Plan Review Details - Permit 18110301
Plan Review Stops For Permit 18110301
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 14:43 Rev Time 0.00
Received By dbattles Date 2019-02-20 Time 13:52 Sent To  
Notes
2019-02-20 14:55:10PROVISO; 107.3.4.1 FBC[R] SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By dbattles Date 2019-01-04 Time 16:53 Rev Time 0.00
Received By dbattles Date 2019-01-02 Time 11:57 Sent To  
Notes
2019-01-04 16:53:10****CORRECTIONS****
 W.P.B. PERMIT: 18110301
 REVIEWED: JANUARY 4, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 107.5.3 FBC[AMENDED] SHOW ON PLANS WHAT CODE VERSION
 IS BEING USED FOR THE ADDITION, OR TELL ME WHAT SHEET
 THE INFORMATION IS LOCATED ON. PLEASE ADD A GENERAL
 NOTE ON DATA SHEET. ALSO, CHECK CODE VERSION REFERENCED
 ON PLUMBING SHEET.
  
 2. 103.1.1.2 FBC[RE] THE BUILDING'S OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA
 STATUTES.
 A. PLEASE HAVE THE OWNER SIGN THE ENERGY CALCULATIONS.
  
 3. 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED
 RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE
 INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL
 ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH
 SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE
 INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR
 CONDENSATION CONTROL.
 A. PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE
 INSULATION AT ROOF DECK.
  
 4. 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 A. PLEASE ADD ROOF PITCH TO ELEVATION, ROOF PLAN OR
 BOTH. IF PITCH IS LESS THAN 4:12 THAN DOUBLE
 UNDERLAYMENT WILL BE REQUIRED.
  
 5. 107.3.4.1 FBC[R] PROVIDE PRODUCT APPROVALS FOR
 ROOFING. I SEE PRODUCT APPROVAL FOR UNDERLAYMENT ONLY
 IN THE SUPPORTING DOCUMENT FOLDER. PLEASE ADD PRODUCT
 APPROVAL FOR ROOFING MATERIAL, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFERED.
  
 6. 107.3.4.1 FBC[R] SUBMIT TRUSS SHOP DRAWINGS TO THE
 BUILDING INSPECTOR PRIOR TO INSTALLATION.
 A. THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 7. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
 A. PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS
 WOULD BE LEVEL 3 ALTERATION AND ADDITION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By jleahy Date 2019-02-20 Time 16:31 Rev Time 0.00
Received By jleahy Date 2019-02-20 Time 16:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By jleahy Date 2018-12-20 Time 17:08 Rev Time 0.00
Received By jleahy Date 2018-12-20 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By jleahy Date 2018-12-20 Time 17:11 Rev Time 0.00
Received By jleahy Date 2018-12-20 Time 17:11 Sent To  
Notes
2018-12-20 17:11:59TELEPHONE, DATA, AND TV CABLING

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By cthroop Date 2019-02-25 Time 08:40 Rev Time 0.00
Received By cthroop Date 2019-02-22 Time 17:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 11:22 Rev Time 0.00
Received By gjohnson Date 2019-01-11 Time 11:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-28 Cont ID  
Sent By shill Date 2019-02-28 Time 13:52 Rev Time 0.00
Received By shill Date 2019-02-08 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 11:23 Rev Time 0.00
Received By gjohnson Date 2018-12-02 Time 08:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-03-06 Cont ID  
Sent By lmarchan Date 2019-03-06 Time 10:00 Rev Time 0.00
Received By lmarchan Date 2019-02-28 Time 14:02 Sent To  
Notes
2019-03-06 10:01:20RECIEPT 2019-0307-32 - $427.67
2019-02-28 14:02:472/28/19 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By dbattles Date 2019-01-04 Time 16:48 Rev Time 0.00
Received By dbattles Date 2019-01-02 Time 11:58 Sent To  
Notes
2019-01-04 16:48:45109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By cthroop Date 2019-02-25 Time 08:40 Rev Time 0.00
Received By cthroop Date 2019-02-22 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By hmoser Date 2019-01-04 Time 10:02 Rev Time 0.00
Received By hmoser Date 2019-01-04 Time 09:11 Sent To  
Notes
2019-01-04 10:01:56PLAN DENIED
 PROVIDE EQUIPMENT SCHEDULE ON PLAN
 PER SECTION 107 FBC 2017.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By cthroop Date 2019-02-25 Time 08:40 Rev Time 0.00
Received By cthroop Date 2019-02-22 Time 17:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 11:13 Rev Time 0.00
Received By gjohnson Date 2019-01-11 Time 10:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 14:42 Rev Time 0.00
Received By dbattles Date 2019-02-20 Time 14:42 Sent To  
Notes
2019-02-20 14:42:1514-1028.02 PRODUCT APPROVAL FOR UNDERLAYMENT - OK
 OTHER PRODUCT APPROVALS FOR ROOFING WILL BE NEEDED WITH
 SUB-PERMIT APPLICATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-01-11 Cont ID  
Sent By dbattles Date 2019-01-04 Time 16:53 Rev Time 0.00
Received By dbattles Date 2019-01-04 Time 16:53 Sent To  
Notes
2019-01-04 16:54:23SEE BUILDING REVIEW COMMENT FOR ROOFING PRODUCT
 APPROVAL NEEDED FOR SHINGLES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By dbattles Date 2019-02-20 Time 14:48 Rev Time 0.00
Received By dbattles Date 2019-02-20 Time 13:52 Sent To  
Notes
2019-02-20 14:49:07IF A THIRD REVIEW IS REQUIRED THE NEW SHEETS WILL NEED
 TO BE DIGITALLY SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-01-04 Cont ID  
Sent By dbattles Date 2019-01-04 Time 16:49 Rev Time 0.00
Received By dbattles Date 2019-01-02 Time 11:57 Sent To  
Notes
2019-01-04 16:50:56DRAWINGS ARE NOT DIGITALLY SIGNED.
 UPON COMPLETION OF ALL REVIEWS EITHER UPLOAD NEW FILES,
 OR TALK TO PERMIT LIBRARIAN ABOUT ALTERNATE SIGNATURE
 VERIFICATION METHODS.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-02-28 Cont ID  
Sent By llouie Date 2019-02-28 Time   Rev Time 0.00
Received By llouie Date 2019-02-28 Time   Sent To  
Notes
2019-02-28 11:25:23ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) DRIVEWAY SHALL NOT EXCEED 20 FT. IN WIDTH AT THE
 FRONT PROPERTY LINE.
  
 2.) SEPARATE PERMITS REQUIRED FOR THE FOLLOWING:
 DRIVEWAY/WALKWAY(S), SWIMMING POOL, NEW FENCE/GATE.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By llouie Date 2018-12-10 Time   Rev Time  
Received By llouie Date 2018-12-10 Time   Sent To  
Notes
2018-12-10 12:36:59** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) INCONSISTENCIES DETECTED BETWEEN THE SURVEY OF THE
 PROPERTY AND THE PROPOSED SITE PLAN (I.E. BUILDING
 FOOTPRINT AND SETBACK DIMENSIONS, PAVED AREAS, FENCE
 ALONG THE PROPERTY LINE, ETC.). PLEASE ADDRESS FOR
 CONSISTENCY.
  
 2.) PER THE SURVEY, THERE IS AN EXISTING 3 FT. UTILITY
 EASEMENT (U.E.) LOCATED ALONG THE REAR PROPERTY LINE.
 PLEASE SHOW IN THE SITE PLAN (SHEET A001).
  
 3.) CHECK CALCULATIONS AND MEASUREMENTS IN THE ZONING
 DATA TABULAR ON SHEET A001. STAFF HAS DETECTED MULTIPLE
 INCORRECT DIMENSIONS AND CALCULATIONS. PLEASE CORRECT.
  
 4.) THE MINIMUM REQUIRED REAR SETBACK IS 8.9 FT. THE
 SITE PLAN SHOWS A PROPOSED BUILDING REAR SETBACK OF 8.8
 FT. PLEASE REVISE TO SHOW MINIMUM REQUIRED REAR
 SETBACK. [ZLDR S.94-74(A)(3)(C)]
  
 5.) STRUCTURAL OVERHANGS SHALL NOT EXTEND FARTHER THAN
 3 FT. INTO A REQUIRED SETBACK. PLEASE PROVIDE
 DIMENSIONS TO DEMONSTRATE COMPLIANCE. [ZLDR
 S.94-305(B)(2)]
  
 6.) MECHANICAL EQUIPMENT (INCLUDING A/C COMPRESSOR UNIT
 AND POOL EQUIPMENT PAD(S)) MAY NOT PROJECT MORE THAN 4
 FT. INTO A REQUIRED SETBACK. PLEASE PROVIDE THE WIDTH
 OF THE CONCRETE PAD TO DEMONSTRATE COMPLIANCE. [ZLDR
 S.94-305(B)(4)]
  
 7.) SHOW WIDTH AND LENGTH OF THE PROPOSED NEW DRIVEWAY.
 THE DRIVEWAY CANNOT EXCEED 20 FT. IN WIDTH. [ZLDR
 S.94-312(1)(C)]
  
 8.) THE VALUE OF THE CONSTRUCTION ($249,000.00) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($105,215.00) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 9.) PER ZLDR S.94-482, THE REQUIRED FRONT YARD (AREA
 WITHIN THE FIRST 25 FT. OF MONCEAUX ROAD) SHALL PROVIDE
 A MINIMUM OF 1,000 SQ. FT. OF LANDSCAPED/PERVIOUS
 SURFACE AREA CONSISTING OF LIVING PLANT MATERIAL. SHOW
 CALCULATIONS OF REQUIRED FRONT YARD TO DEMONSTRATE
 COMPLIANCE.
  
 10.) SHOW SETBACK DIMENSIONS FOR THE PROPOSED NEW
 DRIVEWAY. THE DRIVEWAY MUST BE SETBACK AT LEAST 3 FT.
 FROM THE SIDE PROPERTY LINE. [ZLDR S.94-482(D)(2)]
  
 11.) A MINIMUM OF TWO (2) PARKING SPACES SHALL BE
 PROVIDED ON SITE. PLEASE DEMONSTRATE THAT THE DRIVEWAY
 IS SUFFICIENT TO ACCOMMODATE THE MINIMUM REQUIRED
 PARKING, SINCE THERE IS NO GARAGE STRUCTURE.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR THE FOLLOWING:
 LANDSCAPING, DRIVEWAY/WALKWAY, SWIMMING POOL, NEW
 FENCE/GATE.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF14
  