| Plan Review Stops For Permit 18110642 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2019-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-03-14 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-03-14 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-02-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-02-07 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-02-07 |
Time |
08:01 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-13 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-12-13 |
Time |
06:55 |
Sent To |
I |
|
| Notes |
| 2018-12-13 07:15:43 | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF PLANS FOR THE GENERATOR PAD WITH | | | ANCHORING DETAILS FOR WIND LOADS. PRE-FABRICATED PLANS | | | ARE REQUIRED TO BE SIGNED AND SEALED BY A FLORIDA | | | LICENSED ENGINEER. FBC107.1 GENERAL. SUBMITTAL | | | DOCUMENTS CONSISTING OF CONSTRUCTION DOCUMENTS, | | | STATEMENT OF SPECIAL INSPECTIONS, GEOTECHNICAL REPORT | | | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS | | | WITH EACH PERMIT APPLICATION. THE CONSTRUCTION | | | DOCUMENTS SHALL BE PREPARED BY A REGISTERED DESIGN | | | PROFESSIONAL WHERE REQUIRED BY CHAPTER 471, FLORIDA | | | STATUTES & 61G15 FLORIDA ADMINISTRATIVE CODE OR CHAPTER | | | 481, FLORIDA STATUTES & 61G1 FLORIDA ADMINISTRATIVE | | | CODE. FBC 107.2.1 - INFORMATION ON CONSTRUCTION | | | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC-R301.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-03-12 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-03-12 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-03-12 |
Time |
10:43 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-02-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-02-07 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-02-07 |
Time |
11:52 |
Sent To |
G |
|
| Notes |
| 2019-02-07 11:54:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | VALUE FOR JOB SHALL INCLUDE ALL MATERIALS AND LABOR PER | | | FBC 109.3 | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | 22KW GENERATOR IS USUALLY AROUND $16,500 AND DOES NOT | | | INCLUDE FUEL TANK? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-03 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-03 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2018-12-03 15:22:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | VALUE TO LOW | | | | | | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | PLEASE SUBMIT SIGNED COPY OF THE CONTRACT FOR ALL WORK | | | GENERATOR ELECTRIC GAS |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2019-03-13 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-03-13 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-03-13 |
Time |
05:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-02-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-12 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-02-12 |
Time |
06:48 |
Sent To |
I |
|
| Notes |
| 2019-02-12 09:59:47 | 1) SUBMIT MANUFACTURER'S INSTALLATION INSTRUCTIONS AND | | | SPECIFICATION SHEETS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE STRUCTURE SHALL BE APPROVED FOR OUTDOOR | | | USE.2ND REQUEST. WPB AMEND. TO FBC SEC. 107.2.1, 2017 | | | FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1. | | | 2) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF | | | EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. 2ND | | | REQUEST. | | | 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7). 2ND REQUEST | | | 4) THE SHEETS THAT HAVE BEEN SUBMITTED FROM AN | | | INSTALLATION MANUAL HAVE BEEN UPDATED. SUBMIT SHEETS | | | #14-16 OF THE MANUAL WHICH SHOWS THE CLEARANCES. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-12-07 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-12-07 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-12-07 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2018-12-07 09:13:02 | 1) SUBMIT TWO COPIES OF THE GAS PLAN AND ALL DOCUMENTS. | | | WPB AMEND. TO FBC SEC. 107.1. | | | 2) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS | | | FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.1. | | | 3) REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2017 | | | FBC-FUEL GAS SEC.410.1. | | | 4) A SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD OF | | | EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4. | | | 5) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE | | | INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP | | | REGULATOR. 2017 FBC-FUEL GAS SEC.410.2.(7). | | | 6) PLACE A NOTE ON THE PLAN REFERENCING THE GAS SIZING | | | TABLES BEING USED IN THE DESIGN OF THIS GAS SYSTEM. | | | 7) SHOW THE SIZE OF THE PIPE DOWNSTREAM OF THE | | | REGULATOR AT THE GENERATOR. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-03-14 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-02-27 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2019-02-28 15:18:04 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-02-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-02-12 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-01-23 |
Time |
15:55 |
Sent To |
|
|
| Notes |
| 2019-01-24 15:55:44 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-13 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-11-15 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2018-11-15 16:07:12 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-03-07 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-03-07 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-03-07 |
Time |
13:56 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-02-05 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-02-05 |
Time |
15:06 |
Sent To |
E |
|
| Notes |
| 2019-02-05 15:07:34 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | REPEAT COMMENT: | | | 1) GENERATOR SHALL BE AT LEAST 6 FEET FROM REAR | | | PROPERTY LINE. PURSUANT TO 94-305(B)(4) - MECHANICAL | | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A | | | SETBACK. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-11-27 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-11-27 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2018-11-27 14:39:32 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) GENERATOR SHALL BE AT LEAST 6 FEET FROM REAR | | | PROPERTY LINE. PURSUANT TO 94-305(B)(4) - MECHANICAL | | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A | | | SETBACK. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|