Plan Review Details - Permit 18111153
Plan Review Stops For Permit 18111153
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 10:28 Rev Time 0.00
Received By tklarge Date 2018-12-19 Time 11:48 Sent To  
Notes
2018-12-20 11:48:50RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By tklarge Date 2018-12-11 Time 15:01 Rev Time 0.00
Received By tklarge Date 2018-11-28 Time 13:02 Sent To  
Notes
2018-11-29 13:02:53ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-26 Cont ID  
Sent By tklarge Date 2018-12-26 Time 10:28 Rev Time 0.00
Received By tklarge Date 2018-12-26 Time 10:18 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By tklarge Date 2018-12-11 Time 15:01 Rev Time 0.00
Received By tklarge Date 2018-12-11 Time 14:16 Sent To I
Notes
2018-12-11 15:01:301) THE PRINTING ON THE SUBMITTED PLANS IS ILLEGIBLE.
 SUBMIT TWO SETS OF LEGIBLE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 2) SUBMIT LEGIBLE GREASE TRAP SIZING CALCULATIONS FOR
 REVIEW.2017 FBC-PLUMBING SEC. 1003.2.
 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION FOR REVIEW. WPB AMEND.
 TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  