Plan Review Details - Permit 18110604
Plan Review Stops For Permit 18110604
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-24 Cont ID  
Sent By pvalenti Date 2019-01-24 Time 08:32 Rev Time 0.00
Received By pvalenti Date 2019-01-24 Time 08:32 Sent To  
Notes
2019-01-24 08:55:35PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 1. PROVIDE A COMPLETED FORM BOARD SURVEY (INCLUDING
 ELEVATIONS & WATER RUN-OFF/DRAINAGE INDICATORS) AND
 ELEVATION CERTIFICATE AT TIME OF SLAB INSPECTION.
  
 2. HAVE THE APPROVED ROOFING PERMIT ON-SITE PRIOR TO
 BEGINNING ROOF WORK.
  
 NOTES:
  
 AT TIME OF INSPECTION, PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR THE INSPECTOR.
  
 FBC R 314 AND 315 LISTED AND LABELED CARBON MONOXIDE
 AND SMOKE DETECTORS ARE REQUIRED.
  
 AWS D1.1 CLAUSE 3.1 AND 4.15 AT TIME OF INSPECTION, FOR
 THE STEEL COLUMN, PROVIDE A WELD PROCEDURE
 SPECIFICATION; (SPECIFIES THE ESSENTIAL VARIABLES
 INCLUDING: BASE MATERIALS, THE JOINTS, THE WELDING
 PROCESS, AND THE FILLER METALS TO BE USED).
 ALSO, PROVIDE THE WELDERS PERFORMANCE QUALIFICATION
 RECORD; (SHOWS THE WELDER IS QUALIFIED & CERTIFIED FOR
 THE DESCRIBED TYPE OF WELDING REQUIRED ON THIS
 PROJECT).
  
 THE TRUSS ENGINEERING PACKAGE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-15 Cont ID  
Sent By pvalenti Date 2018-12-15 Time 12:31 Rev Time 0.00
Received By pvalenti Date 2018-12-14 Time 09:51 Sent To  
Notes
2018-12-15 15:44:38****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 CORRECTIONS:
  
 FBC B 107.1 A ROOFING PERMIT IS REQUIRED.
 FBC B 107.2.1 PLEASE PROVIDE MORE INFORMATION:
 ON PAGE A-2, THE 16"X 16" COLUMN AT REAR PATIO DOES NOT
 APPEAR. PLEASE PROVIDE THE COLUMN IN THE PROPOSED
 LOCATION FOR CLARITY.
 ON PAGE A-2, THE COMPONENT AND CLADDING PRESSURE
 SCHEDULE SHOWS A 9'X 7' GARAGE DOOR. PLEASE PROVIDE THE
 INTENDED LOCATION FOR THIS DOOR OR REMOVE FROM PLAN.
 ON PAGE A-3, THE LOCATION/CONFIGURATION OF THE ATTIC
 ACCESS OPENING IS RUNNING PERPINDICULAR TO THE PROPOSED
 DIRECTION OF ROOF TRUSS. PLEASE RECONFIGURE OR
 RELOCATE,
 ON PAGE A-7 DETAILS A, B, D, AND WITHIN THE SUBMITTED
 ENERGY AND LOAD CALCULATION SUBMITTALS, R-19 AND R-30
 INSULATION BATTS ARE INDICATED ABOVE THE CEILING. ON
 PAGE A-3 NOTES AND IN A SEPERATE SUBMITTAL PACKAGE,
 OPEN CELL SPRAY APPLIED ICENYNE INSULATION HAS BEEN
 SUBMITTED. PLEASE
 CLARIFY
 ON PAGES A-1, A-2, AND A-3 THE WINDOW/DOOR SCHEDULE AND
 OPENING INDICATORS ARE NOT COMPLETE AND DO NOT
 COMPLETELY MATCH.
 MISSING MECHANICAL PAGES.
 FBC B 107.2.5 PROVIDE THE PROPOSED FINISHED FLOOR
 ELEVATION AND EXTERIOR GRADE ELEVATIONS WITH DIRECTION
 OF WATER DRAINAGE/RUN-OFF INDICATORS ON THE
 SURVEY/SITE-PLAN.
  
  
 NOTES:
  
 AT TIME OF INSPECTION, PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR THE INSPECTOR.
  
 FBC R 314 AND 315 LISTED AND LABELED CARBON MONOXIDE
 AND SMOKE DETECTORS ARE REQUIRED.
  
 AWS D1.1 CLAUSE 3.1 AND 4.15 AT TIME OF INSPECTION, FOR
 THE STEEL COLUMN, PROVIDE A WELD PROCEDURE
 SPECIFICATION; (SPECIFIES THE ESSENTIAL VARIABLES
 INCLUDING: BASE MATERIALS, THE JOINTS, THE WELDING
 PROCESS, AND THE FILLER METALS TO BE USED).
 ALSO, PROVIDE THE WELDERS PERFORMANCE QUALIFICATION
 RECORD; (SHOWS THE WELDER IS QUALIFIED & CERTIFIED FOR
 THE DESCRIBED TYPE OF WELDING REQUIRED ON THIS
 PROJECT).
  
 THE TRUSS ENGINEERING PACKAGE.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL FORM.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS
 DETACHED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 11:00 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 13:15 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 11:05 Sent To  
Notes
2019-02-05 13:16:15ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. AFCI PROTECTION SHOWN IN NOTE 24 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 2. NOTE 25 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3603.3
 5. SHOW LOCATION ON PLAN OF SERVICE AND MAIN PANEL. IF
 DISTANCE IS GREATER THAN 8 FEET FROM METER TO MAIN
 PANEL, PROVIDE DISCONNECT OR MAIN BREAKER ON EXTERIOR
 OF RESIDENCE. IF THIS IS THE CASE, PROVIDE EQUIPMENT
 GROUNDING CONDUCTOR TO INTERIOR PANEL. WPB FBC 107.2.1;
 NEC 250.122; FBC RE E3704.6, 3607.3.1
 6. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 7. - CORRECTED
 8. - CORRECTED
 9. NOTE PROVIDED - COMPLETED
 10. - CORRECTED
 11. - CORRECTED
 12. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10 - NOT SHOWN
 13. - CORRECTED
 14. - CORRECTED
 15. - CORRECTED
 16. - CORRECTED
 17. - CORRECTED
  
 NEW COMMENTS:
  
 1. - CORRECTED
  
 2. FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5) AND F.S. 481.229.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 08:58 Rev Time 0.00
Received By cthroop Date 2019-01-24 Time 11:14 Sent To  
Notes
2019-01-25 09:03:44ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. AFCI PROTECTION SHOWN IN NOTE 24 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 2. NOTE 25 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3603.3
 5. SHOW LOCATION ON PLAN OF SERVICE AND MAIN PANEL. IF
 DISTANCE IS GREATER THAN 8 FEET FROM METER TO MAIN
 PANEL, PROVIDE DISCONNECT OR MAIN BREAKER ON EXTERIOR
 OF RESIDENCE. IF THIS IS THE CASE, PROVIDE EQUIPMENT
 GROUNDING CONDUCTOR TO INTERIOR PANEL. WPB FBC 107.2.1;
 NEC 250.122; FBC RE E3704.6, 3607.3.1
 6. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 7. CONDUIT SIZE FOR FEED TO INTERIOR PANEL IS TOO SMALL
 FOR THE REQUIRED CONDUCTORS. PROVIDE CORRECTION. NEC
 TABLES; FBC RE TABLES E3904.6 - CORRECTED
 8. RISER DIAGRAM SHOWS 4/0 CONDUCTORS FOR A 300 AMP
 SERVICE. THIS SIZE WIRE IS NOT RATED FOR 300 AMP
 RESIDENTIAL SERVICE. PROVIDE CORRECTION. NEC
 310.15(B)(7) ; FBC RE E3603.1 - CORRECTED
 9. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1 -
 10. PANEL SCHEDULE DOES NOT SHOW THE GFCI PROTECTED
 RECEPTACLE ON A 20 AMP CIRCUIT REQUIRED FOR BATHROOM
 RECEPTACLE OUTLETS. PROVIDE CORRECTION. NEC
 210.11(C)(3), 210.52(D); FBC RE E3703.4, E3901.6
 11. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 12. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 13. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 14. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. AC LOAD SHOULD NOT BE INCLUDED IN THE DEMAND
 FACTORS. SEE FBC RE 3602. NEC 220; FBC RE E3602.2
 15. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 16. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 17. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 NEW COMMENTS:
  
 1. INCLUDE LAUNDRY ROOM ON PANEL SCHEDULE.
  
 2. FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5) AND F.S. 481.229.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-04 Cont ID  
Sent By jpearson Date 2018-12-04 Time 17:51 Rev Time 0.00
Received By jpearson Date 2018-12-04 Time 17:23 Sent To  
Notes
2018-12-04 17:51:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOTE 24 IS NOT CODE
 COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902
 2. NOTE 25 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT
 APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12; FBC RE E4002.14
 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE PANEL INCLUDING INFORMATION FROM THE POWER
 COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT AND DOWNSTREAM PANELS
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3
 4. PROVIDE AIC RATING OF SERVICE PANEL. NEC 110.3,
 110.9; FBC RE E3603.3
 5. SHOW LOCATION ON PLAN OF SERVICE AND MAIN PANEL. IF
 DISTANCE IS GREATER THAN 8 FEET FROM METER TO MAIN
 PANEL, PROVIDE DISCONNECT OR MAIN BREAKER ON EXTERIOR
 OF RESIDENCE. IF THIS IS THE CASE, PROVIDE EQUIPMENT
 GROUNDING CONDUCTOR TO INTERIOR PANEL. WPB FBC 107.2.1;
 NEC 250.122; FBC RE E3704.6, 3607.3.1
 6. RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
 7. CONDUIT SIZE FOR FEED TO INTERIOR PANEL IS TOO SMALL
 FOR THE REQUIRED CONDUCTORS. PROVIDE CORRECTION. NEC
 TABLES; FBC RE TABLES E3904.6
 8. RISER DIAGRAM SHOWS 4/0 CONDUCTORS FOR A 300 AMP
 SERVICE. THIS SIZE WIRE IS NOT RATED FOR 300 AMP
 RESIDENTIAL SERVICE. PROVIDE CORRECTION. NEC
 310.15(B)(7) ; FBC RE E3603.1
 9. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 10. PANEL SCHEDULE DOES NOT SHOW THE GFCI PROTECTED
 RECEPTACLE ON A 20 AMP CIRCUIT REQUIRED FOR BATHROOM
 RECEPTACLE OUTLETS. PROVIDE CORRECTION. NEC
 210.11(C)(3), 210.52(D); FBC RE E3703.4, E3901.6
 11. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN GARAGE, INCLUDING GARAGE DOOR OPENER.
 PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2
 12. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 13. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 14. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. AC LOAD SHOULD NOT BE INCLUDED IN THE DEMAND
 FACTORS. SEE FBC RE 3602. NEC 220; FBC RE E3602.2
 15. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 16. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION. NEC 410.16; FBC RE E4003.12
 17. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 10:59 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 10:59 Sent To  
Notes
2019-02-06 10:59:50PROVISO PROVIDED FOR GAS REVIEW. CT

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 11:25 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 11:04 Sent To  
Notes
2019-02-05 11:39:22GAS PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING, (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 2. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-RES. SEC.
 G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH
 G2413.4 (21). CONTRACTOR TO STATE WHICH TABLES ARE
 USED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 7. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-RES. SEC.G2426 THROUGH G2439.
  
 8. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC-RES. SEC.G2408.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 09:00 Rev Time 0.00
Received By cthroop Date 2019-01-25 Time 09:00 Sent To  
Notes
2019-01-25 09:02:28BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 13:23 Rev Time 0.00
Received By cthroop Date 2019-01-30 Time 14:57 Sent To  
Notes
2019-01-31 14:57:49RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 08:58 Rev Time 0.00
Received By cthroop Date 2019-01-11 Time 15:06 Sent To  
Notes
2019-01-14 15:06:54R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-03 Cont ID  
Sent By cpuell Date 2019-01-03 Time 16:36 Rev Time 0.00
Received By cpuell Date 2018-11-14 Time 15:01 Sent To  
Notes
2018-11-21 10:15:32R11
2018-11-15 15:01:53LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-02-06 Cont ID  
Sent By cthroop Date 2019-02-06 Time 09:25 Rev Time 0.00
Received By cthroop Date 2019-02-06 Time 09:25 Sent To  
Notes
2019-02-06 09:26:11MU-2019-001308-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 13:14 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 11:04 Sent To  
Notes
2019-02-05 13:14:41PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By pvalenti Date 2019-01-04 Time 07:57 Rev Time 0.00
Received By pvalenti Date 2019-01-04 Time 07:57 Sent To  
Notes
2019-01-04 08:00:58****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 08:38 Rev Time 0.00
Received By cthroop Date 2019-01-24 Time 11:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By cmontell Date 2018-12-03 Time 09:34 Rev Time 0.00
Received By cmontell Date 2018-12-03 Time 09:30 Sent To  
Notes
2018-12-03 09:34:40NEED MECHANICAL PLAN
  
 CHRIS MONTELLO
 805-6733

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-02-05 Cont ID  
Sent By cthroop Date 2019-02-05 Time 11:24 Rev Time 0.00
Received By cthroop Date 2019-02-05 Time 11:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-01-25 Cont ID  
Sent By cthroop Date 2019-01-25 Time 08:36 Rev Time 0.00
Received By cthroop Date 2019-01-24 Time 11:15 Sent To  
Notes
2019-01-25 08:38:40PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5) AND F.S. 481.229.
  
 2. GAS PERMIT REQUIRED. PROVIDE GAS PLAN AND RISER
 DIAGRAHM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-03 Cont ID  
Sent By jesmith Date 2019-01-03 Time 14:23 Rev Time 0.00
Received By jesmith Date 2019-01-03 Time 13:36 Sent To  
Notes
2019-01-03 14:23:42CODES IN EFFECT
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 PLUMBING COMMENTS
  
 1.RE: PLAN SHEET A-9
 A. PLAN SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER WPB FBC 107.2.1 WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE
 B. RISER DIAGRAM
 1) LAUNDRY SINK REQUIRES A VENT PER FBC RES P3105.1
 2) CLOTHES WASHER REQUIRES A VENT PER FBC RES P3105.1
 IF AN AIR ADMITTANCE VALVE IS USED THEN THE UNDER FLOOR
 HORIZONTAL PORTION OF THE FIXTURE DRAIN PIPING SHALL BE
 A MINIMUM OF 3" IN ACCORDANCE WITH MANUFACTURER'S
 RECOMMENDATION.
 3) FIXTURE BRANCH PIPING DOWNSTREAM OF THE CONNECTION
 BETWEEN THE CLOTHES WASHER AND THE LAUNDRY SINK SHALL
 BE A MINIMUM OF 3" PER FBC RES P2601.1 AND FBC PL
 406.2.
 4) IDENTIFY THE KITCHEN SINK ON THE RISER DIAGRAM PER
 WPB FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-17 Cont ID  
Sent By awooten Date 2019-01-17 Time   Rev Time 0.00
Received By awooten Date 2019-01-17 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-30 Cont ID  
Sent By awooten Date 2018-11-30 Time   Rev Time  
Received By awooten Date 2018-11-30 Time   Sent To  
Notes
2018-11-30 14:57:01*************************ZONING REVIEW
 FAILED******************************
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION
 PERMIT. SHOWING THE FOLLOWING:
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRES A
 SEPARATE PERMIT.
  
 PROVIDE A SITE PLAN FOR HOUSE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]