Plan Review Details - Permit 18110717
Plan Review Stops For Permit 18110717
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-18 Cont ID  
Sent By pvalenti Date 2019-01-18 Time 08:04 Rev Time 0.00
Received By pvalenti Date 2019-01-18 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 13:39 Rev Time 0.00
Received By skennedy Date 2018-12-04 Time 13:39 Sent To  
Notes
2018-12-04 16:43:081ST REVIEW: FBC 2017 6TH EDITION
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 BUILDING - FAILED
  
 PLEASE PROVIDE CODE INFORMATION ON PLAN. IT APPEARS THE
 CODE INFORMATION SHOULD BE AS FOLLOWS:
  
 FBC 2017 6TH EDITION
 FBC 2017 EXISTING BUILDING
 ALTERATION LEVEL II
 TYPE IIB CONSTRUCTION NON-COMBUSTIBLE
  
 FBC 107 MINIMUM PLAN REVIEW CRITERIA - PROVIDE DETAILS
 OF THE NEW WALL FRAMING AND FINISHES, WITH A TYPICAL
 WALL SECTION.
  
 IS FLOORING TO BE INSTALLED AT THE BATH TUB REMOVAL
 AREA? PLEASE CLARIFY. THE PLAN IS NOT CLEAR IF THERE IS
 EXISTING FLOORING TO REMAIN. IF SO, PROVIDE FLOORING
 INSULATION AND FLOORING TYPE INFORMATION. FOR SOUND
 INSULATION PROVIDE TEST REPORTS DEMONSTRATING
 COMPLIANCE WITH THE FOLLOWING SECTIONS:
  
 FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED
 FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE
 W/FLAME SPREAD INDEX OF 200 OR LESS.
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By jleahy Date 2019-01-23 Time 09:22 Rev Time 0.00
Received By jleahy Date 2019-01-23 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-04 Cont ID  
Sent By jleahy Date 2018-12-04 Time 13:34 Rev Time 0.00
Received By jleahy Date 2018-12-04 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-15 Cont ID  
Sent By scaldero Date 2019-01-15 Time 11:32 Rev Time 0.00
Received By scaldero Date 2019-01-15 Time 11:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By scaldero Date 2018-11-20 Time 10:54 Rev Time 0.00
Received By scaldero Date 2018-11-20 Time 10:51 Sent To  
Notes
2018-11-20 10:53:56PERMIT # 18110717
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-23 Cont ID  
Sent By jleahy Date 2019-01-23 Time 09:22 Rev Time 0.00
Received By jleahy Date 2019-01-09 Time 13:46 Sent To  
Notes
2019-01-22 08:39:26ON JLEAHY DESK 1/22/19
2019-01-10 13:46:38B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 10:09 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 10:09 Sent To  
Notes
2018-11-19 14:17:57B18
2018-11-16 09:48:21LIBRARY

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By jesmith Date 2019-01-22 Time 08:34 Rev Time 0.00
Received By jesmith Date 2019-01-22 Time 08:34 Sent To  
Notes
2019-01-22 08:34:24APPROVED
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 10:08 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 10:08 Sent To  
Notes
2018-12-06 10:08:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 1. PLEASE PROVIDE ADDRESS OF PROJECT IN THE TITLE BLOCK
 PER WPB FBC 107.2.1.
 2. PROVIDE UL LISTED ASSEMBLY FOR ABANDONED BATHTUB
 FLOOR PENETRATION REPAIR PER WPB FBC 107.2.1.
 3. WILL THE TOILET AND VANITY IN THE MASTERBATH BE
 REPLACED WITH NEW FIXTURES OR WILL THE EXISTING BE
 REINSTALLED AFTER TILE. WILL THERE BE A RELOCATION OF
 THE TOILET OR VANITY FROM ORIGINAL LOCATIONS. PLEASE
 CLARIFY PER WPB FBC 107.2.1
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
 18110717 403 S SAPODILLA AVE 214