| 2019-09-09 16:36:22 | PLEASE NOTE, EVALUATE REVOKING 10080004, |
| | 04030624,03110409, 18040048 WHILE PERFORMING 3RD |
| | REVIEW. |
| 2019-08-26 07:51:01 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18111038 |
| | ADD: 124 N DIXIE HWY. |
| | CONT: GARBER CONSTRUCTION |
| | TEL: 561-929-2505 |
| | E-MAIL: |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. AUGUST 26, 2019 |
| | ACTION: DENIED |
| | |
| | *******************4X FEE / NOTICE!!!!! FLORIDA STATUTE |
| | 553.80(2)(B) ************************** |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS' |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | |
| | 1) 2ND REQUEST. THE ARCHITECTURAL SHEET 1.0A NOTE 9 |
| | INDICATES THE REMOVAL OF THE FRONT ENTRY DOOR AND SIDE |
| | ENTRY DOOR. |
| | THE PLANS INDICATE TO CREATE A NEW RECESSED DOUBLE |
| | GLASS DOOR SYSTEM IN THE FRONT OF THE BUILDING. THE |
| | PRODUCT APPROVAL SUBMITTED A MIAMI-DADE NOA SERIES |
| | "SE-3550" OUTSWING DOOR WAS SUBMITTED. PLEASE NOTE |
| | COMPLIANCE WITH W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) 2ND REQUEST. PLEASE NOTE THE MIAMI-DADE NOA SERIES |
| | "SE-3550" NOA # 17-1114.01 HAS 15 PAGES OF TECHNICAL |
| | PAGES. PAGE 11 OF 15 HAS LOCKING DETAILS 3, 4, & 5 |
| | WHEREAS PAGE 6 OF 15 HAS LOCKING OPTIONS 1, 2 & 6. THE |
| | OPTIONS ON PAGE 6 ARE ALL PANIC HARDWARE. PLEASE NOTE |
| | NEITHER THE CONTRACTOR NOR THE DESIGNER OF RECORD HAVE |
| | CIRCLED WHICH LOCKING OPTION AND ASSOCIATE PRESSURE ARE |
| | TO BE INSTALLED. |
| | PLEASE PROVIDE COMPLIANCE WITH THE 2017 FBC-B 1010.1.10 |
| | PANIC AND FIRE EXIT HARDWARE. DOORS SERVING AN OCCUPANT |
| | LOAD OF 50 OR MORE IN A GROUP A SHALL NOT BE PROVIDED |
| | WITH A LATCH OR LOCK OTHER THAN PANIC HARDWARE OR FIRE |
| | EXIT HARDWARE. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |