Plan Review Details - Permit 18111061
Plan Review Stops For Permit 18111061
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By pvalenti Date 2019-01-02 Time 13:19 Rev Time 0.00
Received By pvalenti Date 2019-01-02 Time 13:19 Sent To  
Notes
2019-01-02 13:22:58****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION: MISSING
 COMPLETE DETAILS FOR CONNECTING EQUIPMENT TO EXISTING
 WOOD POLE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-17 Cont ID  
Sent By jleahy Date 2018-12-17 Time 10:38 Rev Time 0.00
Received By jleahy Date 2018-12-17 Time 10:38 Sent To Z
Notes
2018-12-17 10:39:19NEED A SIGNED COPY OF THE CONTRACT FOR JOB INCLUDING
 ALL MATERIALS AND LABOR. JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-02 Cont ID  
Sent By pvalenti Date 2019-01-02 Time 13:23 Rev Time 0.00
Received By pvalenti Date 2018-11-27 Time 11:32 Sent To  
Notes
2018-11-29 11:33:00ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By eschneid Date 2018-12-19 Time 15:38 Rev Time 0.50
Received By eschneid Date 2018-12-19 Time 15:38 Sent To B
Notes
2018-12-19 16:20:07FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PLEASE PROVIDE VERIFICATION IN THE FORM OF A SURVEY
 TO VERIFY THAT THE PROPOSED FACILITIES ARE LOCATED
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
 THE SUPPLIED PLAN IS SIGNED AND SEALED BY AN ENGINEER,
 NOT A SURVEYOR. THE BACK OF A SIDEWALK IS TYPICALLY THE
 BOUNDARY BETWEEN THE RIGHT-OF-WAY AND THE PRIVATE
 PROPERTY, BUT THE PLAN SHOWS THE SIDEWALKS LOCATED AWAY
 FROM THE PROPERTY LINE.
  
 2) PROVIDE CONSENT FROM FPL, THE OWNER OF THE UTILITY
 POLE, THAT PERMITS THE PLACEMENT OF THE ANTENNAS AND
 RELATED EQUIPMENT ON IT.
  
 3) THE CITY REQUIRES THAT THE EQUIPMENT CABINETS
 (UTILITY METER, DISCONNECT AD NEMA BOX) BE SCREENED BY
 LANDSCAPE. PLEASE SHOW HOW THIS WILL OCCUR. NOTE: WHILE
 THE PLANS CALL THE EQUIPMENT CABINETS' HEIGHT AT A
 MAXIMUM OF SIX (6) FEET, PLEASE CONSIDER HAVING THEM
 MOUNTED ON A SHORTER POLE TO MINIMIZE THE VISUAL IMPACT
 (A LOWER LANDSCAPE SCREEN COULD THEN BE USED).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
2018-11-30 08:19:27ROUTED TO AJV
 MC