Plan Review Details - Permit 18111060
Plan Review Stops For Permit 18111060
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jduprey Date 2019-01-03 Time 09:29 Rev Time 0.00
Received By jduprey Date 2019-01-03 Time 09:28 Sent To  
Notes
2019-01-03 09:29:17BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLEASE PROVIDE DETAILS OF HOW THE ANTENNA WILL BE
 ATTACHED TO THE POLE (E.I. SCREW TYPE, AMOUNT,
 LOCATION, ETC..), ALSO PROVIDE CALCULATIONS FOR WIND
 SPEED. FBC 107
  
 2. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. YOU MAY PROVIDE A COPY OF THE
 CONTRACT SIGNED BY THE OWNER OR A LIST OF LABOR,
 MATERIALS AND EQUIPMENT RENTAL TO VERIFY VALUE. CITY OF
 WPB CHAPTER 109.3
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-17 Cont ID  
Sent By jleahy Date 2018-12-17 Time 13:33 Rev Time 0.00
Received By jleahy Date 2018-12-17 Time 13:33 Sent To Z
Notes
2018-12-17 13:35:10NEED A SIGNED COPY OF THE CONTRACT FOR JOB INCLUDING
 ALL MATERIALS AND LABOR. JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-03 Cont ID  
Sent By jduprey Date 2019-01-03 Time 09:29 Rev Time 0.00
Received By jduprey Date 2018-11-27 Time 11:31 Sent To  
Notes
2018-11-29 11:31:41ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By eschneid Date 2018-12-19 Time 17:01 Rev Time 0.50
Received By eschneid Date 2018-12-19 Time 17:01 Sent To B
Notes
2018-12-19 17:06:41FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) PLEASE PROVIDE VERIFICATION IN THE FORM OF A SURVEY
 TO VERIFY THAT THE PROPOSED FACILITIES ARE LOCATED
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
 THE SUPPLIED PLAN IS SIGNED AND SEALED BY AN ENGINEER,
 NOT A SURVEYOR. THE BACK OF A SIDEWALK IS TYPICALLY THE
 BOUNDARY BETWEEN THE RIGHT-OF-WAY AND THE PRIVATE
 PROPERTY, SO THE POLE AND PROPOSED EQUIPMENT THAT ARE
 SHOWN NOT WITHIN THE SIDEWALK MAY BE ON PRIVATE
 PROPERTY.
  
 2) PROVIDE CONSENT FROM FPL, THE OWNER OF THE UTILITY
 POLE, THAT PERMITS THE PLACEMENT OF THE ANTENNAS AND
 RELATED EQUIPMENT ON IT.
  
 3) ANY PORTION OF THE ANTENNA OR EQUIPMENT THAT IS ON
 PRIVATE PROPERTY IS NOT LOCATED WITHIN THE RIGHT-OF-WAY
 AND REQUIRES THE APPROVAL OF A CITY PRIVATE PROPERTY
 WIRELESS COMMUNICATION PERMIT IN ACCORDANCE WITH
 ARTICLE X OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS. PLEASE CONTACT ME FOR A COPY OF THE
 WIRELESS COMMUNICATION PERMIT APPLICATION.
  
 4) THE CITY REQUIRES THAT THE EQUIPMENT CABINETS
 (UTILITY METER, DISCONNECT AND NEMA BOX) BE SCREENED,
 IN THIS CASE WITH A DECORATIVE WRAP. PLEASE SHOW HOW
 THIS WILL OCCUR. NOTE: WHILE THE PLANS CALL THE
 EQUIPMENT CABINETS' HEIGHT AT A MAXIMUM OF SIX (6)
 FEET, PLEASE CONSIDER HAVING THEM MOUNTED ON A SHORTER
 POLE TO MINIMIZE THE VISUAL IMPACT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
2018-11-30 08:19:48ROUTED TO AJV
 MC