Plan Review Details - Permit 18110642
Plan Review Stops For Permit 18110642
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-14 Cont ID  
Sent By rmcdouga Date 2019-03-14 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2019-03-14 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By rmcdouga Date 2019-02-07 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2019-02-07 Time 08:01 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By rmcdouga Date 2018-12-13 Time 06:55 Rev Time 0.00
Received By rmcdouga Date 2018-12-13 Time 06:55 Sent To I
Notes
2018-12-13 07:15:43REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF PLANS FOR THE GENERATOR PAD WITH
 ANCHORING DETAILS FOR WIND LOADS. PRE-FABRICATED PLANS
 ARE REQUIRED TO BE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER. FBC107.1 GENERAL. SUBMITTAL
 DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS,
 STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH PERMIT APPLICATION. THE CONSTRUCTION
 DOCUMENTS SHALL BE PREPARED BY A REGISTERED DESIGN
 PROFESSIONAL WHERE REQUIRED BY CHAPTER 471, FLORIDA
 STATUTES & 61G15 FLORIDA ADMINISTRATIVE CODE OR CHAPTER
 481, FLORIDA STATUTES & 61G1 FLORIDA ADMINISTRATIVE
 CODE. FBC 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC-R301.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-03-12 Cont ID  
Sent By jleahy Date 2019-03-12 Time 10:43 Rev Time 0.00
Received By jleahy Date 2019-03-12 Time 10:43 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-07 Cont ID  
Sent By jleahy Date 2019-02-07 Time 11:52 Rev Time 0.00
Received By jleahy Date 2019-02-07 Time 11:52 Sent To G
Notes
2019-02-07 11:54:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 VALUE FOR JOB SHALL INCLUDE ALL MATERIALS AND LABOR PER
 FBC 109.3
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 22KW GENERATOR IS USUALLY AROUND $16,500 AND DOES NOT
 INCLUDE FUEL TANK?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By jleahy Date 2018-12-03 Time 15:12 Rev Time 0.00
Received By jleahy Date 2018-12-03 Time 15:11 Sent To  
Notes
2018-12-03 15:22:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE TO LOW
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE SUBMIT SIGNED COPY OF THE CONTRACT FOR ALL WORK
 GENERATOR ELECTRIC GAS

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-03-13 Cont ID  
Sent By tklarge Date 2019-03-13 Time 08:38 Rev Time 0.00
Received By tklarge Date 2019-03-13 Time 05:45 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-02-12 Cont ID  
Sent By tklarge Date 2019-02-12 Time 10:10 Rev Time 0.00
Received By tklarge Date 2019-02-12 Time 06:48 Sent To I
Notes
2019-02-12 09:59:471) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
 SPECIFICATION SHEETS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE STRUCTURE SHALL BE APPROVED FOR OUTDOOR
 USE.2ND REQUEST. WPB AMEND. TO FBC SEC. 107.2.1, 2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 2) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. 2ND
 REQUEST.
 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7). 2ND REQUEST
 4) THE SHEETS THAT HAVE BEEN SUBMITTED FROM AN
 INSTALLATION MANUAL HAVE BEEN UPDATED. SUBMIT SHEETS
 #14-16 OF THE MANUAL WHICH SHOWS THE CLEARANCES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-12-07 Cont ID  
Sent By tklarge Date 2018-12-07 Time 09:26 Rev Time 0.00
Received By tklarge Date 2018-12-07 Time 06:47 Sent To  
Notes
2018-12-07 09:13:021) SUBMIT TWO COPIES OF THE GAS PLAN AND ALL DOCUMENTS.
 WPB AMEND. TO FBC SEC. 107.1.
 2) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.1.
 3) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2017
 FBC-FUEL GAS SEC.410.1.
 4) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4.
 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7).
 6) PLACE A NOTE ON THE PLAN REFERENCING THE GAS SIZING
 TABLES BEING USED IN THE DESIGN OF THIS GAS SYSTEM.
 7) SHOW THE SIZE OF THE PIPE DOWNSTREAM OF THE
 REGULATOR AT THE GENERATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-03-14 Cont ID  
Sent By rmcdouga Date 2019-03-14 Time 07:11 Rev Time 0.00
Received By rmcdouga Date 2019-02-27 Time 15:17 Sent To  
Notes
2019-02-28 15:18:04RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-12 Cont ID  
Sent By tklarge Date 2019-02-12 Time 10:11 Rev Time 0.00
Received By tklarge Date 2019-01-23 Time 15:55 Sent To  
Notes
2019-01-24 15:55:44RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-13 Cont ID  
Sent By rmcdouga Date 2018-12-13 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2018-11-15 Time 16:07 Sent To  
Notes
2018-11-15 16:07:12ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2019-03-07 Cont ID  
Sent By mcruz Date 2019-03-07 Time 13:59 Rev Time 0.00
Received By mcruz Date 2019-03-07 Time 13:56 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2019-02-05 Cont ID  
Sent By mcruz Date 2019-02-05 Time 15:07 Rev Time 0.00
Received By mcruz Date 2019-02-05 Time 15:06 Sent To E
Notes
2019-02-05 15:07:34ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 REPEAT COMMENT:
 1) GENERATOR SHALL BE AT LEAST 6 FEET FROM REAR
 PROPERTY LINE. PURSUANT TO 94-305(B)(4) - MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By mcruz Date 2018-11-27 Time 14:39 Rev Time 0.00
Received By mcruz Date 2018-11-27 Time 14:35 Sent To  
Notes
2018-11-27 14:39:32ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) GENERATOR SHALL BE AT LEAST 6 FEET FROM REAR
 PROPERTY LINE. PURSUANT TO 94-305(B)(4) - MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 SETBACK.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  