Plan Review Details - Permit 18111241
Plan Review Stops For Permit 18111241
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-15 Cont ID  
Sent By jleahy Date 2019-03-15 Time 07:44 Rev Time 0.00
Received By jleahy Date 2019-03-15 Time 07:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By jleahy Date 2018-12-19 Time 18:17 Rev Time 0.00
Received By jleahy Date 2018-12-19 Time 18:17 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-19 Cont ID  
Sent By tklarge Date 2019-03-19 Time 11:40 Rev Time 0.00
Received By tklarge Date 2019-03-07 Time 13:20 Sent To  
Notes
2019-03-08 13:20:50RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-27 Cont ID  
Sent By tklarge Date 2018-12-27 Time 14:42 Rev Time 0.00
Received By tklarge Date 2018-11-30 Time 13:03 Sent To  
Notes
2018-12-03 13:04:13ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-12-19 Cont ID  
Sent By ccole Date 2018-12-19 Time 17:36 Rev Time 0.00
Received By ccole Date 2018-12-19 Time 16:54 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2019-04-02 Cont ID  
Sent By skennedy Date 2019-04-02 Time 10:03 Rev Time 0.00
Received By skennedy Date 2019-04-02 Time 10:03 Sent To  
Notes
2019-04-02 10:04:17NO PLUMBING IN SCOPE OF WORK. RREVISION REQUIRED FOR
 REMOVED P SHEETS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-03-19 Cont ID  
Sent By tklarge Date 2019-03-19 Time 11:40 Rev Time 0.00
Received By tklarge Date 2019-03-19 Time 05:26 Sent To I
Notes
2019-03-19 11:40:371) THE SPECIFICATION SHEETS THAT HAVE BEEN SUBMITTED
 FOR THE COMPRESSOR, THE DRYER, THE RECEIVER AND THE
 FILTERS DO MATCH THE EQUIPMENT CALLED OUT FOR ON THE
 PLANS. THE PLANS CALL OUT INGERSOLL-RAND EQUIPMENT BUT
 THE SPECS ARE FOR KAESER AND CHAMPION EQUIPMENT. ALSO,
 SEE SHT.P-1 UNDER THE "REMARKS" BOX. CLARIFY.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR THE OIL/WATER SEPARATOR, THE
 PNEUMATIC NO-LOSS DRAIN, THE RECEIVER, THE DRYER AND
 THE COMPRESSOR. WPB AMEND. TO FBC SEC. 107.2.1.
 3) ALL INFORMATION, DRAWINGS,SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE
 MANUFACTURER'S SPECIFICATION SHEETS SHALL BE STAMPED BY
 THE E.O.R. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE AIR PIPING ISOMETRIC ON SHT. P-3 SHOWS A 1 1/2
 INCH INLET AND OUTLET AT THE DRYER BUT A SIZE OF 1 INCH
 IS CIRCLED ON THE TECHNICAL SPECIFICATION PAGE OF THE
 DRYER SPECIFICATIONS. CLARIFY.
 5) A PRESSURE GAUGE AND THERMOMETER ARE REQUIRED ON THE
 AIR COMPRESSOR PER SHT.P-1, NOTE #3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-27 Cont ID  
Sent By tklarge Date 2018-12-27 Time 14:42 Rev Time 0.00
Received By tklarge Date 2018-12-27 Time 04:15 Sent To I
Notes
2018-12-27 14:42:151) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL FOR THE COMPRESSOR AND OTHER
 SYSTEM COMPONENTS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-3 - IDENTIFY ALL SYSTEM COMPONENTS ON THE CEP
 BUILDING - NEW AIR COMPRESSOR PLAN, INCLUDING THE
 EXISTING. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. E-1 - PROVIDE THE UL ASSEMBLY NUMBER FOR THE 2
 HOUR FIRE RATED FIRESTOP SYSTEM FOR MULTIPLE METAL PIPE
 THROUGH CONCRETE WALLS. THERE IS NO UL ASSEMBLY NUMBER
 ON THE DETAIL.
 4) SUBMIT A COMPRESSED AIR PIPING RISER FOR ANY NEW
 PIPING TO BE ADDED. SHOW THE REQUIRED THERMOMETER AND
 PRESSURE GAUGE ON THE DISCHARGE PIPING FROM EACH AIR
 COMPRESSOR AND RECEIVER PER THE SPECIFICATIONS ON SHT.
 P-1. SHOW ALL REQUIRED VALVES PER THE SPECIFICATIONS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 5) SUBMIT ADDITIONAL INFORMATION FOR THE ANCHORING OF
 THE COMPRESSOR TO THE SLAB/PAD. THE PLANS CALL OUT 5/8"
 BOLTS. INDICATE THE LENGTH OF THE BOLTS AND TORQUING
 REQS. FOR THE BOLTS. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P-4 - SOME OF THE PRINTING ON THE DETAILS IS SO
 SMALL IT IS ILLEGIBLE. SUBMIT DETAILS WHERE THE THE
 NOTES ARE LEGIBLE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  