Plan Review Details - Permit 18110844
Plan Review Stops For Permit 18110844
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 13:52 Rev Time 0.00
Received By cthroop Date 2019-02-01 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-07 Cont ID  
Sent By shill Date 2018-12-07 Time 14:53 Rev Time 0.00
Received By shill Date 2018-12-07 Time 14:53 Sent To  
Notes
2018-12-07 14:54:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 [email protected], 561-805-6716
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
  
 1.ONE COPY OF EACH PRODUCT APPROVAL WAS SUBMITTED;
 HOWEVER, TWO COPIES ARE REQUIRED FOR EACH PERMIT
 APPLICATION.
 107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE
 BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE ADDITIONAL
 CONSTRUCTION DOCUMENTS TO BE PREPARED BY A REGISTERED
 DESIGN PROFESSIONAL. ELECTRONIC MEDIA DOCUMENTS SHALL
 BE SUBMITTED WHEN REQUIRED BY THE BUILDING OFFICIAL AND
 MAY REQUIRE ONLY ONE SET OF SUBMITTALS.
  
 2.PRODUCT APPROVAL NOA NO. 17-1102.24 SPECIFY IS FOR
 ?SMALL MISSILE IMPACT RESISTANT?. THE APPLICABLE CODE
 REQUIRED LARGE IMPACT RESISTANT.
 R301.2.1.2 PROTECTION OF OPENINGS. GLAZED OPENINGS IN
 BUILDINGS LOCATED IN WINDBORNE DEBRIS REGIONS SHALL BE
 PROTECTED FROM WINDBORNE DEBRIS. GLAZED OPENING
 PROTECTION FOR WINDBORNE DEBRIS SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM E 1996
 AND ASTM E 1886 REFERENCED THEREIN, SSTD 12, TAS 201,
 202 AND 203 OR AAMA 506, AS APPLICABLE.
  
 3. PROVIDE PLAN SHOWING LOCATION OF WINDOWS WITH
 DIMENSIONS OF ROUGH OPENINGS. IF NO CHANGES ARE TO BE
 MADE TO THE ROUGH OPENINGS, PROVIDE STATEMENT THAT
 WINDOWS WILL BE LIKE FOR LIKE. IF OPENINGS ARE ALTERED,
 PROVIDE FRAMING PLAN PER FBCR CHAPTER 6.
  
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By fmittner Date 2019-01-14 Time 12:14 Rev Time 0.00
Received By fmittner Date 2019-01-14 Time 12:14 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By shill Date 2018-12-07 Time 14:54 Rev Time 0.00
Received By fmittner Date 2018-12-06 Time 11:24 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-01 Cont ID  
Sent By cthroop Date 2019-02-01 Time 13:52 Rev Time 0.00
Received By cthroop Date 2019-01-10 Time 12:20 Sent To  
Notes
2019-01-11 12:20:43RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-07 Cont ID  
Sent By shill Date 2018-12-07 Time 14:54 Rev Time 0.00
Received By shill Date 2018-11-19 Time 08:34 Sent To HIST
Notes
***NONE***