Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-30 Cont ID  
Sent By fgiaquin Date 2018-11-30 Time 07:13 Rev Time 0.00
Received By fgiaquin Date 2018-11-30 Time 06:56 Sent To I
Notes
2018-11-30 07:13:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE UL OR OTHER NRTL LISTINGS FOR EQUIPMENT.
 90,7, 110.2, 110.3B NEC
  
 2. WHERE IS WORK BEING PERFORMED. PERMIT APP ONLY SAYS
 250 S AUSTRALIAN.. SUITE #??? FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-30 Cont ID  
Sent By fgiaquin Date 2018-11-30 Time 07:14 Rev Time 0.00
Received By fgiaquin Date 2018-11-28 Time 13:54 Sent To  
Notes
2018-11-29 13:54:50ROUTED TO ELECTRICAL INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved