Plan Review Details - Permit 18111084
Plan Review Stops For Permit 18111084
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-06 Cont ID  
Sent By pvalenti Date 2019-02-06 Time 10:52 Rev Time 0.00
Received By pvalenti Date 2019-02-06 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-31 Cont ID  
Sent By pvalenti Date 2018-12-31 Time 07:14 Rev Time 0.00
Received By pvalenti Date 2018-12-31 Time 07:14 Sent To  
Notes
2018-12-31 07:26:32PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED AS NOTED
  
 NOTES:
  
 1. THE CONTRACTOR STILL NEEDS TO BE DETERMINED.
 2. SEPERATE PERMITS STILL NEED TO BE OBTAINED FOR THE
 KITCHEN HOOD AND HOOD SUPPRESSION.
 3. THE COUNTY IMPACT FEES STILL NEED TO BE ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-03 Cont ID  
Sent By jpearson Date 2019-02-03 Time 13:25 Rev Time 0.00
Received By jpearson Date 2019-02-03 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-12 Cont ID  
Sent By jpearson Date 2018-12-12 Time 13:01 Rev Time 0.00
Received By jpearson Date 2018-12-11 Time 11:03 Sent To  
Notes
2018-12-12 13:01:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. ONE PERMIT APPLICAITON STATES $200,000 FOR VALUE,
 ANOTHER STATES $50,000. PROVIDE COPY OF SIGNED CONTRACT
 WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS
 AND LABOR. THIS IS FOR TOTAL PROJECT, NOT JUST
 ELECTRICAL. FBC 109.3
 2. RISER DIAGRAM SHOWS PANEL KP3 FED FROM PANEL KP2.
 THE PANEL SCHEDULES SHOW IT FED FROM KP1. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS. WPB FBC 107.2.1
 3. ALL KITCHEN RECEPTACLES, INCLUDING DROP CORDS,
 REQUIRED GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8
 4. HOT WATER HEATERS IN PANELS A AND KP2 SHOULD BE
 CALCULATED AS A CONTINUOUS LOAD. PROVIDE CORRECTION.
 NEC 422.13
 5. BASED ON SITE VISIT BY INSPECTOR, THE EXISTING RISER
 DIAGRAM DOES NOT APPEAR TO BE CORRECT AS SHOWN. THIS
 RISER DIAGRAM EVEN DIFFERS FROM THE ONE PROVIDED FOR
 PERMIT 18050930. IF THERE IS ADDITIONAL WORK TO THE
 SERVICE PLANNED, PROVIDE AN ACCURATE EXISTING RISER
 DIAGRAM AS WELL AS A PROPOSED RISER DIAGRAM. THERE
 SHOULD BE MAIN DISCONNECTS PER NEC 230.70(A). NEC
 215.5, 230.70, 230.71, 230.72; WPB FBC 107.2.1
 6. PROVIDE LOCATION OF SERVICE AND PANELS ON PLAN. WPB
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-07 Cont ID  
Sent By pleduc Date 2018-12-07 Time   Rev Time 0.00
Received By pleduc Date 2018-12-07 Time 11:24 Sent To  
Notes
2018-12-07 11:27:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE PLAN SHEETS INDICATING A KITCHEN HOOD AND
 SUPPRESSION SYSTEMS.
  
 THESE SYSTEMS SHALL BE SUBMITTED UDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 PLEASE ENSURE THAT PERMITS ARE SUBMITTED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By jesmith Date 2019-01-08 Time 13:41 Rev Time 0.00
Received By jesmith Date 2019-01-08 Time 12:40 Sent To  
Notes
2019-01-08 13:41:15A REVIEW HAS BEEN CONDUCTED OF THE SUBMITTED PLANS AND
 THE FOLLOWING COMMENTS APPLY:
  
 1. A GAS PERMIT IS REQUIRED PER WPB FBC SECTION 105.
  
 2. RE: PLAN SHEET P-2.2; INDICATE DELIVERY PRESSURE OF
 SYSTEM IN THE GAS SIZING CALCULATIONS PER WPB FBC
 107.2.1.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT PER WPB FBC
 107.2.1 TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG 402.2, AND 301. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION PER FBC FG 305.1. THE
 MANUFACTURER?S SPECIFICATION SHEETS / INSTALLATION
 MANUAL SUBMITTAL MAY BE DEFERRED TO A LATER DATE IN
 ACCORDANCE WITH THE PROVISIONS OF WPB FBC 107.3.4.1 ARE
 AS FOLLOW:
 A. 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-06 Cont ID  
Sent By pvalenti Date 2019-02-06 Time 10:52 Rev Time 0.00
Received By pvalenti Date 2019-01-16 Time 15:53 Sent To  
Notes
2019-01-17 15:53:27B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By jesmith Date 2019-01-08 Time 15:35 Rev Time 0.00
Received By jesmith Date 2019-01-08 Time 15:35 Sent To  
Notes
2018-11-29 15:47:34B15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2019-01-02 Cont ID  
Sent By pvalenti Date 2018-12-31 Time 07:30 Rev Time 0.00
Received By pvalenti Date 2018-12-31 Time 07:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-31 Cont ID  
Sent By ccole Date 2019-01-31 Time 11:37 Rev Time 0.00
Received By ccole Date 2019-01-31 Time 11:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-18 Cont ID  
Sent By ccole Date 2018-12-18 Time 17:41 Rev Time 0.00
Received By ccole Date 2018-12-18 Time 16:41 Sent To  
Notes
2018-12-18 17:53:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111084
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.2 ADVISORY: AS NOTED ON THE PLAN, A
 SEPARATE PERMIT IS REQUIRED FOR THE KITCHEN EXHAUST
 HOOD, HOWEVER AN EYEBROW HOOD IS NOT PERMITTED FOR USE
 OVER HEAVY DUTY COOKING APPLIANCES- SECTIONS 507.5.2
 AND 202 FBC M.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES- SECTION 623.1 FBC FG.
  
 3) M-2.2: MAKEUP AIR FOR THE HOOD EXHAUST CANNOT BE
 USED AS COMBUSTION AIR FOR THE GAS-FIRED APPLIANCES-
 SEE SECTION 304.9.3 FBC FG.
  
 4) M-2.2: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY AIR SYSTEM OF THE 5-TON AHU-1 PER SECTION
 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE
 APPLIED IF THE MANUFACTURER'S SPECIFICATIONS INDICATE
 THE AIR HANDLER IS NOT CAPABLE OF PRODUCING OVER 2000
 CFMS OF SUPPLY AIR.
  
 5) M.2-2: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.3
 FBC EC.
  
 6) M-2.2: PROVIDE ACCESS PANELS FOR THE ABOVE CEILING
 AIR HANDLERS- SECTION 306.1 FBC M.
  
 7) M-2.2: PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW
 AIR HANDLERS- SECTION 307.2.1 FBC M.
  
 8) ENERGYGAUGE REPORT; THE COOLING SYSTEM CAPACITY
 LISTED ON THE FORM FOR SYSTEM 2 DOES NOT MATCH THE
 CAPACITY OF THE SYSTEM ON THE PLAN, AND MISSING FROM
 THE REPORT IS SYSTEM 3.
  
 9) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE KITCHEN EXHAUST HOOD, FIRE SUPPRESSION SYTEM, AND
 THE WALKIN COOLER AND FREEZER.
  
 10) CLARIFY HOW THE MUA UNIT WAS SIZED FOR THE KITCHEN
 HOOD EXHAUST SYSTEM- PROVIDE A CALCULATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-08 Cont ID  
Sent By jesmith Date 2019-01-08 Time 15:35 Rev Time 0.00
Received By jesmith Date 2019-01-08 Time 12:19 Sent To  
Notes
2019-01-08 15:34:49APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. RE: KITCHEN EQUIPMENT; HOT FOOD WELLS
 A. EACH FOOD WELL SHALL INDEPENDENTLY DISCHARGE TO A
 WASTE RECEPTOR PER FBC PL 802.1.1.
  