Plan Review Details - Permit 18111031
Plan Review Stops For Permit 18111031
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-11 Time 10:42 Rev Time 0.00
Received By shill Date 2019-03-11 Time 07:38 Sent To  
Notes
2019-03-11 10:39:23***PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PRODUCT APPROVALS FOR LOUVERS, METAL ROOF ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION. IT APPEARS THAT A
 PARTIAL APPROVAL WAS PROVIDED BUT THE FLORIDA STATE
 PRODUCT APPROVAL NUMBER IS NOT ON THE DOCUMENTS
 SUBMITTED.
  
 2. A SEPARATE ROOF PERMIT IS REQUIRED. ROOFING
 CONTRACTOR IS TO INDICATE OPTIONS PROPOSED TO SHOW
 COMPLIANCE WITH DESIGN PRESSURES SPECIFIED ON SHEET S1.
 OR, THIS INFORMATION CAN BE PROVIDED AT THIS TIME.
  
 3. TRUSS ENGINEERING REVIEWED BY ENGINEER OF RECORD IS
 TO BE PROVIDED ON THE JOB PRIOR TO INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 11:27 Rev Time 0.00
Received By shill Date 2019-02-16 Time 11:27 Sent To  
Notes
2019-02-16 11:28:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FOR COMPONENTS AND CLADDING. THIS CAN BE A PROVISO ITEM
 FOR LARGE PROJECTS, BUT IT APPEARS THAT ROOFING AND THE
 LOUVER ARE A SIGNIFICANT PART OF THIS PROJECT. PROVIDE
 AT THIS TIME, REVIEWED BY DESIGNER OF RECORD, OR
 PROVIDE RATIONALE FOR REQUESTING A PROVISO, FBC B 1609.
  
 2ND REVIEW - THE PRODUCT APPROVALS SUBMITTED ARE
 INCOMPLETE. THEY LACK AT LEAST ONE OF THE FOLLOWING:
 THE FLORIDA STATE PRODUCT APPROVAL COVER PAGE,
 EVALUATION REPORT, INSTALLATION INSTRUCTIONS.
  
 2. OK
  
 3. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A SEPARATE ROOF PERMIT IS REQUIRED. ROOFING CONTRACTOR
 IS TO INDICATE OPTIONS PROPOSED TO SHOW COMPLIANCE WITH
 DESIGN PRESSURES SPECIFIED ON SHEET S1. OR, THIS
 INFORMATION CAN BE PROVIDED AT THIS TIME.
  
 TRUSS ENGINEERING REVIEWED BY ENGINEER OF RECORD IS TO
 BE PROVIDED ON THE JOB PRIOR TO INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-05 Cont ID  
Sent By shill Date 2018-12-05 Time 11:07 Rev Time 0.00
Received By shill Date 2018-12-05 Time 11:07 Sent To M
Notes
2018-12-05 11:21:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED
 FOR COMPONENTS AND CLADDING. THIS CAN BE A PROVISO ITEM
 FOR LARGE PROJECTS, BUT IT APPEARS THAT ROOFING AND THE
 LOUVER ARE A SIGNIFICANT PART OF THIS PROJECT. PROVIDE
 AT THIS TIME, REVIEWED BY DESIGNER OF RECORD, OR
 PROVIDE RATIONALE FOR REQUESTING A PROVISO, FBC B 1609.
  
 2. S1, LOUVER OPENING DETAIL, THE DETAIL DOES NOT
 GRAPHICALLY SHOW REBAR ON SIDES OR BELOW THE PROPOSED
 NEW OPENING. EMBEDMENT INTO EXISTING IS NOT SPECIFIED.
 NOTE STATES TO VERIFY FILLED CELLS IN FIELD; IT APPEARS
 THAT AT LEAST ONE SIDE WILL BE REQUIRED TO BE
 CONSTRUCTED AS WELL AS THE SILL, UNLESS ENGINEER HAS
 KNOWLEDGE OF EXISTING CONDITIONS, PLEASE PROVIDE
 COMPLETE DETAILS OR CLARIFY.
  
 2. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A SEPARATE ROOF PERMIT IS REQUIRED. ROOFING CONTRACTOR
 IS TO INDICATE OPTIONS PROPOSED TO SHOW COMPLIANCE WITH
 DESIGN PRESSURES SPECIFIED ON SHEET S1. OR, THIS
 INFORMATION CAN BE PROVIDED AT THIS TIME.
  
 TRUSS ENGINEERING REVIEWED BY ENGINEER OF RECORD IS TO
 BE PROVIDED ON THE JOB PRIOR TO INSPECTION.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-03-05 Cont ID  
Sent By jleahy Date 2019-03-05 Time 10:56 Rev Time 0.00
Received By jleahy Date 2019-03-05 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 09:41 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 07:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-10 Cont ID  
Sent By jleahy Date 2018-12-10 Time 18:30 Rev Time 0.00
Received By jleahy Date 2018-12-10 Time 18:30 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-11 Cont ID  
Sent By shill Date 2019-03-11 Time 10:42 Rev Time 0.00
Received By shill Date 2019-02-21 Time 13:18 Sent To  
Notes
2019-02-22 13:18:58B14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 11:28 Rev Time 0.00
Received By shill Date 2019-01-17 Time 14:31 Sent To  
Notes
2019-01-18 14:31:47B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By jleahy Date 2018-12-11 Time 11:10 Rev Time 0.00
Received By jleahy Date 2018-11-26 Time 13:35 Sent To  
Notes
2018-11-28 13:35:55BLDG MISC 1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-06 Cont ID  
Sent By ccole Date 2019-03-06 Time 16:43 Rev Time 0.00
Received By ccole Date 2019-03-06 Time 12:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-01-31 Cont ID  
Sent By ccole Date 2019-01-31 Time 16:42 Rev Time 0.00
Received By ccole Date 2019-01-31 Time 16:10 Sent To  
Notes
2019-01-31 16:44:402ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18111031
 1/31/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE 1ST REVIEW COMMENTS, THE
 ARCHITECT HAS SUBMITTED AN OLD PLAN FOR THE EXISTING
 FACILTIY THAT IS DATED AUGUST 2000. THERE ARE NO CITY
 STAMPS ON THE PLAN, NO ADDRESS SHOWN, AND NO COPY OF
 THIS PLAN IN OUR CITY RECORDS TO VALIDATE IT. THE
 CORRECTED NEW PLAN FOR THE FACILITY IS NOW SHOWING
 THREE NEW FANS INSTEAD OF ONE. PLEASE REVISE THE NEW
 PLAN TO ADDRESS COMMENTS #2- 5 BELOW.
  
 2) SHEET ME-1: PROVIDE SIZING CALCULATION FOR THE NEW
 EXHAUST FANS BASED ON TABLE 403.3.1.1 FBC M.
  
 3) ME-1: INDICATE THE SEQUENCE OF OPERATION FOR THE
 FANS. WILL THE FAN RUN CONTINUOUSLY OR INTERMITTENTLY?
  
 4) ME-1: INDICATE HOW MAKEUP AIR IS TO BE PROVIDED FOR
 THE EXHAUST.
  
 5) ME-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE NEW LOUVERS- RULE 9N-3 FAC.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By ccole Date 2018-12-10 Time 16:39 Rev Time 0.00
Received By ccole Date 2018-12-10 Time 16:32 Sent To E
Notes
2018-12-10 17:00:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111031
 12/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ME-1: PROVIDE A SIZING CALCULATION FOR THE NEW
 EXHAUST FAN BASED ON TABLE 403.3.1.1 FBC M.
  
 2) ME-1: INDICATE THE SEQUENCE OF OPERATION FOR THE
 FAN. WILL THE FAN RUN CONTINUOUSLY OR INTERMITTENTLY?
 THE NOTES ON THE PLAN SHOW "EXISTING OPERATING
 CONTROLS" BUT THIS IS A "NEW" FAN. ARE THERE GAS
 SENSORS LOCATED IN THE GARAGE? PLEASE SEE SECTION 405.1
 AND PROVIDE MORE INFORMATION.
  
 3) ME-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE NEW LOUVER- RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 11:26 Rev Time 0.00
Received By shill Date 2019-02-16 Time 11:26 Sent To  
Notes
2019-02-16 11:27:09PROVISO: ROOF PRODUCT APPROVAL REVIEWED BY DESIGNER OF
 RECORD ARE TO BE SUBMITTED WITH ROOF PERMIT APPLICATION
 PRIOR TO INSTALLATION.
  
  