Plan Review Details - Permit 18120027
Plan Review Stops For Permit 18120027
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-05 Cont ID  
Sent By jpearson Date 2019-04-05 Time 08:24 Rev Time 0.00
Received By jpearson Date 2019-04-05 Time 08:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-27 Cont ID  
Sent By jpearson Date 2019-02-27 Time 15:03 Rev Time 0.00
Received By jpearson Date 2019-02-27 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By jpearson Date 2018-12-14 Time 13:21 Rev Time 0.00
Received By jpearson Date 2018-12-14 Time 13:21 Sent To  
Notes
2018-12-14 13:21:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE SHEETS SUBMITTED SEEM LIKE A REVISION SUBMITTAL
 TO THE ORIGINAL PERMIT. REVIEWER DOES NOT SEE
 ELECTRICAL INFORMATION RELATING TO THE HOOD
 INSTALLATION. PROVIDE CORRECTION. ANY REVISIONS TO
 MASTER PERMIT SHOULD BE SUBMITTED SEPARATELY. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-01 Cont ID  
Sent By scaldero Date 2019-04-01 Time 13:35 Rev Time 0.00
Received By scaldero Date 2019-04-01 Time 13:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-02-27 Cont ID  
Sent By scaldero Date 2019-02-27 Time 13:11 Rev Time 0.00
Received By scaldero Date 2019-02-27 Time 13:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-07 Cont ID  
Sent By scaldero Date 2018-12-07 Time 12:17 Rev Time 0.00
Received By scaldero Date 2018-12-07 Time 12:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-08 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-27 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-02-28 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-26 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-12-18 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-05 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-08 Cont ID  
Sent By ccole Date 2019-04-08 Time 11:16 Rev Time 0.00
Received By ccole Date 2019-04-08 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-28 Cont ID  
Sent By ccole Date 2019-02-28 Time 11:52 Rev Time 0.00
Received By ccole Date 2019-02-27 Time 17:49 Sent To  
Notes
2019-02-28 11:54:022ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18120027
 12/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW STILL
 EXISTS. THE 3M FIRE BARRIER DUCT WRAP IS A
 FIRE-RESISTANT WRAP THAT IS USED TO FIRE RATE
 COMMERCIAL KITCHEN GREASE DUCTS, AND IS A LISTED AND
 LABELED AS A FIELD APPLIED GREASE DUCT ENCLOSURE
 MATERIAL IN ACCORDANCE WITH THE ASTM E2336 STANDARD-
 SEE SUBMITTED PRODUCT SPECS AND SECTION 506.3.11.2 FBC
 M WHICH STATES "THE SURFACE OF THE DUCT SHALL BE
 CONTINUOUSLY COVERED ON ALL SIDES FROM THE POINT AT
 WHICH THE DUCT ORIGINATES TO THE OUTLET TERMINAL", AND
 "PARTIAL APPLICATION OF A FIELD-APPLIED GREASE DUCT
 ENCLOSURE SHALL NOT BE INSTALLED FOR THE SOLE PURPOSE
 OF REDUCING CLEARANCES TO COMBUSTIBLES AT ISOLATED
 SECTIONS OF GREASE DUCT".
 1) REFER TO SECTION FBC M SECTION 506.5.1.2 IN-LINE FAN
 LOCATION. REVISE THE PLAN AND DETAILS TO SHOW
 COMPLIANCE. WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED
 TO IN-LINE FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE
 LOCATED IN A ROOM OR SPACE HAVING THE SAME
 FIRE-RESISTANCE RATING AS THE DUCT ENCLOSURE. ACCESS
 SHALL BE PROVIDED FOR SERVICING AND CLEANING OF FAN
 COMPONENTS. SUCH ROOMS OR SPACES SHALL BE VENTILATED IN
 ACCORDANCE WITH THE FAN MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 2) COMMENT #2 PRINTED BELOW STILL EXISTS. PLEASE
 CONSULT WITH THE CAPTIVEAIRE ENGINEER AND ENGINEER OF
 RECORD TO PROVIDE EITHER TEMPERED MAKEUP AIR, OR
 CALCULATIONS TO PROVE THE ADDED COOLING LOADS OF THE
 MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE HVAC
 SYSTEM. FOR CLARIFICATION THE MAKEUP AIR FOR THE HOOD
 IS BEING PROVIDED BY KSF-1 NOT THE DOAS WHICH IS
 PROVIDING OUTSIDE AIR FOR OCCUPANTS
 2) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE.
 REVISE THE PLAN AND DETAILS TO SHOW COMPLIANCE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 3) COMMENT #3 STILL EXISTS. M-101 SHOWS TWO MAKEUP AIR
 SUPPLY DROPS INTO THE HOOD- H-1 SHOWS 4 DROPS.
 3) SHEETS H-1 & M-101: THE EXHAUST DUCT CONFIGURATIONS
 AND DUCT SIZES ON THE TWO PLANS DO NOT MATCH. THE KEF
 IS MISLABELED KSF ON H-1.
  
 4) COMMENT #4 STILL EXISTS. THE H-1 PLAN SHOWS A
 MINIMUM 1/8" SLOPE FOR THE GREASE DUCT. SECTION 506.3.7
 REQUIRES A MINIMUM SLOPE OF 1/4" PER FT.
 4) H-1: PROVIDE THE SLOPE OF THE DUCT RUN- SECTION
 506.3.7 FBC M, AND A DETAIL FOR THE GREASE RESERVOIR
 (NOTED AS A GREASE TRAP ON PLAN)- SECTION 506.3.7.1.
  
 6) COMMENT #6 STILL EXISTS. THE NEW SUBMITTAL FOR THE
 GREENHECK INLINE EXHAUST FAN INDICATES THE FAN IS UL
 705 LISTED, NOT UL 762, AND NO SPECIFICATIONS PROVIDED
 FOR THE HOUSING MATERIAL.
 6) H-1: THE GREENHECK EXHAUST FAN SHALL EITHER BE UL
 762 LISTED AND LABELED, OR THE FAN HOUSING SHALL BE
 CONSTRUCTED WITH THE SAME MATERIALS AS REQUIRED FOR
 GREASE DUCTS- SEE SECTIONS 506.5.1 & 506.3.1.1.
  
 9) COMMENT #9 NOT COMPLETELY ADDRESSED. WHAT ARE THE
 DIMENSIONS OF THE GREASE EXHAUST OUTLET? THE REVISED
 H-1 SHOWS DIMENSIONS THAT ARE NOT COMPLETELY LEGIBLE,
 AND THE M-101 PLAN INDICATES 48X30". THE M-101 PLAN
 DOES NOT LIST REQUIRED CLEARANCES.
 9) H-1: PLEASE VERIFY THE EXHAUST OUTLET IS MEETING ALL
 CLEARANCE REQUIREMENTS AS OUTLINED IN SECTION
 506.3.13.3- NOT LESS THAN 10' HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES, AND NOT LESS THAN 10' ABOVE THE ADJOINING GRADE
 LEVEL,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-17 Cont ID  
Sent By ccole Date 2018-12-17 Time 12:47 Rev Time 0.00
Received By ccole Date 2018-12-17 Time 12:12 Sent To  
Notes
2018-12-17 13:19:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120027
 12/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) REFER TO SECTION FBC M SECTION 506.5.1.2 IN-LINE FAN
 LOCATION. REVISE THE PLAN AND DETAILS TO SHOW
 COMPLIANCE.
  
 WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE
 FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN
 A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING
 AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR
 SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR
 SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 2) REFER TO SECTION 508.1.1 MAKEUP AIR TEMPERATURE.
 REVISE THE PLAN AND DETAILS TO SHOW COMPLIANCE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 3) SHEETS H-1 & M-101: THE EXHAUST DUCT CONFIGURATIONS
 AND DUCT SIZES ON THE TWO PLANS DO NOT MATCH. THE KEF
 IS MISLABLED KSF ON H-1.
  
 4) H-1: PROVIDE THE SLOPE OF THE DUCT RUN- SECTION
 506.3.7 FBC M, AND A DETAIL FOR THE GREASE RESERVOIR
 (NOTED AS A GREASE TRAP ON PLAN)- SECTION 506.3.7.1.
  
 5) H-1: REVISE THE NOTE THAT INDICATES THE CAPTIVE AIRE
 HOOD DRAWINGS ARE SUBMITTED UNDER A SEPARATE PERMIT.
 THOSE DRAWINGS ARE SUBMITTED UNDER THIS PERMIT.
  
 6) H-1: THE GREENHECK EXHAUST FAN SHALL EITHER BE UL
 762 LISTED AND LABELED, OR THE FAN HOUSING SHALL BE
 CONSTRUCTED WITH THE SAME MATERIALS AS REQUIRED FOR
 GREASE DUCTS- SEE SECTIONS 506.5.1 & 506.3.1.1.
  
 7) H-1: REVISE NOTE #6 IN THE FAN SCHEDULE IN
 ACCORDANCE WITH SECTIONS 507.1.1 AND 508.1 FBC M.
 AUTOMATIC OPERATION OF THE FANS IS REQUIRED. PLEASE
 REVIEW THE CODE SECTIONS AND PROVIDE A SEQUENCE OF
 OPERATION IN COMPLIANCE.
  
 8) H-1 & CAPTIVEAIRE SHEET 1: THE EXHAUST AND MAKEUP
 AIR RATES IN THE H-1 FAN SCHEDULE DO MATCH THE REQUIRE
 EXHAUST RATES SHOWN ON THE CAPTIVEAIRE SCHEDULE.
  
 9) H-1: PLEASE VERIFY THE EXHAUST OUTLET IS MEETING ALL
 CLEARANCE REQUIRMENTS AS OUTLINED IN SECTION
 506.3.13.3- NOT LESS THAN 10' HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY
 LINES, AND NOT LESS THAN 10' ABOVE THE ADJOINING GRADE
 LEVEL,
  
 10) PLEASE REMOVE THE SMOKE CONTROL FANS FROM THE FAN
 SUBMITTAL PACKAGE, AND RESUBMIT THEM UNDER A SEPARATE
 APPLICATION WITH ALL LABOR, MATERIAL, AND EQUIPMENT
 COSTS ACCOUNTED FOR- SECTION 107.2.1 AND 109.3 WPB.
  
 11) THERE ARE THREE ENGINEERS SUBMITTING PLANS ON THIS
 EXHAUST HOOD SYSTEM. ONE OF THE ENGINEERS MUST BE THE
 EOR AND PROVIDE HIS/HER SHOP DRAWING STAMPS ON THE
 OTHER PLANS- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-04-08 Cont ID  
Sent By ccole Date 2019-04-08 Time 11:16 Rev Time 0.00
Received By ccole Date 2019-04-08 Time 11:16 Sent To  
Notes
2019-04-05 08:24:21ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-28 Cont ID  
Sent By ccole Date 2019-02-28 Time 12:00 Rev Time 0.00
Received By ccole Date 2019-02-28 Time 12:00 Sent To  
Notes
2019-02-27 14:42:37ELECTRICAL SHEETS OK.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-12-18 Cont ID  
Sent By ccole Date 2018-12-17 Time 12:38 Rev Time 0.00
Received By ccole Date 2018-12-17 Time 12:38 Sent To  
Notes
***NONE***