| 2018-12-04 16:43:08 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | 1ST REVIEW FBC 2017 EXISTING BUILDING |
| | |
| | BUILDING - FAILED |
| | |
| | PLEASE PROVIDE CODE INFORMATION ON PLAN. IT APPEARS THE |
| | CODE INFORMATION SHOULD BE AS FOLLOWS: |
| | |
| | FBC 2017 6TH EDITION |
| | FBC 2017 EXISTING BUILDING |
| | ALTERATION LEVEL II |
| | TYPE IIB CONSTRUCTION NON-COMBUSTIBLE |
| | |
| | FBC 107 MINIMUM PLAN REVIEW CRITERIA - PROVIDE DETAILS |
| | OF THE NEW WALL FRAMING AND FINISHES, WITH A TYPICAL |
| | WALL SECTION. |
| | |
| | IS FLOORING TO BE INSTALLED AT THE BATH TUB REMOVAL |
| | AREA? PLEASE CLARIFY. THE PLAN IS NOT CLEAR IF THERE IS |
| | EXISTING FLOORING TO REMAIN. IF SO, PROVIDE FLOORING |
| | INSULATION AND FLOORING TYPE INFORMATION. FOR SOUND |
| | INSULATION PROVIDE TEST REPORTS DEMONSTRATING |
| | COMPLIANCE WITH THE FOLLOWING SECTIONS: |
| | |
| | FBC 603.1 FLAME SPREAD; INSULATION BETWEEN A FINISHED |
| | FLOOR AND SOLID DECKING W/O AN INTERVENING SPACE |
| | W/FLAME SPREAD INDEX OF 200 OR LESS. |
| | |
| | FBC 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | FBC 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | STEVEN KENNEDY, CBO |
| | ASSISTANT BUILDING OFFICIAL |
| | (561) 805-6710 |
| | [email protected] |
| | |