Plan Review Details - Permit 18111203
Plan Review Stops For Permit 18111203
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By dbattles Date 2019-05-08 Time 08:28 Rev Time 0.00
Received By dbattles Date 2019-05-08 Time 08:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-04-19 Cont ID  
Sent By dbattles Date 2019-04-19 Time 15:03 Rev Time 0.00
Received By dbattles Date 2019-04-19 Time 15:03 Sent To  
Notes
2019-04-19 15:14:50****CORRECTIONS****
 W.P.B. PERMIT: 1901
 REVIEWED: APRIL 19, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) ALONG WITH PROVIDING CLASS I VAPOR BARRIER ITEM 2 OF
 R408.3 NEEDS TO BE ADDRESSED.
 R408.3 UNVENTED CRAWL SPACE. VENTILATION OPENINGS IN
 UNDERFLOOR SPACES SPECIFIED IN SECTIONS R408.1 AND
 R408.2 SHALL NOT BE REQUIRED WHERE THE FOLLOWING ITEMS
 ARE PROVIDED:
 1. EXPOSED EARTH IS COVERED WITH A CONTINUOUS CLASS I
 VAPOR RETARDER. JOINTS OF THE VAPOR RETARDER SHALL
 OVERLAP BY 6 INCHES (152 MM) AND SHALL BE SEALED OR
 TAPED. THE EDGES OF THE VAPOR RETARDER SHALL EXTEND NOT
 LESS THAN 6 INCHES (152 MM) UP THE STEM WALL AND SHALL
 BE ATTACHED AND SEALED TO THE STEM WALL OR INSULATION.
 2. ONE OF THE FOLLOWING IS PROVIDED FOR THE UNDER-FLOOR
 SPACE: 2.1. CONTINUOUSLY OPERATED MECHANICAL EXHAUST
 VENTILATION AT A RATE EQUAL TO 1 CUBIC FOOT PER MINUTE
 (0.47 L/S) FOR EACH 50 SQUARE FEET (4.7 M2) OF CRAWL
 SPACE FLOOR AREA, INCLUDING AN AIR PATHWAY TO THE
 COMMON AREA (SUCH AS A DUCT OR TRANSFER GRILLE), AND
 PERIMETER WALLS INSULATED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, ENERGY CONSERVATION.
 2.2. CONDITIONED AIR SUPPLY SIZED TO DELIVER AT A RATE
 EQUAL TO 1 CUBIC FOOT PER MINUTE (0.47 L/S) FOR EACH 50
 SQUARE FEET (4.7 M2) OF UNDER-FLOOR AREA, INCLUDING A
 RETURN AIR PATHWAY TO THE COMMON AREA (SUCH AS A DUCT
 OR TRANSFER GRILLE), AND PERIMETER WALLS INSULATED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION.
 2.3. PLENUM IN EXISTING STRUCTURES COMPLYING WITH
 SECTION M1601.5, IF UNDER-FLOOR SPACE IS USED AS A
 PLENUM.
  
 2) PLEASE SELECT THE SYSTEM BEING USED ON FLAT ROOF
 PRODUCT APPROVAL AND PROVIDE RAS 177 IF APPLICABLE.
 [RAS 117]PROVIDE ENGINEERING FOR ENHANCED NAILING AS
 STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS
 #7.
 THIS CAN BE DEFERRED UNTIL ROOFING SUB PERMIT IS
 APPLIED FOR, OR SUPPLIED NOW.
  
 3) ALL OTHER COMMENTS ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By dbattles Date 2019-01-02 Time 11:10 Rev Time 0.00
Received By dbattles Date 2018-12-31 Time 09:37 Sent To  
Notes
2019-01-02 11:13:59****CORRECTIONS****
 W.P.B. PERMIT: 18111203
 REVIEWED: JANUARY 02, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 103.1.1.2 FBC[E] THE BUILDING'S OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES. -PLEASE HAVE THE OWNER SIGN THE ENERGY
 CALCULATIONS
  
 2) 107.5.3[E] THE FLOOR TYPE IN THE ENERGY CALCULATIONS
 SAYS SLAB ON GRADE. THIS IS A RAISED WOOD FLOOR.
 -UPDATE ENERGY CALCULATIONS FOR THE EXISTING FLOOR TYPE
 AND R-VALUE)
  
 3) 408.1 [R] VENTILATION. THE UNDER-FLOOR SPACE BETWEEN
 THE BOTTOM OF THE FLOOR JOISTS AND THE EARTH UNDER ANY
 BUILDING (EXCEPT SPACE OCCUPIED BY A BASEMENT) SHALL
 HAVE VENTILATION OPENINGS THROUGH FOUNDATION WALLS OR
 EXTERIOR WALLS.
 -PLEASE PROVIDE THE AMOUNT OF EXISTING UNDER FLOOR
 VENTILATION AND SHOW WHERE ACCESS PANEL IS LOCATED.
  
  
 4) 806.5 [R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES.
 5.1.2. WHERE AIR-PERMEABLE INSULATION IS PROVIDED
 INSIDE THE BUILDING THERMAL ENVELOPE, IT SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 5.1.1. IN ADDITION
 TO THE AIR-PERMEABLE INSULATION INSTALLED DIRECTLY
 BELOW THE STRUCTURAL SHEATHING, RIGID BOARD OR SHEET
 INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE
 STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH THE
 R-VALUES IN TABLE R806.5 FOR CONDENSATION CONTROL.
 -PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE
 INSULATION AT ROOF DECK.
  
 5) 107 5.3 [AMENDED] PROVIDE PRODUCT APPROVAL FOR HARDI
 PLANK SIDING AND STATE ATTACHMENT TYPE AND SPACING, OR
 INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
  
 6) 905.11.1 [R] SLOPE. MODIFIED BITUMEN MEMBRANE ROOFS
 SHALL
 HAVE A DESIGN SLOPE OF NOT LESS THAN ONE-FOURTH UNIT
 VERTICAL
 IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE.
 -UPDATE SHEET S-06 TO SHOW MINIMUN SLOPE AS REQ?D
 905.11.1 [R].
  
 7) [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR
 LOW SLOPE ROOFING, OR INDICATE THAT YOU WOULD LIKE IT
 DEFERED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-04-29 Cont ID  
Sent By jpearson Date 2019-04-29 Time 10:05 Rev Time 0.00
Received By jpearson Date 2019-04-29 Time 07:13 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By jpearson Date 2018-12-14 Time 15:49 Rev Time 0.00
Received By jpearson Date 2018-12-14 Time 13:22 Sent To  
Notes
2018-12-14 15:49:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE 25 AND NOTE IN SYMBOLS LEGEND STATES THAT
 RECEPTACLES SHALL BE TAMPER RESISTANT PER NEC 406.11.
 THIS CODE SECTION DOES NOT APPLY TO TAMPER RESISTANT
 RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; FBC RE
 E4002.14
 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. NEC 220; FBC RE E3602.2
 3. A MINIMUM OF TWO SMALL APPLIANCE BRANCH CIRCUITS IS
 REQUIRED FOR KITCHEN COUNTER TOP RECEPTACLE OUTLETS.
 THE LIGHTING IN THE KITCHEN IS NOT PERMITTED TO BE ON
 ONE OF THE SMALL APLLIANCE CIRCUITS. PROVIDE
 CORRECTION. NEC 210.11(C)(1) , FBC RE E3703.2
 4. THE DRYER LOAD IS NOT SHOWN IN PANEL SCHEDULE OR
 LOAD CALCULATION. PROVIDE CORRECTION. NEC 220.54; FBC
 RE E3602.2
 5. ITEMS MARKED WITH AN ASTERIK IN PANEL SCHEDULE FOR
 AFCI PROTECTION DO NOT INCLUDE ALL AREAS REQUIRED TO BE
 AFCI PROTECTED. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC
 RE E3902; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS
 APPLICABLE.
 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 7. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 8. SMOKE ALARMS SHOULD NOT BE INSTALLED WITHIN CERTAIN
 DISTANCES FROM THE RANGE, DEPENDING ON THE TYPE OF
 SMOKE ALARM USED. SEE FBC RE R314.3.1 AND PROVIDE
 CORRECTION.
 9. ALL KITCHEN COUNTER RECEPTACLE OUTLETS ARE REQUIRED
 TO BE GFCI PROTECTED ON AN AFCI CIRCUIT. PROVIDE
 CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 10. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 11. PLAN SHOWS #8 WIRE ON A 50 AMP BREAKER FOR THE
 RANGE. #8 ROMEX WIRE, WHICH IS TYPICAL IN RESIDENTIAL
 WIRING, IS NOT RATED FOR 50 AMPS. PROVIDE CORRECTION.
 NEC 334.80; FBC RE E3705.4.4
 12. A GFCI PROTECTED RECEPTACLE OUTLET IS REQUIRED ON
 THE ISLAND. PROVIDE CORRECTION. NEC 210.8,
 210.52(C)(2); FBC RE E3901.4.2
 13. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 14. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9,
 110.10; FBC RE E3606.3
 15. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3606.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 14:30 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 14:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 15:46 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 15:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By lcrespo Date 2019-01-02 Time 15:57 Rev Time 0.00
Received By lcrespo Date 2019-01-02 Time 15:57 Sent To  
Notes
2019-01-02 16:08:2901/02/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1. ON THE FORM FOR YOUR ENERGY CONSERVATION R405-2017
 ITEM 14B. EFFICIENCY IS .60 AND, .62 IS WHAT IS CALLED
 OUT PER 2017 FBC EC TABLE C 404.2 ASSUMING IT IS AN
 INSTANTANEOUS WATER HEATER, GAS > 50,000 BTU/H AND <
 200,000 BTU/HC, PLEASE CORRECT ACCORDINGLY WITH NEW
 ENERGY CALCULATIONS, WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. THE PLANS ON PAGE S-3 CALL FOR A GAS WATER HEATER
 BUT ON THE ENERGY CALCULATION IT REFERS TO AN ELECTRIC
 1 GALLON TANKLESS, PLEASE CLARIFY AS WHICH ONE WILL BE
 USED.
 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS RES SECS. G2413.4.1, G2413.4.2.
 4. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (TO
 VERIFY COMPLIANCE WITH INSTANTANEOUS WATER HEATERS),
 GAS 2017 FBC FUEL GAS RES. SEC. G2408.1.
 5. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. PLEASE PUT THE TYPE OF GAS ON ISOMETRIC AND SHOW
 METER (LP OR NATURAL). WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE ISOMETRIC PLAN PER 2017 FBC FUEL GAS RES. SEC.
 G2413.2.
 8. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 9. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
 10. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
 11. THE TANKLESS WATER HEATER AND THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 12. A SUB ELECTRICAL OUTLET MAY BE REQUIRED FOR THE
 SOURCE OF IGNITION, WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-08 Cont ID  
Sent By cmontell Date 2019-05-08 Time 13:12 Rev Time 0.00
Received By cmontell Date 2019-05-08 Time 13:12 Sent To  
Notes
2019-05-06 16:38:57R31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-04-29 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-11 Time 16:08 Sent To  
Notes
2019-04-12 16:08:28R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-03 Cont ID  
Sent By cmontell Date 2019-01-03 Time 09:18 Rev Time 0.00
Received By cmontell Date 2019-01-03 Time 09:18 Sent To  
Notes
2018-12-03 11:08:15R12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-08 Cont ID  
Sent By cmontell Date 2019-05-08 Time 13:12 Rev Time 0.00
Received By cmontell Date 2019-05-08 Time 13:12 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-04-15 Cont ID  
Sent By cmontell Date 2019-04-15 Time 13:33 Rev Time 0.00
Received By cmontell Date 2019-04-15 Time 13:18 Sent To  
Notes
2019-04-15 13:32:30MECHANICAL PLAN REVIEW FAIL
  
 1 NEED RETURN DUCTS IN BEDROOMS PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. M1602.3 BALANCED
 RETURN AIR. MASTER BEDROOM AND GUEST BEDROOM SHOWING
 8"SUPPLY AND 4" JUMPER FROM ROOM TO ROOM RETURN AIR
 NEEDS TO BE RETURNED TO AIR HANDLER, DEN HAS NO DUCT
 SIZE ON JUMPER FLEX DUCT.
  
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
  
 EXCEPTIONS:
 1.TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 2.TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGHTHE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 3.HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By cmontell Date 2019-01-03 Time 09:17 Rev Time 0.00
Received By cmontell Date 2019-01-03 Time 08:31 Sent To I
Notes
2019-01-03 09:17:07MECHANICAL PLAN REVIEW FAIL
  
 1 NEED RETURN DUCTS IN BEDROOMS PER 2017 FLORIDA
 BUILDING CODE - RESIDENTIAL SEC. 2017 FLORIDA BUILDING
 CODE - RESIDENTIAL
  
 2 PLEASE EXPLAIN DESIGN - HOW IS FLEX DUCT ATTACHED TO
 FLEX DUCT - NEED SIZE ON ALL DUCTS PER 2017 FLORIDA
 BUILDING CODE - BUILDING SEC. [A]107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
  
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-07 Cont ID  
Sent By thunt Date 2019-05-07 Time 14:30 Rev Time 0.00
Received By thunt Date 2019-05-07 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-04-16 Cont ID  
Sent By thunt Date 2019-04-16 Time 15:46 Rev Time 0.00
Received By thunt Date 2019-04-16 Time 15:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By lcrespo Date 2019-01-02 Time 15:56 Rev Time 0.00
Received By lcrespo Date 2019-01-02 Time 15:56 Sent To  
Notes
2019-01-02 15:57:2001/02/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ACCORDING TO MANUFACTURES SPECIFICATION ON AN AIR
 ADMITTANCE VALVE FOR THE WASHING MACHINE, IT NEEDS TO
 BE A 3? STANDPIPE, 2017 FBC SEC R P3114.2 INSTALLATION.
 2. STANDPIPE ISOMETRIC DRAWING S-7 REQUIRES A TRAP THEN
 VENT TO AAV, 2017 FBC SEC. R3101.2 TRAP SEALS
 PROTECTION.
 3. HOT WATER UNDERGROUND REQUIRES R-13 INSULATION
 ACCORDING TO 2017 FBC SEC. RE 403.5.3.
 4. IF THE SHOWER PAN IS NOT RECEDED IT WILL REQUIRE
 LINING, 2017 FBC SEC. R 2709.2.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-05-08 Cont ID  
Sent By dbattles Date 2019-05-08 Time 08:29 Rev Time 0.00
Received By dbattles Date 2019-05-08 Time 08:29 Sent To  
Notes
2019-05-08 08:33:46SUBMITTAL OF PRODUCT APPROVALS NEEDED AT TIME OF
 ROOFING SUB PERMIT.
 WHILE A PRODUCT APPROVAL WAS SUBMITTED WITHE THE
 PRIMARY PERMIT(18-0919.07), NO SYSTEM WAS SELECTED FROM
 IT AS REQUESTED IN THE SECOND REVIEW.
 ALSO, PROVIDE FOR ENHANCED NAILING AS REQUIRED FORN
 LIMITATION #7.

Review Stop Z ZONING
Rev No 2 Status P Date 2019-04-26 Cont ID  
Sent By mcruz Date 2019-04-26 Time 07:35 Rev Time 0.00
Received By mcruz Date 2019-04-25 Time 17:00 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-18 Cont ID  
Sent By mcurz Date 2018-12-18 Time 09:45 Rev Time 0.00
Received By mcruz Date 2018-12-18 Time 08:51 Sent To PC
Notes
***NONE***