Plan Review Details - Permit 18110667
| Plan Review Stops For Permit 18110667 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-12-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-12-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-12-19 |
Time |
14:50 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-11-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-11-19 |
Time |
15:10 |
Sent To |
I |
|
| Notes |
| 2018-11-19 15:16:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED CALCULATIONS SHEETS DO NOT CLEARLY | | | INDICATE THE SAFETY FACTOR OF THIS PROPOSED | | | INSTALLATION. | | | | | | PLEASE PROVIDE THE REMAINING SAFETY FACTOR OF THE | | | PROPOSED. | | | | | | | | | | | | 2) THERE ARE FLEX HOSE PROPOSED; HOWEVER, THERE ARE NO | | | INDICATIONS OF MODEL TYPE(S) INDICATED. | | | | | | PLEASE INDICATED WHICH FLEX HOSE TYPES ARE BEING USED | | | (ARE THEY ALL THE SAME?) TO ENSURE THAT THE CORRECT | | | FRICTION LOSS IS PROVIDED AS EACH LOCATION? | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-12-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-12-19 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-12-17 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2018-12-18 14:25:42 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-11-19 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-11-15 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2018-11-15 16:00:30 | ROUTED TO FIRE INBOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |