION 506.3.7 |
| | REQUIRES A MINIMUM SLOPE OF 1/4" PER FT. |
| | 4) H-1: PROVIDE THE SLOPE OF THE DUCT RUN- SECTION |
| | 506.3.7 FBC M, AND A DETAIL FOR THE GREASE RESERVOIR |
| | (NOTED AS A GREASE TRAP ON PLAN)- SECTION 506.3.7.1. |
| | |
| | 6) COMMENT #6 STILL EXISTS. THE NEW SUBMITTAL FOR THE |
| | GREENHECK INLINE EXHAUST FAN INDICATES THE FAN IS UL |
| | 705 LISTED, NOT UL 762, AND NO SPECIFICATIONS PROVIDED |
| | FOR THE HOUSING MATERIAL. |
| | 6) H-1: THE GREENHECK EXHAUST FAN SHALL EITHER BE UL |
| | 762 LISTED AND LABELED, OR THE FAN HOUSING SHALL BE |
| | CONSTRUCTED WITH THE SAME MATERIALS AS REQUIRED FOR |
| | GREASE DUCTS- SEE SECTIONS 506.5.1 & 506.3.1.1. |
| | |
| | 9) COMMENT #9 NOT COMPLETELY ADDRESSED. WHAT ARE THE |
| | DIMENSIONS OF THE GREASE EXHAUST OUTLET? THE REVISED |
| | H-1 SHOWS DIMENSIONS THAT ARE NOT COMPLETELY LEGIBLE, |
| | AND THE M-101 PLAN INDICATES 48X30". THE M-101 PLAN |
| | DOES NOT LIST REQUIRED CLEARANCES. |
| | 9) H-1: PLEASE VERIFY THE EXHAUST OUTLET IS MEETING ALL |
| | CLEARANCE REQUIREMENTS AS OUTLINED IN SECTION |
| | 506.3.13.3- NOT LESS THAN 10' HORIZONTALLY FROM PARTS |
| | OF THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY |
| | LINES, AND NOT LESS THAN 10' ABOVE THE ADJOINING GRADE |
| | LEVEL, |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |