| Plan Review Stops For Permit 18110768 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-15 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-04-15 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2019-04-15 08:50:17 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVED WITH PROVISOS: | | | | | | 1. OK | | | 2. OK | | | 3. OK PER RED?LINED PLANS. FBC R 322.2.2.1 THE FLOOD | | | VENTS NEED TO BE INSTALLED ON DIFFERENT SIDES. | | | 4. OK | | | 5. OK A SEPERATE PERMIT IS REQUIRED FOR THE POOL. | | | 6. OK A SEPERATE PERMIT IS REQUIRED FOR THE GENERATOR. | | | 7. OK WITH PROVISO THE PRODUCT APPROVALS FOR WINDOWS | | | AND DOORS WILL BE REQUIRED PRIOR TO INSPECTION. | | | 8. OK | | | 9. OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-03-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-29 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-29 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2019-03-29 13:57:26 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | PLAN REVIEW DENIED | | | | | | STILL PENDING: | | | | | | ITEM #4 FROM LAST REVIEW. THE ENERGY SUBMITTALS STILL | | | NEED TO BE SIGNED BY THE OWNER AUTHORIZING THE AGENT. | | | ITEM #9 FROM LAST REVIEW. THE ELEVATION CERTS STILL | | | HAVE NOT BEEN CORRECTED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-13 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-12 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2019-03-13 08:12:08 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND REVIEW | | | RESULTS DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT. | | | | | | 1. OK | | | 2. OK | | | 3. OK PER RED-LINED PLANS. FBC R 322.2.2.1 THE FLOOD | | | VENTS NEED TO BE INSTALLED ON DIFFERENT SIDES. | | | 4. FAIL ENERGY SUBMITTALS STILL NEED TO BE SIGNED BY | | | OWNER AGENT. | | | 5. OK A SEPERATE PERMIT IS REQUIRED FOR THE POOL. | | | 6. OK A SEPERATE PERMIT IS REQUIRED FOR THE GENERATOR. | | | 7. OK WITH PROVISO THE PRODUCT APPROVALS FOR WINDOWS | | | AND DOORS WILL BE REQUIRED PRIOR TO INSPECTION. | | | 8. FAIL PALM BEACH COUNTY IMPACT FEES ARE STILL | | | PENDING. | | | 9. FAIL THE SUBMITTED ELEVATION CERTIFICATION NEEDS TO | | | BE RE-EVALUATED, CORRECTED, AND RE-SUBMITTED. | | | SECTION A9(B) FBC R 322.2.2.1 NEEDS TO BE CORRECTED. | | | SECTION A9(C) FBC R 322.2.2 NEEDS TO BE CORRECTED. | | | SECTION B6 DATE IS NOT CORRECT (OUR RECORDS SHOW | | | 10/5/2017). | | | SECTION B7 DATE IS NOT CORRECT (OUR RECORDS SHOW | | | 10/5/2017). | | | SECTION C2(A) IS NOT CORRECT (THIS SHOULD BE AT 8.00'). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-18 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2018-12-26 10:17:58 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. STRUCTURE APPEARS TO EXCEED MAXIMUM BUILDING HEIGHT | | | PER FBC RCHPT. 3. PROVIDE ELEVATION OF AVERAGE GRADE | | | AND MEAN ROOF HEIGHT. | | | | | | 2. PROVIDE SURVEY WITH CURRENT NAVD DATUM. | | | | | | 3. PROVIDE FLOOD VENTS IN ENCLOSED AREAS BELOW DFE. | | | G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. | | | FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION | | | SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO | | | THE FOLLOWING: | | | 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY | | | WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS | | | TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF | | | FLOODWATERS. | | | | | | 4. OWNER/AGENT TO SIGN ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 5. SEPERATE PERMIT REQUIRED FOR POOL. | | | | | | 6. SEPERATE PERMIT REQUIRED FOR GENERATOR. | | | | | | 7. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS. | | | DESIGNER MAY CHOOSE TO DEFER THESE SUBMITTALS, SEE | | | BELOW. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS | | | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE | | | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE | | | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO | | | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. | | | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR | | | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST | | | THE DEFERRED SUBMITTALS ON | | | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING | | | OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 8. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF. | | | | | | 9. ELEVATION CERTIFICATE REQUIRED. | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NAVD. | | | | | | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED | | | FLOOR ELEVATION IS RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2019-03-13 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2019-03-13 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2019-03-13 12:56:16 | PLEASE SEE NOTES ON PLAN PP |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-12-07 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-12-07 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-12-07 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2018-12-07 12:41:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE WEATHER PROOF GFCI PROTECTED RECEPTACLE | | | OUTLET FOR EACH BALCONY ACCESSIBLE FROM THE DWELLING | | | UNIT. NEC 210.52(E)(3); FBC RE E3901.7 | | | 2. RISER DIAGRAM SHOWS THE FEED TO THE GENERATOR WITH A | | | #10 EQUIPMENT GROUNDING CONDUCTOR. THIS IS NOT THE | | | CORRECT SIZE FOR A FEED WITH A 125 AMP BREAKER ON | | | GENERATOR AS SHOWN. PROVIDE CORRECTION. NEC 250.122; | | | FBC RE E3704.6 | | | 3. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM | | | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET | | | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE | | | R314.3(4), NFPA 72:29.8.3.4 | | | 4. THERE ARE 3 LIGHTS SHOWN OUTSIDE THAT APPEAR TO BE | | | IN THE POOL, SWITCHED FROM INSIDE THE HOUSE. ARE THESE | | | IN FACT POOL LIGHTS, RATED TO BE IN THE POOL, OR IS | | | THIS SOMETHING THAT WILL BE MOUNTED ABOVE THE POOL? | | | PROVIDE CLARIFICATION AND COMPLIANCE WITH FBC RE E4203 | | | IF NECESSARY. WPB FBC 107.2.1; NEC 680.22; FBC RE | | | E4203.4 | | | 5. BASED ON THE OUTLINE OF POOL SHOWN ON PLAN, THERE | | | ARE GFCI RECEPTACLES THAT ARE TOO CLOSE TO THE POOL | | | WATER. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC | | | 680.22; FBC RE E4203.1 | | | 6. ALL GROUNDING ELECTRODES PRESENT MUST BE BONDED | | | TOGETHER. THE CONCRETE ENCASED ELECTRODE IS NOT SHOWN | | | ON RISER DIAGRAM. PROVIDE CORRECTION. NEC 250.52; FBC | | | RE E3608.1 | | | 7. ALL RECEPTACLE OUTLETS IN BATHROOM MUST BE GFCI | | | PROTECTED. PROVIDE CORRECTION FOR MASTER BATH TOILET | | | AREA. NEC 210.8; FBC RE E3902.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-03-12 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-12 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-12 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2019-03-12 12:26:14 | GAS PROVISO: 1) PROVIDE MANUFACTURE INSTALLATION | | | MANUALS | | | FOR ALL GAS EQUIPMENT AND PRESSURE REGULATORS BY FIRST | | | INSPECTION. | | | 2) ALL FURTURE GAS EQUIPMENT MAY COMPLY WITH FBC GAS | | | CODE BUT LOCATION | | | SHALL BE APPROVED BY ZONING. USE OF ANY OTHER PIPING | | | SYSTEM OTHER THEN | | | WHAT IS SPEC OUT WILL REQUIRE A PLAN REVISON. | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-26 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2018-12-26 11:06:02 | GAS PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. FLOOR PLAN FOR FUTURE GENERATOR INDICATES IT WILL | | | REQUIRE 221,000 BTU'S. ISOMETRIC FOR FUTURE GENERATOR | | | INDICATES IT WILL REQUIRE 352,000 BTU'S. PLEASE | | | CLARIFY. | | | | | | 2. PLACE NOTE ON ISOMETRIC DRAWING THAT THE POOL HEATER | | | AND GENERATOR ARE FOR FUTURE USE. | | | | | | 3. PROVIDE TOTAL DISTANCE NOTE FROM GAS DELIVERY TO | | | FARTHEST APPLIANCE ON ISOMETRIC NOTES, PLAN PAGE P-2. | | | | | | 4. ISOMETRIC INDICATE A 1 INCH PLASTIC LINE GOING UNDER | | | THE SLAB. THIS IS NOT ALLOWED PER 402.4. | | | | | | 5. FLOOR PLAN INDICATES GAS DRYER REQUIRES 40,000 | | | BTU'S. ISOMETRIC INDICATES GAS DRYER REQUIRES 20,000 | | | BTU'S. PLEASE CLARIFY. | | | | | | 6. PROVIDE MANUFACTURERS SPECIIFCATIONS FOR ALL GAS | | | APPLIANCES. | | | | | | 7. GENERAL NOTE: ALL EXTERIOR GAS APPLIANCES SHALL BE | | | AT LEAST 4 FEET AWAY FROM ANY DOOR OR WINDOW OPENING. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-15 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-04-11 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2019-04-12 15:10:19 | RESUB ROUTED TO PVALENTI |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-03-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-29 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-27 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2019-03-28 14:45:01 | RESUB ROUTED TO PVALENTI |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-15 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-02-19 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-11-16 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-03-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-29 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-29 |
Time |
13:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-18 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2018-12-26 09:13:20 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-03-14 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2019-03-14 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2019-03-14 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-26 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2018-12-26 10:34:13 | MECHANICAL PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | STRUCTURE IS LOCATED IN FLOOD ZONE AE WITH A BASE FLOOD | | | ELEVATION OF 7.0 FEET AND A DESIGN FLOOD ELEVGATION OF | | | 8.0 FEET. | | | | | | 1. CONDENSING UNITS SHALL BE ELEVATED AT OR ABOVE DFE. | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NAVD. | | | | | | 2. OWNER/AGENT SHALL SIGN THE ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 3. PROVIDE A DESIGN FOR THE CONDENSING UNITS STAND | | | SIGNED AND SEALED BY A DESIGN PROFESSIONAL. | | | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY | | | CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA | | | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES& | | | 61G1 FLORIDA ADMINISTRATIVE CODE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
P |
Date |
2019-04-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-04-15 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-04-15 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2019-03-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-29 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-29 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2019-03-29 16:28:35 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | THE CORRECTED ELEVATION CERTIFICATE IS STILL REQUIRED. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-15 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-15 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2019-03-15 17:41:50 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVAL IS PENDING THE SUBMITTAL OF APPROVED ELEVATION | | | CERTIFICATE. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-18 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2018-12-26 09:11:06 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE ELEVATION CERTIFICATE. | | | | | | 1612.4 DESIGN AND CONSTRUCTION. | | | THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES | | | LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH | | | HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF | | | ASCE 7 AND WITH ASCE 24. | | | | | | FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) & | | | R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND | | | STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS | | | COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED | | | TO OR ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE FLOOD | | | DESIGN INFORMATION ON THE PROPOSED SURVEY AND PROVIDE | | | FLOOD ELEVATION CERTIFICATE. | | | | | | G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. | | | FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION | | | SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO | | | THE FOLLOWING: | | | | | | 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY | | | WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS | | | TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF | | | FLOODWATERS. | | | | | | THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS | | | AE WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY | | | OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN | | | ADDITIONAL 24 INCHES OF FREEBOARD REQUIRING THE DESIGN | | | FLOOD ELEVATION (DFE) TO BE 8. 0 FEET. PLEASE NOTE THIS | | | INFORMATION ON YOUR PLANS. | | | | | | A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS | | | REQUIRED AT TIME OF PERMIT APPLICATION. | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | | SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NAVD. | | | | | | AN UNDER CONSTRUCTION (FORMBOARD) SURVEY WITH FINISHED | | | FLOOR ELEVATION IS RECOMMENDED. | | | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | | REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-03-12 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-12 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-12 |
Time |
12:25 |
Sent To |
G |
|
| Notes |
| 2019-03-12 12:15:47 | PLUMBING PROVISO:1) WASHING MACHNE APPEARS TO BE | | | LOCATED UNDER A CABINET. | | | IF SO REMOTE SHUT OFF VALVES LOCATED WITH IN THE SAME | | | ROOM AND SHALL | | | BE ACCESSIBLE FBC-R P2903.9.4. 2) HAMMER ARRESTORS | | | REQUIRED AT QUICK | | | CLOSING VALVES. FBC-R P2903.5.(3) BATH TUBS/ ROMAN TUBS | | | SHALL BE TEMPERED | | | BY A 1070 DEVICE TO 120F FBC-R P2713.3 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-26 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2018-12-26 10:51:42 | PLUMBING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. REFERENCE PLAN PAGE P-1. THE 3" SANITARY FROM THE | | | LAUNDRY ROOM TERMINATES IN PANTRY WALL. PLEASE CLARIFY. | | | | | | 2. REFERENCE PLAN PAGE P-1. THERE IS A 2" SANITARY PIPE | | | COMING OFF OF THE MASTER BATH GROUP THAT TERMINATES AT | | | THE EXTERIOR WALL. PLEASE CLARIFY. | | | | | | 3. PLAN FOR BATH #1 SHOWS A TUB TO BE INSTALLED. | | | ISOMETRIC FOR BATH #1 SHOWS A SHOWER. PLEASE CLARIFY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-03-15 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-03-15 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2019-03-15 17:28:38 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVED WITH PROVISO: | | | | | | A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOFING. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-12-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-26 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-18 |
Time |
13:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-02-25 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-03-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-02-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-02-25 16:47:17 | NOTES: | | | | | | * SIGNED CONDITIONAL PERMIT FOR LANDSCAPING ATTACHED. | | | | | | * SEPARATE PERMIT FOR LANDSCAPING REQUIRED PRIOR TO THE | | | ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.). A HOLD | | | ON THE C.O. HAS BEEN PLACED IN THE SYSTEM. | | | | | | * ADDITIONAL SEPARATE PERMITS REQUIRED FOR: SWIMMING | | | POOL, GENERATOR. | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-30 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-11-30 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-11-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-11-30 12:33:13 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE EMAIL RESPONSE DOCUMENT FROM THE PBC TAX | | | COLLECTOR'S OFFICE DOES NOT VERIFY THAT THAT THE UNITY | | | OF TITLE WAS BROKEN. PROVIDE FORMAL DOCUMENTATION THAT | | | THE LOTS HAVE BEEN SEPARATED (129 SEVILLE ROAD AND 114 | | | SUMMA STREET). | | | | | | 2.) A SIGNED AND SEALED SURVEY OF THE PROPERTY IS | | | REQUIRED. SURVEY MUST ILLUSTRATE ALL EASEMENTS RUNNING | | | THROUGH THE PROPERTY (IF APPLICABLE). PLEASE PROVIDE. | | | | | | 3.) ALTHOUGH A CONDITIONAL APPROVAL HAS BEEN APPLIED | | | FOR THE LANDSCAPE PERMIT, CALCULATIONS TO ENSURE THAT | | | THERE WILL BE AT LEAST 1,000 SQ. FT. OF LANDSCAPED AREA | | | WITHIN THE REQUIRED FRONT YARD (THE AREA WITHIN THE | | | FIRST 25 FT. OF THE FRONT PROPERTY LINE) SHALL BE | | | PROVIDED IN THE SITE PLAN. | | | | | | 4.) STEPS LEADING TO THE FRONT ENTRANCE OF THE | | | RESIDENCE EXCEED 3 FT. IN HEIGHT ABOVE GRADE. | | | THEREFORE, THESE STEPS CANNOT ENCROACH INTO THE | | | REQUIRED FRONT SETBACK. [ZLDR S.94-305(B)(7)] | | | | | | 5.) THE MAXIMUM BUILDING HEIGHT CANNOT EXCEED 30 FT. | | | BASED ON CALCULATIONS OF THE MEAN GRADE OF THE LOT, THE | | | HEIGHT OF THE PROPOSED RESIDENCE SEEMS TO EXCEED THE | | | MAXIMUM ALLOWABLE HEIGHT. [ZLDR S.94-72(A)(3)] | | | | | | | | | NOTES: | | | | | | * CONDITIONAL PERMIT FOR LANDSCAPING WILL BE SIGNED | | | PRIOR TO PERMIT APPROVAL BY ZONING STAFF. | | | | | | * SEPARATE PERMIT FOR LANDSCAPING REQUIRED PRIOR TO THE | | | ISSUANCE OF A CERTIFICATE OF OCCUPANCY (C.O.). A HOLD | | | ON THE C.O. HAS BEEN PLACED IN THE SYSTEM. | | | | | | * ADDITIONAL SEPARATE PERMITS REQUIRED FOR: SWIMMING | | | POOL, GENERATOR. | | | | | | * A RIGHT-OF-WAY PERMIT FROM THE ENGINEERING SERVICES | | | DEPARTMENT FOR THE PORTION OF THE FRONT YARD PEDESTRIAN | | | WALKWAY OUTSIDE OF PROPERTY LINE, IS REQUIRED PRIOR TO | | | ANY IMPROVEMENT IN THE RIGHT-OF-WAY. | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: SF7 | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|