| Plan Review Stops For Permit 18110316 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2019-01-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2019-01-09 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2019-01-09 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-13 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-12-13 |
Time |
07:45 |
Sent To |
I |
|
| Notes |
| 2018-12-13 07:48:04 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEER'S HANDWRITTEN SIGNATURE AND SEAL IS | | | REQUIRED ON THE GENERATOR PAD PLANS. FAC 61G15-23.003 | | | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-01-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-01-09 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-01-09 |
Time |
17:15 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-12-04 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-04 |
Time |
17:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-20 |
Time |
06:01 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-20 |
Time |
05:38 |
Sent To |
G |
|
| Notes |
| 2018-11-20 05:44:46 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | | LOADS. LOAD CALC SHOWS "1- ELECTRIC CAR CHARGER" WITH | | | ZERO WATTS AS LOAD. NEC 220; FBC RE E3602.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-12-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-12-03 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-12-03 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-01-09 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-01-09 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-12-19 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2018-12-20 11:47:53 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-13 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-11-07 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2018-11-08 13:01:12 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-01-07 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2019-01-07 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2019-01-07 |
Time |
15:59 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2018-11-14 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2018-11-14 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2018-11-14 15:44:19 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | | | 1) PURSUANT TO 94-305(B)(4) - MECHANICAL EQUIPMENT MAY | | | NOT PROJECT MORE THAN 4 FEET INTO A SETBACK. GENERATOR | | | SHALL BE AT LEAST 6 FEET FROM EAST PROPOERTY LINE, | | | SURVEY SUBMITTED SAYS 5' FEET. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ | | | ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: 561-822-1442 | | | E-MAIL: [email protected] | | | |
|
|