Plan Review Details - Permit 18111201
Plan Review Stops For Permit 18111201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By rmcdouga Date 2018-12-21 Time 07:40 Rev Time 0.00
Received By rmcdouga Date 2018-12-21 Time 07:40 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2018-12-10 Cont ID  
Sent By rmcdouga Date 2018-12-10 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2018-12-10 Time 13:02 Sent To  
Notes
2018-12-10 13:02:54SEE DEFFERED SUBMITTAL UNDER PERMIT # 18120188.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By rmcdouga Date 2018-12-03 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2018-12-03 Time 18:15 Sent To I
Notes
2018-12-03 18:49:32PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SYSTEM A - PRODUCT APPROVAL FL16730-R17, FOR THE
 EVERGUARD TPO SINGLE-PLY ROOF MEMBRANE SYSTEM SYSTEM
 NUMBER S-106 ON PAGE 26 OF 86 HAS A MAXIMUM DESIGN
 PRESSURE OF -45.0 PSF AND IS MARKED WITH AN ASTERISK.
 ACCORDING TO NOTE #9 ON PAGE 3 OF 86 INCREASED FASTENER
 DENSITY EXTRAPOLATION IS NOT PERMITTED FOR SYSTEMS THAT
 ARE MARKED WITH AN ASTERISK *. SUBMIT ROOFING PRODUCT
 APPROVALS WITH ADEQUATE DESIGN PRESSURES. FBC 1609.1
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED HAVE NOT
 BEEN APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THIS PROJECT. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
  
 3) THREE SETS OF CONSTRUCTION DOCUMENTS ARE TYPICALLY
 SUBMITTED FOR THRESHOLD BUILDINGS. IF YOU WISH TO HAVE
 A SET OF PLANS FOR THE THRESHOLD INSPECTOR, YOU WILL
 HAVE TO SUBMIT AN ADDITIONAL SET OF DOCUMENTS. FBC
 107.1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-03 Cont ID  
Sent By rmcdouga Date 2018-12-03 Time 18:15 Rev Time 0.00
Received By rmcdouga Date 2018-11-29 Time 14:04 Sent To  
Notes
2018-11-30 14:04:23RMCDOUGAL