Plan Review Details - Permit 18110241
Plan Review Stops For Permit 18110241
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2019-06-20 Cont ID  
Sent By pvalenti Date 2019-06-20 Time 14:09 Rev Time 0.00
Received By pvalenti Date 2019-06-20 Time 14:09 Sent To  
Notes
2019-06-20 14:14:35PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH NOTES:
  
 THIS STRUCTURE HAS IT'S OWN ADDRESS (313 N. LAKESIDE
 COURT). THE PARCEL OR MAIN ADDRESS IS STILL 1700 N.
 DIXIE HIGHWAY.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2019-04-17 Cont ID  
Sent By shill Date 2019-04-17 Time 07:19 Rev Time 0.00
Received By shill Date 2019-04-17 Time 07:19 Sent To  
Notes
2019-04-17 07:19:52FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL):
  
 MICHAEL ORIO
 GIS SUPPORT SPECIALIST
 [email protected]
 CITY OF WEST PALM BEACH
 INFORMATION TECHNOLOGY DEPARTMENT
 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401
 P: 561.494.1080
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-06-20 Cont ID  
Sent By pvalenti Date 2019-06-20 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2019-06-20 Time 14:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 07:45 Rev Time 0.00
Received By shill Date 2019-05-16 Time 07:45 Sent To  
Notes
2019-05-16 07:49:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLEASE REFER TO EMAIL SENT 4/17/19 TO PAM EGAN, CC'D
 ROBERT BROWN, STEVE KENNEDY, PATRICK O'CONNELL RA,
 CAMILLE DAWSON, ROCK DESJARDINS, DANIEL USHER, DENIS
 HOLMES, REBECCA MILLER WHERE YOU WERE INFORMED THAT
 THIS IS NOT R4, SHOULD BE I-1, AND IS SUBJECT TO
 ACCESSIBILITY. SEE SP1, OCCUPANCY CLASSIFICATION IS
 STILL R4 ON THE PLAN. NOTE THAT R3/R4 IS FOR RESIDENTS
 PERMANENT IN NATURE; UNDER 30 DAYS IS NOT CONSIDERED
 PERMANENT.
  
 SEE ALSO PLUMBING COMMENTS REGARDING ACCESSIBILITY
 REQUIREMENTS.
  
 2. BASED ON DESCRIPTION OF SERVICES, IT APPEARS THAT
 THIS RENOVATION IS TO COMPLY WITH THE REQUIREMENTS OF
 FBC A 224, TRANSIENT LODGING ROOMS. FLORIDA SPECIAL
 ROOM COMPLIANCE NOT CLEAR, UNABLE TO LOCATE
 COMMUNICATION FEATURES TABLE 224.4, ALSO SEE 224.5
 DISPERSION. ONE ROOM WITH A SINGLE TWIN BED IS SHOWN AS
 THE ACCESSIBLE ROOM; OTHER ROOMS ARE SHOWN WITH A FULL
 BED. COMPLIANCE NOT CLEAR.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 17:43 Rev Time 0.00
Received By shill Date 2019-03-26 Time 17:43 Sent To  
Notes
2019-03-26 17:43:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A NARRATIVE DESCRIBING SERVICES TO BE
 PROVIDED, FBC B CHAPTER 3. OCCUPANCY CLASSIFICATION R4
 IS STATED ON THE PLAN, BUT NO FURTHER CLARIFICATION WAS
 PROVIDED. PLEASE SEND THIS VIA EMAIL PRIOR TO
 RESUBMITTING. A REVIEW CANNOT BE DONE WITHOUT THIS
 INFORMATION AS IT IS NOT CLEAR IF THIS IS SUBJECT TO
 ACCESSIBILITY OR FAIR HOUSING.
  
 2. FBC 107, PLAN STATES THAT THIS IS A RENOVATION FOR
 "GRATITUDE HOUSE". THAT NON PROFIT HAS BEEN CLOSED
 SINCE 2017, REVISE OR CLARIFY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 14:29 Rev Time 0.00
Received By shill Date 2018-12-08 Time 14:29 Sent To  
Notes
2018-12-08 14:30:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SCOPE NOT CLEAR, FBC 107. THE PLAN APPEARS TO
 PROPOSE RENOVATIONS (SEE SP1 SCOPE OF WORK, INTERIOR
 RENOVATINOS AND MODIFICATIONS). LEVEL OF ALTERATION NOT
 STATED IN BUILDING CODE INFORMATION, EXISTING FLOOR
 PLANS WERE PROVIDED BUT NO INDICATION OF ANY WORK
 PROPOSED OTHER THAN ELECTRICAL AND PLUMBING.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-06-17 Cont ID  
Sent By jpearson Date 2019-06-17 Time 14:25 Rev Time 0.00
Received By jpearson Date 2019-06-17 Time 14:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 12:41 Rev Time 0.00
Received By jpearson Date 2019-05-14 Time 12:06 Sent To  
Notes
2019-05-14 12:41:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE ADDRESS AND PROJECT NAME HAVE BEEN ALTERED WITH
 RED PEN BY SOMEONE. CHANGES TO THE PLANS AFTER THE
 DESIGN PROFESSIONAL HAS SIGNED/SEALED ARE NOT ACCEPTED.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-26 Cont ID  
Sent By jpearson Date 2019-03-26 Time 09:56 Rev Time 0.00
Received By jpearson Date 2019-03-26 Time 08:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-30 Cont ID  
Sent By jpearson Date 2018-11-30 Time 10:49 Rev Time 0.00
Received By jpearson Date 2018-11-30 Time 09:38 Sent To  
Notes
2018-11-30 10:49:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. IS THERE ANY LOAD BEING ADDED TO THE SERVICE? IF SO,
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-06-20 Cont ID  
Sent By pleduc Date 2019-05-28 Time   Rev Time 0.00
Received By pleduc Date 2019-05-28 Time 13:10 Sent To I
Notes
2019-05-28 13:36:266/20/19
  
 ON REVIEW OF THE PREVIOUS REVIEWS THE FOLLOWING
 COMMENTS WILL BE PROVISED:
  
 PLEASE ENSURE COMPLIANCE WITH THE BELOW COMMENTS AS
 THEY WILL INSPECTED BY A FIRE ISNPECTOR FOR
 VERIFICATION PURPOSES.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
 5/28/19
  
 THE PREVIOUS FIRE PLAN REVIEWER IS NO LONGER WITH THE
 CITY.
  
 BASED ON MY REVIEW OF THE PREVIOUSLY SUBMITTED
 INFORMATION, UNFORTUNATLY, THE FOLLOWING COMMENTS ARE
 NEEDED FOR CLARIFICATION PURPOSES.
  
  
  
 1) BASED ON WHAT HAS BEEN PREVIOUSLY SUBMITTED, THIS
 OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE
 PREVENTION CODE IS LODGING AND ROOMING HOUSE PER NFPA
 101, CH 26.
  
 PER NFPA 101, CH 3 , DEFINITIONS
  
 3.3.167 LODGING OR ROOMING HOUSE. A BUILDING OR PORTION
 THEREOF
 THAT DOES NOT QUALIFY AS A ONE- OR TWO-FAMILY DWELLING,
 THAT PROVIDES
 SLEEPING ACCOMMODATIONS FOR A TOTAL OF 16 OR FEWER
 PEOPLE ON A
 TRANSIENT OR PERMANENT BASIS, WITHOUT PERSONAL CARE
 SERVICES, WITH OR
 WITHOUT MEALS, BUT WITHOUT SEPARATE COOKING FACILITIES
 FOR INDIVIDUAL
 OCCUPANTS
  
 SHOULD YOU DISAGREE PLEASE PROVIDE A DETAILED NARRATIVE
 WITH SPECIFIC CODE REFERENCES.
  
  
 2) THERE ARE NO INDICATION OF A FIRE ALARM SYSTEM.
  
 PER NFPA 101, CH 26
  
 26.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 26.3.4.1 GENERAL.
 26.3.4.1.1 LODGING AND ROOMING HOUSES, OTHER THAN THOSE
 MEETING
 26.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM
 IN ACCORDANCE
 WITH SECTION 9.6.
 26.3.4.1.2 A FIRE ALARM SYSTEM IN ACCORDANCE WITH
 SECTION 9.6 SHALL
 NOT BE REQUIRED IN EXISTING LODGING AND ROOMING HOUSES
 THAT HAVE AN
 EXISTING SMOKE DETECTION SYSTEM MEETING OR EXCEEDING
 THE
 REQUIREMENTS OF 26.3.4.5.1 WHERE THAT DETECTION SYSTEM
 INCLUDES NOT
 LESS THAN ONE MANUAL FIRE ALARM BOX PER FLOOR ARRANGED
 TO INITIATE THE
 SMOKE DETECTION ALARM.
  
 PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT.
  
  
  
 3) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM.
  
 PER NFPA 101, CH 26
  
 26.3.6 EXTINGUISHMENT REQUIREMENTS.
 26.3.6.1 ALL NEW LODGING OR ROOMING HOUSES SHALL BE
 PROTECTED
 THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 26.3.6.2.
  
 PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT.
  
  
  
  
 4) THERE IS ONLY 1 EXIT INDICATED FRON THE 2ND FLOOR.
  
 PER NFPA 101, CH 26
  
 26.2.1 NUMBER AND TYPES OF MEANS OF ESCAPE.
 26.2.1.1 PRIMARY MEANS OF ESCAPE.
 26.2.1.1.1 EVERY SLEEPING ROOM AND LIVING AREA SHALL
 HAVE ACCESS
 TO A PRIMARY MEANS OF ESCAPE COMPLYING WITH CHAPTER 24
 AND
 LOCATED TO PROVIDE A SAFE PATH OF TRAVEL TO THE
 OUTSIDE.
 26.2.1.1.2 WHERE THE SLEEPING ROOM IS ABOVE OR BELOW
 THE LEVEL OF
 EXIT DISCHARGE, THE PRIMARY MEANS OF ESCAPE SHALL BE AN
 INTERIOR
 STAIR IN ACCORDANCE WITH 26.2.2, AN EXTERIOR STAIR, A
 HORIZONTAL EXIT
 IN ACCORDANCE WITH 7.2.4, OR AN EXISTING FIRE ESCAPE
 STAIR IN
 ACCORDANCE WITH 7.2.8.
 26.2.1.2 SECONDARY MEANS OF ESCAPE. IN ADDITION TO THE
 PRIMARY
 ROUTE, EACH SLEEPING ROOM AND LIVING AREA SHALL HAVE A
 SECOND
 MEANS OF ESCAPE IN ACCORDANCE WITH 24.2.2, UNLESS THE
 SLEEPING
 ROOM OR LIVING AREA HAS A DOOR LEADING DIRECTLY OUTSIDE
 THE
 BUILDING WITH ACCESS TO THE FINISHED GROUND LEVEL OR TO
 A STAIRWAY
 THAT MEETS THE REQUIREMENTS FOR EXTERIOR STAIRS IN
 26.2.1.1.2.
  
 PLEASE PROVIDE SPECIFIC DETAILS IN COMPLIANCE WITH THE
 ABOVE.
  
  
  
 6) THE STAIRWAY FROM THE 2ND FLOOR APPEARS TO BE
 UNINCLOSED.
  
 PER NFPA 101, CH 26
  
 26.2.2 STAIRWAYS.
 26.2.2.1 INTERIOR STAIRWAYS, OTHER THAN THOSE IN
 ACCORDANCE WITH
 26.2.2.2 OR 26.2.2.3, SHALL COMPLY WITH 7.2.2.5.3 AND
 SHALL BE
 ENCLOSED BY FIRE BARRIERS HAVING A MINIMUM ?-HOUR FIRE
 RESISTANCE
 RATING, WITH ALL OPENINGS PROTECTED WITH SMOKE-ACTUATED
 AUTOMATIC-CLOSING OR SELF-CLOSING DOORS HAVING A FIRE
 RESISTANCE
 COMPARABLE TO THAT REQUIRED FOR THE ENCLOSURE.
 26.2.2.2 WHERE AN INTERIOR STAIR CONNECTS THE STREET
 FLOOR WITH THE
 STORY NEXT ABOVE OR BELOW ONLY, BUT NOT WITH BOTH, THE
 INTERIOR
 STAIR SHALL BE REQUIRED TO BE ENCLOSED ONLY ON THE
 STREET FLOOR.
 26.2.2.3 STAIRWAYS SHALL BE PERMITTED TO BE UNENCLOSED
 IN
 ACCORDANCE WITH 26.3.1.1.2 AND 26.3.1.1.3.
  
 PLEASE PROVIDE SPECIFIC DETAILS IN COMPLIANCE WITH THE
 ABOVE.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-04-26 Cont ID  
Sent By scaldero Date 2019-04-26 Time 10:23 Rev Time 0.00
Received By scaldero Date 2019-04-26 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-03-11 Cont ID  
Sent By scaldero Date 2019-03-11 Time 10:35 Rev Time 0.00
Received By scaldero Date 2019-03-11 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-08 Cont ID  
Sent By scaldero Date 2018-11-08 Time 10:14 Rev Time 0.00
Received By scaldero Date 2018-11-08 Time 10:05 Sent To  
Notes
2018-11-08 10:14:24PERMIT #18110241
 FIRE REVIEW COMMENTS:
  
 APPROVED WITH COMMENTSL:
  
 1) SHEET A-1: BOTH LAYOUTS ARE MARKED AS "EXISTING
 SECOND FLOOR". PLEASE CORRECT AS THE FIRST DIAGRAM
 SHOULD BE LABELED "EXISTING FIRST FLOOR".
  
 2) SCOPE OF WORK APPEARS TO BE LIMITED TO ELECTRICAL
 AND PLUMBING RENOVATIONS ONLY. THERE ARE NO STRUCTURAL
 CHANGES IDENTIFIED.
  
 SUE ELLEN CALDERON
 [email protected]
 ASST. FIRE MARSHAL
 WPBFR

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 10:42 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 10:33 Sent To  
Notes
2018-12-11 10:42:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 IT APPEARS THAT THE DRYERS WILL BE GAS OPERATED; A GAS
 PERMIT IS REQUIRED
 GAS COMMENTS FOR YOUR USE
 SUBMIT THE FOLLOWING PER WPB FBC 107.2.1
 1. SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. FBC FG 402.4.1, 402.4.2
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 3. TYPE OF GAS (LP OR NATURAL).
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE FBC FG SECS.401.8,
 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC FG
 402.4.1, 402.4.2
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER FBC FG
 304.1
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER FBC FG 402.1, 402.4.3 THRU 402.
 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC FG305.1.
 9. SUBMIT APPLICABLE SIZING TABLES USED TO SIZE THE GAS
 SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING
 WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER
 STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE FBC FG 401.4, 401.8, 402.3, AND
 TABLES 402.4 (1) THRU 402.4 (37)
 11. SHOW THE LOCATION OF ANY AND ALL MP (STEP-DOWN)
 REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC FG 409.4,
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-20 Cont ID  
Sent By cpuell Date 2019-06-20 Time 15:39 Rev Time 0.00
Received By cpuell Date 2019-05-22 Time 16:09 Sent To  
Notes
2019-05-23 16:10:03B12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 08:02 Rev Time 0.00
Received By shill Date 2019-04-23 Time 14:49 Sent To  
Notes
2019-04-24 14:50:10B08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-26 Cont ID  
Sent By shill Date 2019-03-26 Time 17:43 Rev Time 0.00
Received By shill Date 2019-03-07 Time 13:23 Sent To  
Notes
2019-03-08 13:23:34B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 10:43 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 10:43 Sent To  
Notes
2018-12-08 14:32:5712/8 REMOVED FROM BOARD, ROUTED TO JES DESK / S.HILL
  
  
2018-11-07 14:22:56B29

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-06-06 Cont ID  
Sent By ccole Date 2019-06-06 Time 16:23 Rev Time 0.00
Received By ccole Date 2019-06-06 Time 15:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-05-03 Cont ID  
Sent By ccole Date 2019-05-03 Time 16:12 Rev Time 0.00
Received By ccole Date 2019-05-03 Time 13:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By ccole Date 2019-03-21 Time 14:52 Rev Time 0.00
Received By ccole Date 2019-03-21 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By ccole Date 2018-11-27 Time 11:12 Rev Time 0.00
Received By ccole Date 2018-11-27 Time 09:42 Sent To  
Notes
2018-11-27 11:52:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110241
 11/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE CLARIFY IF ANY MECHANICAL ALTERATIONS ARE
 PROPOSED, AND PROVIDE A SCOPE OF WORK WITH
 CORRESPONDING DRAWINGS AND DETAILS- SECTION 107.1 WPB.
  
 2) SUBMIT MANUFACTURER'S FOR THE NEW DRYERS- SECTION
 504 FBC M, AND ANY NEW KITCHEN COOKING APPLIANCES OR
 EXHAUST HOODS IF APPLICABLE- SECTION 107.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-06-04 Cont ID  
Sent By jesmith Date 2019-06-04 Time 15:23 Rev Time 0.00
Received By jesmith Date 2019-06-04 Time 12:21 Sent To  
Notes
2019-06-04 15:23:45LUMBING COMMEMTS: APPROVED WITH PROVISO
 1. PLAN PAGE DET-1, DETAIL 7: SEE REDLINED COMMENTS
 SIDE WALL HAND RAIL SHALL FALL INTO THE 27" MAXIMUM
 SPACE CALLED OUT FOR CONTROLS IN ORDER CONFORM TO FBC
 ACC FIGURE 608.5.2 (B) AS WELL AS FIGURES 608.3.2 (B)
 AND 608.2.2.
 2. PLAN SHEET DET-1, DETAIL 3, 4 AND 8: SEE REDLINED
 COMMENTS
 KITCHEN SINK IS PROVIDED WITH A FORWARD APPROACH;
 PROVIDE KNEE AND TOE CLEARANCE TO CONFORMTO THE
 REQUIREMENTS OF FBC ACC 306.2 AND 306.3. REFER TO
 DETAIL 3 WHICH IS APPLICABLE TO BOTH LAVATORIIES AND
 SINKS.
 3. PLAN SHEET P-3, DETAIL 6; SEE REDLINED COMMENT. SINK
 SHALL MEET DIMENSIONAL REQUIREMENT TO ALLOW IT TO
 COMPLY WITH THE REQUIREMENTS OF FBC ACC 306.3
  
  
 A SPECIAL NOTE: THERE IS AN EXISTING GAS METER SHOWN ON
 A-1. THERE DOES NOT APPEAR TO BE ANY GAS APPLIANCES OR
 EQUIPMENT IN THE STRUCTURE. IF THERE IS EXISTING GAS
 PIPING IN THE BUILDING IT MUST BGE RENDERED HARMLESS
 AND CAPPED TO COMPLIY WITH THE REQUIREMENTS OF THE
 PUBLIC GAS UTILITIES. A SEPARATE PERMIT WILL BE
 REQUIRED.
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2019-04-29 Cont ID  
Sent By thunt Date 2019-04-29 Time 17:11 Rev Time 0.00
Received By thunt Date 2019-04-29 Time 17:11 Sent To  
Notes
2019-04-29 17:14:42PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 1) THE SHOWER DOES NOT COMPLY AS A STANDARD ROLL IN AS
 CALLED OUT ON SHEET P-1 AS THE SEAT/ CONTROLS IS NOT
 PERMITTED TO BE ADJACENT TO THE SINK. FBC-ACC 608.2.1.
 SHT DET-1 SHOWS HOW IT SHOULD BE IF THE SINK WAS ON THE
 OPPOSITE WALL.SEE FBC-ACC 608.2.2.1 EXCEPTION.
  
 2) PROVIDE CLEAR FLOOR SPACE FOR THE SHOWER. I WAS NOT
 ABLE TO LOCATE IT ON ANY SHEETS. FBC 107.3.5
  
 3) SHT. P-2 DETAIL #1 SHOWER PAN DETAIL IS SHOWING A
 CURB 2"-9". CURB'S/ THRESHOLDS OVER 1/2" ARE NOT
 PERMITTED (ROLL IN). FBC-ACC 608.7
  
 4) DRINKING FOUNTAIN SHALL BE A HIGH/ LOW DRINKING
 FOUNTAIN. FBC-PLUMBING 410.3
  
 5) SHT DET-1 SHOWS THE WASHING MACHINES AND DRYERS AS
 HAVING A FORWARD APPROACH. PER FBC-ACC 611.2 ONLY A
 PARALLEL APPROACH IS PERMITTED.
  
 6) SHOW ALL CLEAR FLOOR SPACE ON SHT.A-1. YOU ARE
 MISSING THE WASHING MACHINES, DRYERS, KITCHEN SINK, AND
 SHOWER. NOTE WASHING MACHINES AND DRYERS MUST BE
 PARALLEL. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-03-25 Cont ID  
Sent By thunt Date 2019-03-25 Time 17:13 Rev Time 0.00
Received By thunt Date 2019-03-25 Time 15:41 Sent To  
Notes
2019-03-25 17:13:46PLUMBING 2ND REVIEW**DENIED**
  
 1) COMPLIED
  
 2A) COMPLIED
  
 2B) COMPLIED
  
 2C) COMPLIED
  
 2D) COMPLIED
  
 2E) COMPLIED
  
 2F) PENDING**PROVIDE TOTAL PIPE DEVELOPED LENGTH FROM
 THE WATER HEATER TO THE FURTHEST FIXTURE. IF OVER 50' A
 HOT WATER RETURN SYSTEM MUST BE INCORPORATED INTO THE
 SYSTEM AND COMPLY WITH BOTH FBC-P 607.2, 607.2.1
  
 2G) COMPLIED
  
 2H) COMPLIED
  
 2I) DISAGREE. FLORIDA ACCESSIBILITY DOES COVER R-4
 RESIDENTIAL DWELLING UNIT SUCH AS THIS. YOU ARE
 COMPLYING WITH THE BATHROOMS WHY WOULD THE KITCHEN AND
 LAUNDRY AREA NOT ALSO HAVE TO COMPLY? PROVIDE
 COMPLIANCE WITH FBC-ACCESSIBILITY 809, 809.2.2, 809.3,
 804, AND 611 SHOWING COMPLETE DETAIL TO INCLUDE,
 CABINET/ WASHER AND DRYER HEIGHT, TURNING RADIUS, CLEAR
 FLOOR SPACE SHOWING THE ENTIRE KITCHEN MEETS THE
 FLORIDA ACCESSIBILITY CODE.
  
 2J) COMPLIED
  
 3 AND 4) DISAGREE. THE RESIDENTIAL CODE DOES NOT
 ADDRESS OCCUPANCY CLASSIFICATION OR MIN PLUMBING
 FIXTURE REQUIREMENTS. THE FBC-PLB 403.1 UNDER R-4
 CLASSIFICATION REQUIRES BOTH A DRINKING FOUNTAIN AND A
 SERVICE SINK. THERE ARE NO EXCEPTION FOR R-4 OCCUPANCY
 ON THIS ONE . PROVIDE A SERVICE SINK AND DRINKING
 FOUNTAIN AS REQUIRED BY FBC 403.1
  
  
 NEW COMMENT:
  
 5) PROVIDE DIMENSIONS FOR THE ADA 1ST FLOOR SHOWER.
 PROVIDE A COMPLETE DETAIL OF GRAB BAR'S, SHOWER VALVE
 CONTROLS AND HAND HELD. PROVIDE CLEAR FLOOR SPACE AND
 LIST WHAT SHOWER COMPARTMENT YOU ARE DESIGNING TO.
 FBC-ACCESSSIBILITY 608
  
 6) PROVIDE NOTE AND LOCATION THAT TEMPERED WATER IS
 GOING TO BE PROVIDE TO ALL HAND WASHING SINKS.
 FBC-P607.1.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.**
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 10:32 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 07:42 Sent To  
Notes
2018-12-11 10:32:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 1. PLUMBING PLANS SHALL BE STAMPED/SEALED AND SIGNED BY
 DESIGNER OF RECORD AS DESCRIBED BY WPB FBC 107.1 AND IN
 ACCORDANCE WITH FS 471 AND FAC 61G15.
 2. PROVIDE A DETAILED SCOPE OF WORK IN ACCORDANCE WITH
 WPB FPC 107.2.1 WHICH ADDRESSING THE FOLLOWING
 COMMENTS.
 A) THE SANITARY BUILDING DRAIN BRANCH SERVICING THE
 KITCHEN AND LAUNDRY FACILITIES AND THE P-2 FIXTURE
 APPEAR NOT TO BE EXISTING, BUT RATHER, ADDED. PLEASE
 CLARIFY.
 B) PROVIDE SANITARY PLUMBING RISER DIAGRAM FOR NEW
 SANITARY BUILDING DRAIN BRANCH, P-2 FIXTURE AND POINTS
 OF CONNECTION. PROVIDE SIZING AND FIXTURE UNIT LOAD FOR
 EXISTING PIPING AND NEW FIXTURE UNIT LOAD (SEE FBC PL
 709) BEING ADDED SHOWING COMPLIANCE WITH FBC PL 710.
 SHOW ALL FIXTURE DRAINS, BRANCHES, TRAPS AND VENTS.
 C) PROVIDE FLOOR PLAN AND RISER DIAGRAM OF NEW POTABLE
 WATER DISTRIBUTION AND POINT(S) OF CONNECTION. PROVIDE
 SIZING AND LOAD/DEMAND FOR NEW AND EXISTING PIPING
 SHOWING COMPLIANCE WITH FBC PL 604.
 D) PROVIDE LOCATION OF EXISTING BACKFLOW PREVENTER FOR
 THE WATER SUPPLY. PROVIDE DOCUMENTATION OF CURRENT
 CERTIFICATION FOR THE SAME.
 E) PROVIDE A FIXTURE SCHEDULE OF ALL AFFECTED FIXTURES
 REPLACED OR ADDED. SPECIFY SHOWER CONTROL VALVES AND
 VACUUM BREAKERS FOR HAND HELD SHOWERS. INDICATE ON THE
 PLAN WHICH FIXTURES ARE ADDED AND WHICH ARE BEING
 REPLACED.
 F) PROVIDE WATER HEATER SCHEDULE NOTING STORAGE
 CAPACITY AND ELECTRICAL CHARACTERISTICS. COORDINATE
 WITH ELECTRICAL DESIGN. PROVIDE WATER HEATER DETAIL,
 SHOWING COMPLIANCE WITH THE REQUIREMENTS OF FBC PL 504
 AND 607.3.
 G) PROVIDE SHOWER PAN DETAIL, SHOWING COMPLIANCE WITH
 THE REQUIREMENTS OF FBC PL 417.
 H) PROVIDE DETAIL FOR WASHER BOX WITH FIXTURE DRAIN,
 TRAP AND WATER OUTLETS. SHOW COMPLIANCE WITH FBC 604.9.
 I) PROVIDE DETAIL FOR KITCHEN CABINET AND SINK SHOWING
 COMPLIANCE WITH FBC ACC 233, 809, 804 AND 606.
 J) PROVIDE DETAIL ON ICE LINE IF APPLICABLE. SHOW
 COMPLIANCE WITH FBC 604.9.
 K) SHOW DISHWASHER COMPLIANCE WITH FBC 604.9.
 3. PROVIDE A SERVICE SINK IN ACCORDANCE WITH FBC PL
 TABLE 403.1
 4. PROVIDE A DRINKING FOUNTAIN IN ACCORDANCE WITH FBC
 PL TABLE 403.1. DRINKING FOUNTAIN SHALL BE BARRIER FREE
 IN ACCORDANCE WITH FBC ACC 211 AND 602.
  
 END OF COMMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-06-05 Cont ID  
Sent By llouie Date 2019-06-05 Time   Rev Time 0.00
Received By llouie Date 2019-06-05 Time   Sent To  
Notes
2019-06-05 15:19:39- MAXIMUM # OF BEDS FOR THE ENTIRE FACILITY = 41 BEDS
 - # OF BEDS PROPOSED FOR THE ENTIRE FACILITY = 34 BEDS
 ( 317 N. LAKESIDE CT. = 26 BEDS + 313 N. LAKESIDE CT. =
 8 BEDS)
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-03 Cont ID  
Sent By llouie Date 2019-05-03 Time   Rev Time 0.00
Received By llouie Date 2019-04-30 Time 15:16 Sent To  
Notes
2019-05-03 13:49:45- MAXIMUM # OF BEDS FOR THE ENTIRE FACILITY = 41 BEDS
 - # OF BEDS PROPOSED FOR THE ENTIRE FACILITY = 35 BEDS
 ( 317 N. LAKESIDE CT. = 26 BEDS + 313 N. LAKESIDE CT. =
 9 BEDS)
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-21 Cont ID  
Sent By llouie Date 2019-03-21 Time   Rev Time 0.00
Received By llouie Date 2019-03-20 Time   Sent To  
Notes
2019-03-21 09:09:16MAXIMUM NUMBER OF BEDS FOR THE FACILITY = 41 BEDS
  
 APPROVED BED COUNT (#18050930): HIBISCUS HOUSE @ 313
 LAKESIDE CT. = 9 BEDS; LOTUS HOUSE @ 317 LAKESIDE CT. =
 26 BEDS
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By llouie Date 2018-11-15 Time   Rev Time  
Received By llouie Date 2018-11-15 Time   Sent To  
Notes
2018-11-15 09:14:29** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY. SURVEY
 IS MISSING FROM THE PERMIT APPLICATION.
  
 2.) PER STAFF'S RECORDS, A MAXIMUM OF 41 BEDS IS
 PERMITTED FOR THE ENTIRE FACILITY. SINCE MULTIPLE
 BUILDING PERMITS HAVE BEEN SUBMITTED FOR THE RENOVATION
 OF VARIOUS BUILDINGS WITHIN THE FACILITY, IT IS
 IMPORTANT TO PROVIDE AN UPDATED/PROPOSED BED COUNT.
 PLEASE PROVIDE A TABULAR WITH THE BED CALCULATIONS FOR
 THE OVERALL FACILITY WITHIN THE PLANS.
  
 3.) EXISTING FLOOR PLAN ON SHEET A-1 SEEMS TO BE
 MISLABELED. PLEASE CORRECT.
  
 4.) PROPOSED FLOOR PLAN IS MISSING FROM THE PERMIT SET.
 PLEASE PROVIDE. ALSO INDICATE THE NUMBER OF BEDS
 PROPOSED FOR THE SCOPE.
  
 5.) ANY CHANGES TO THE ARCHITECTURAL PLANS SHALL BE
 REFLECTED IN ALL PLANS FOR CONSISTENCY (I.E. ELECTRICAL
 AND PLUMBING PLANS, ETC.).
  
  
 NOTES:
  
 * EXISTING TREATMENT FACILITY.
  
 * MAXIMUM NUMBER OF BEDS FOR THE FACILITY = 41 BEDS
  
 * PER PERMIT #18050930: HIBISCUS HOUSE @ 313 LAKESIDE
 CT. = 9 BEDS; LOTUS HOUSE @ 317 LAKESIDE CT. = 26 BEDS
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: GC AND POR
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved