Plan Review Details - Permit 18111038
Plan Review Stops For Permit 18111038
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-10-04 Cont ID  
Sent By pvalenti Date 2019-10-04 Time 07:25 Rev Time 0.00
Received By pvalenti Date 2019-10-04 Time 07:25 Sent To  
Notes
2019-10-04 07:28:10PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD BUILDING REVIEW APPROVED WITH PROVISO:
  
 FBC B 107.3.4 AT TIME OF INSPECTION, PROVIDE PRODUCT
 APPROVALS WITH THE DESIGNER OF RECORD'S REVIEW STAMP
 AND SIGNATURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-08-26 Cont ID  
Sent By jwitmer Date 2019-08-26 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2019-08-26 Time 07:38 Sent To  
Notes
2019-09-09 16:36:22PLEASE NOTE, EVALUATE REVOKING 10080004,
 04030624,03110409, 18040048 WHILE PERFORMING 3RD
 REVIEW.
2019-08-26 07:51:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18111038
 ADD: 124 N DIXIE HWY.
 CONT: GARBER CONSTRUCTION
 TEL: 561-929-2505
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. AUGUST 26, 2019
 ACTION: DENIED
  
 *******************4X FEE / NOTICE!!!!! FLORIDA STATUTE
 553.80(2)(B) **************************
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS'
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) 2ND REQUEST. THE ARCHITECTURAL SHEET 1.0A NOTE 9
 INDICATES THE REMOVAL OF THE FRONT ENTRY DOOR AND SIDE
 ENTRY DOOR.
 THE PLANS INDICATE TO CREATE A NEW RECESSED DOUBLE
 GLASS DOOR SYSTEM IN THE FRONT OF THE BUILDING. THE
 PRODUCT APPROVAL SUBMITTED A MIAMI-DADE NOA SERIES
 "SE-3550" OUTSWING DOOR WAS SUBMITTED. PLEASE NOTE
 COMPLIANCE WITH W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2ND REQUEST. PLEASE NOTE THE MIAMI-DADE NOA SERIES
 "SE-3550" NOA # 17-1114.01 HAS 15 PAGES OF TECHNICAL
 PAGES. PAGE 11 OF 15 HAS LOCKING DETAILS 3, 4, & 5
 WHEREAS PAGE 6 OF 15 HAS LOCKING OPTIONS 1, 2 & 6. THE
 OPTIONS ON PAGE 6 ARE ALL PANIC HARDWARE. PLEASE NOTE
 NEITHER THE CONTRACTOR NOR THE DESIGNER OF RECORD HAVE
 CIRCLED WHICH LOCKING OPTION AND ASSOCIATE PRESSURE ARE
 TO BE INSTALLED.
 PLEASE PROVIDE COMPLIANCE WITH THE 2017 FBC-B 1010.1.10
 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING AN OCCUPANT
 LOAD OF 50 OR MORE IN A GROUP A SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK OTHER THAN PANIC HARDWARE OR FIRE
 EXIT HARDWARE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-18 Cont ID  
Sent By jwitmer Date 2018-12-18 Time 12:38 Rev Time 0.00
Received By jwitmer Date 2018-12-17 Time 14:23 Sent To  
Notes
2018-12-18 12:38:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18111038
 ADD: 124 N DIXIE HWY.
 CONT: GARBER CONSTRUCTION
 TEL: 561-929-2505
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 18/2018
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEET 1.0A NOTE 9 INDICATES THE
 REMOVAL OF THE FRONT ENTRY DOOR AND SIDE ENTRY DOOR.
 THE PLANS INDICATE TO CREATE A NEW RECESSED DOUBLE
 GLASS DOOR SYSTEM IN THE FRONT OF THE BUILDING. THE
 PRODUCT APPROVAL SUBMITTED A MIAMI-DADE NOA SERIES
 ?SE-3550? OUTSWING DOOR WAS SUBMITTED. PLEASE NOTE
 COMPLIANCE WITH W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) PLEASE NOTE THE MIAMI-DADE NOA SERIES ?SE-3550? NOA
 # 17-1114.01 HAS 15 PAGES OF TECHNICAL PAGES. PAGE 11
 OF 15 HAS LOCKING DETAILS 3, 4, & 5 WHEREAS PAGE 6 OF
 15 HAS LOCKING OPTIONS 1, 2 & 6. THE OPTIONS ON PAGE 6
 ARE ALL PANIC HARDWARE. PLEASE NOTE NEITHER THE
 CONTRACTOR NOR THE DESIGNER OF RECORD HAVE CIRCLED
 WHICH LOCKING OPTION AND ASSOCIATE PRESSURE ARE TO BE
 INSTALLED.
 PLEASE PROVIDE COMPLIANCE WITH THE 2017 FBC-B 1010.1.10
 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A OCCUPANT
 LOAD OF 50 OR MORE IN A GROUP A SHALL NOT BE PROVIDED
 WITH A LATCH OR LOCK OTHER THAN PANIC HARDWARE OR FIRE
 EXIT HARDWARE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-08-23 Cont ID  
Sent By jpearson Date 2019-08-23 Time 15:27 Rev Time 0.00
Received By jpearson Date 2019-08-23 Time 15:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By jpearson Date 2018-12-11 Time 12:42 Rev Time 0.00
Received By jpearson Date 2018-12-11 Time 11:03 Sent To  
Notes
2018-12-11 12:42:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN REVIEW NEEDS AN ELECTRICAL PERMIT
 APPLICATION FROM AN ELECTRICAL CONTRACTOR FOR APPROVAL.
 PLEASE EMAIL THE ELECTRICAL PERMIT APPLICATION TO
 [email protected] AND CC [email protected] AND
 [email protected] SO WE RECEIVE IT ALSO. WHEN THIS EMAIL
 IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE PLAN
 REVIEW. THE ORIGINAL PERMIT APPLICATION MUST BE
 SUBMITTED WHEN THE PERMIT IS PICKED UP. WPB FBC 105.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-08-09 Cont ID  
Sent By pleduc Date 2019-08-09 Time   Rev Time 0.00
Received By pleduc Date 2019-08-09 Time 13:26 Sent To  
Notes
2019-08-09 13:33:11APPLICATION HAS ADDRESS OF 124 N DIXIE HWY - PLAN
 SHEETS HAVE 124 BANYAN
  
 NEED TO CONFIRM WHICH ADDRESS IS CORRECT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By scaldero Date 2018-12-06 Time 10:54 Rev Time 0.00
Received By scaldero Date 2018-12-06 Time 10:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-10-04 Cont ID  
Sent By pvalenti Date 2019-10-04 Time 07:28 Rev Time 0.00
Received By pvalenti Date 2019-09-24 Time 13:26 Sent To  
Notes
2019-09-25 13:27:46RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-09-18 Cont ID  
Sent By cpuell Date 2019-09-18 Time 16:36 Rev Time 0.00
Received By cpuell Date 2019-08-07 Time 14:22 Sent To  
Notes
2019-09-17 15:50:04ZONING PASSED ON 8/20/2019 BUT WAS NOT IN SYSTEM.
 PASSED IN SYSTEM ON 9/17/19
  
 ROUTED FROM ZONING TO PERMIT LIBRARIAN 9/17/19 EL
2019-08-08 14:22:41B09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By jesmith Date 2019-01-08 Time 12:08 Rev Time 0.00
Received By jesmith Date 2019-01-08 Time 12:08 Sent To  
Notes
2018-12-05 09:41:28ROUTED FROM ZONING TO PERMIT LIBRARIAN 12/5/18
2018-11-28 13:38:52B24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-09-10 Cont ID  
Sent By hmoser Date 2019-09-10 Time 13:55 Rev Time 0.00
Received By hmoser Date 2019-09-10 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-18 Cont ID  
Sent By ccole Date 2018-12-18 Time 16:16 Rev Time 0.00
Received By ccole Date 2018-12-18 Time 16:16 Sent To  
Notes
2018-12-18 16:30:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111038
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) MECHANICAL PLAN REVIEW REQUIRES A MECHANICAL PERMIT
 APPLICATION FROM A FL. LICENSED MECHANICAL OR AC
 CONTRACTOR FOR APPROVAL.
  
 PLEASE EMAIL THE APPLICATION TO [email protected], AND TO
 [email protected] FOR PLAN REVIEW APPROVAL. THE ORIGINAL
 PERMIT APPLICATION MUST BE SUBMITTED WHEN THE PERMIT IS
 PICKED UP- SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-08-27 Cont ID  
Sent By jesmith Date 2019-08-27 Time 13:54 Rev Time 0.00
Received By jesmith Date 2019-08-27 Time 13:54 Sent To  
Notes
2019-08-27 13:54:51PLUMBING COMMEMTS: APPROVED W/PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2.PER FBC PL 912.1, ONLY BATHROOM GROUP FIXTURES MAY
 CONNECT TO THE WET VENT. CONNECT EWC DOWNSTREAM OF THE
 WET VENT AS RED LINED ON PLAN SHEET 3.0P.
 3. PER FBC PL 416.5, PROVIDE TEMPERED WATER TO EACH
 LAVATORY THROUGH AN APPROVED TEMPERATURE LIMITING
 DEVICE CONFORMING TO ASSE 1070 OR CSA B125.3 AS RED
 LINED ON PLAN SHEET 3.0P.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By jesmith Date 2019-01-08 Time 12:08 Rev Time 0.00
Received By jesmith Date 2019-01-08 Time 11:40 Sent To  
Notes
2019-01-08 12:08:16CODES IN EFFECT
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS
  
 1. PLUMBING PLAN REVIEW REQUIRES A PLUMBING PERMIT
 APPLICATION FROM A FLORIDA LICENSED PLUMBING CONTRACTOR
 FOR APPROVAL.PLEASE EMAIL THE APPLICATION TO
 [email protected], AND CC TO [email protected] FOR PLAN
 REVIEW APPROVAL. THE ORIGINAL PERMIT APPLICATION MUST
 BE SUBMITTED WHEN THE PERMIT IS PICKED UP- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 2 Status P Date 2019-09-17 Cont ID  
Sent By elevesqu Date 2019-09-17 Time 15:49 Rev Time 0.00
Received By elevesqu Date 2019-09-17 Time 15:49 Sent To  
Notes
2019-09-17 15:49:24STAMPED ON AUGUST 20, 2019

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-05 Cont ID  
Sent By elevesqu Date 2018-12-05 Time 09:41 Rev Time 0.00
Received By elevesqu Date 2018-12-05 Time 09:39 Sent To  
Notes
2018-12-05 09:41:05PLEASE PROVIDE ELEVATION OF BUILDING AND INDICATE THE
 HEIGHT OF THE EXISTING AREA OF MAIN CORNER DOOR THAT IS
 TO BE REMOVED AND RECESSED.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426