Plan Review Details - Permit 18110383
Plan Review Stops For Permit 18110383
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-03-26 Cont ID  
Sent By jleahy Date 2019-03-26 Time 14:05 Rev Time 0.00
Received By jleahy Date 2019-03-26 Time 14:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-02 Cont ID  
Sent By fgiaquin Date 2019-03-02 Time 11:23 Rev Time 0.00
Received By fgiaquin Date 2019-03-02 Time 11:11 Sent To I
Notes
2019-03-02 11:03:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CUT SHEETS OF ALL EQUIPMENT AND MATERIALS
 FOR PRODUCT APPROVAL. FBC 107.2.1 NEC 90.7, 110.2,
 110.3B
  
 2. VALUE LOW, RAISE VALUE.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By jleahy Date 2018-12-14 Time 13:12 Rev Time 0.00
Received By jleahy Date 2018-12-14 Time 13:12 Sent To  
Notes
2018-12-14 13:12:49FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SUBMIT PLANS FOR ALL LV WORK INVOLVED, WE ONLY
 HAVE DATA AND TELEPHONE ON RECORD.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-26 Cont ID  
Sent By jleahy Date 2019-03-26 Time 14:05 Rev Time 0.00
Received By jleahy Date 2019-03-26 Time 14:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-03-02 Cont ID  
Sent By fgiaquin Date 2019-03-02 Time 11:24 Rev Time 0.00
Received By fgiaquin Date 2019-02-20 Time 16:24 Sent To  
Notes
2019-02-20 16:24:14ROUTED TO ELEC<5K