Plan Review Details - Permit 18110889
Plan Review Stops For Permit 18110889
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By cthroop Date 2018-12-13 Time 13:39 Rev Time 0.00
Received By cthroop Date 2018-12-13 Time 13:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-04 Cont ID  
Sent By skennedy Date 2018-12-04 Time 13:50 Rev Time 0.00
Received By skennedy Date 2018-12-04 Time 13:50 Sent To  
Notes
2018-12-04 14:51:261ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 BUILDING - FAILED
  
 PLEASE PROVIDE CODE INFORMATION AND WALL SECTION. IT
 APPEARS THE PROPER CDOE REFERENCE WHICH MUST BE ADDED
 TO THE DRAWING IS AS FOLLOWS:
  
 FBC 2017 6TH ED. RESIDENTIAL
 FBC 2017 EXISTING BUILDING
 ALTERATION LEVEL II
  
 FBC 107 - PROVIDE A WALL SECTION TO SHOW THE MATERIALS
 TO BE USED.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 13:42 Rev Time 0.00
Received By jleahy Date 2018-12-04 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-20 Cont ID  
Sent By jesmith Date 2018-12-20 Time 11:40 Rev Time 0.00
Received By jesmith Date 2018-12-20 Time 11:40 Sent To  
Notes
2018-12-19 13:19:26RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-13 Cont ID  
Sent By cthroop Date 2018-12-13 Time 13:39 Rev Time 0.00
Received By cthroop Date 2018-12-11 Time 14:16 Sent To  
Notes
2018-12-12 14:16:36RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-04 Cont ID  
Sent By jesmith Date 2018-12-04 Time 15:25 Rev Time 0.00
Received By jesmith Date 2018-12-04 Time 15:25 Sent To  
Notes
2018-11-28 12:51:27R03
2018-11-21 10:11:35LIBRARY

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-12-20 Cont ID  
Sent By jesmith Date 2018-12-20 Time 11:39 Rev Time 0.00
Received By jesmith Date 2018-12-20 Time 11:21 Sent To  
Notes
2018-12-20 11:39:36REVIEWED FOR CODE COMPLIANCE
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-12-13 Cont ID  
Sent By jesmith Date 2018-12-13 Time 09:18 Rev Time 0.00
Received By jesmith Date 2018-12-13 Time 09:01 Sent To  
Notes
2018-12-13 09:02:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
 COMMENTS: DENIED
 1. RE: MASTER BATH SANITARY RISER DIAGRAM; PROVIDE
 COMPREHENSIVE CODE COMPLIANT DRAWING REFLECTING THE
 NECESSARY PIPING CHANGES TO ACCOMMODATE THE MASTER BATH
 RECONFIGURATION PER WPB FBC 107.2.1. THIS INCLUDES THE
 INTERCONNECTIONS OF THE UNDERGROUND PIPING SHOWING HOW
 EACH FIXTURE IS VENTED. PROVIDE NOTE ?CONNECT TO
 EXISTING BUILDING DRAIN?
 2. RE: KITCHEN RISER DIAGRAM; SEE BELOW
 A. PROVIDE VENT EITHER IN THE FORM OF INDIVIDUAL TO THE
 OUTSIDE OR AN AIR ADMITTANCE VALVE (AAV) PER FBC RES
 P3104.1 AND P3105.1.
 B. THERE ARE TWO (2) NEW SINKS. PROVIDE NOTE ?TYPICAL
 OF TWO?
 C. PROVIDE NOTE ?CONNECT TO BUILDING DRAIN?
 3. RE: SHOWER RISER DIAGRAM; PROVIDE NOTE ?EXTENDED
 FROM ORIGINAL BATHTUB DRAIN, NOT TO EXCEED 8? FROM
 VENT? PER WPB FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-04 Cont ID  
Sent By jesmith Date 2018-12-04 Time 15:25 Rev Time 0.00
Received By jesmith Date 2018-12-04 Time 15:12 Sent To  
Notes
2018-12-04 15:24:551ST REVIEW
 COMMENTS: DENIED
  
 1. A SANITARY RISER DIAGRAM IS REQUIRED REFLECTING THE
 NECESSARY PIPING CHANGES TO ACCOMMODATE THE MASTER BATH
 AND POWDER ROOM RECONFIGURATION PER WPB FBC 107.2.1.
 2. IDENTIFY THE PLUMBING FIXTURES ON THE FLOOR PLAN
 INCLUDING THE WATER CLOSETS, LAVATORIES, SHOWERS AND
 KITCHEN SINK. INDICATE THE SAME ON THE CORRESPONDING
 RISER DIAGRAM PER WPB FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  