| Plan Review Stops For Permit 18110241 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-20 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-20 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2019-06-20 14:14:35 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | APPROVED WITH NOTES: | | | | | | THIS STRUCTURE HAS IT'S OWN ADDRESS (313 N. LAKESIDE | | | COURT). THE PARCEL OR MAIN ADDRESS IS STILL 1700 N. | | | DIXIE HIGHWAY. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2019-04-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-04-17 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-17 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2019-04-17 07:19:52 | FOR ADDRESSING, PLEASE CONTACT (PREFERABLY VIA EMAIL): | | | | | | MICHAEL ORIO | | | GIS SUPPORT SPECIALIST | | | [email protected] | | | CITY OF WEST PALM BEACH | | | INFORMATION TECHNOLOGY DEPARTMENT | | | 401 CLEMATIS STREET, WEST PALM BEACH, FLORIDA 33401 | | | P: 561.494.1080 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-06-20 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-06-20 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-16 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-05-16 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2019-05-16 07:49:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PLEASE REFER TO EMAIL SENT 4/17/19 TO PAM EGAN, CC'D | | | ROBERT BROWN, STEVE KENNEDY, PATRICK O'CONNELL RA, | | | CAMILLE DAWSON, ROCK DESJARDINS, DANIEL USHER, DENIS | | | HOLMES, REBECCA MILLER WHERE YOU WERE INFORMED THAT | | | THIS IS NOT R4, SHOULD BE I-1, AND IS SUBJECT TO | | | ACCESSIBILITY. SEE SP1, OCCUPANCY CLASSIFICATION IS | | | STILL R4 ON THE PLAN. NOTE THAT R3/R4 IS FOR RESIDENTS | | | PERMANENT IN NATURE; UNDER 30 DAYS IS NOT CONSIDERED | | | PERMANENT. | | | | | | SEE ALSO PLUMBING COMMENTS REGARDING ACCESSIBILITY | | | REQUIREMENTS. | | | | | | 2. BASED ON DESCRIPTION OF SERVICES, IT APPEARS THAT | | | THIS RENOVATION IS TO COMPLY WITH THE REQUIREMENTS OF | | | FBC A 224, TRANSIENT LODGING ROOMS. FLORIDA SPECIAL | | | ROOM COMPLIANCE NOT CLEAR, UNABLE TO LOCATE | | | COMMUNICATION FEATURES TABLE 224.4, ALSO SEE 224.5 | | | DISPERSION. ONE ROOM WITH A SINGLE TWIN BED IS SHOWN AS | | | THE ACCESSIBLE ROOM; OTHER ROOMS ARE SHOWN WITH A FULL | | | BED. COMPLIANCE NOT CLEAR. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-03-26 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-26 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2019-03-26 17:43:30 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PROVIDE A NARRATIVE DESCRIBING SERVICES TO BE | | | PROVIDED, FBC B CHAPTER 3. OCCUPANCY CLASSIFICATION R4 | | | IS STATED ON THE PLAN, BUT NO FURTHER CLARIFICATION WAS | | | PROVIDED. PLEASE SEND THIS VIA EMAIL PRIOR TO | | | RESUBMITTING. A REVIEW CANNOT BE DONE WITHOUT THIS | | | INFORMATION AS IT IS NOT CLEAR IF THIS IS SUBJECT TO | | | ACCESSIBILITY OR FAIR HOUSING. | | | | | | 2. FBC 107, PLAN STATES THAT THIS IS A RENOVATION FOR | | | "GRATITUDE HOUSE". THAT NON PROFIT HAS BEEN CLOSED | | | SINCE 2017, REVISE OR CLARIFY. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-08 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-12-08 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2018-12-08 14:30:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. SCOPE NOT CLEAR, FBC 107. THE PLAN APPEARS TO | | | PROPOSE RENOVATIONS (SEE SP1 SCOPE OF WORK, INTERIOR | | | RENOVATINOS AND MODIFICATIONS). LEVEL OF ALTERATION NOT | | | STATED IN BUILDING CODE INFORMATION, EXISTING FLOOR | | | PLANS WERE PROVIDED BUT NO INDICATION OF ANY WORK | | | PROPOSED OTHER THAN ELECTRICAL AND PLUMBING. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2019-06-17 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-06-17 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-06-17 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-05-14 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-05-14 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-05-14 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2019-05-14 12:41:41 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. THE ADDRESS AND PROJECT NAME HAVE BEEN ALTERED WITH | | | RED PEN BY SOMEONE. CHANGES TO THE PLANS AFTER THE | | | DESIGN PROFESSIONAL HAS SIGNED/SEALED ARE NOT ACCEPTED. | | | PROVIDE CORRECTION. WPB FBC 107.1, 107.2 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-03-26 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-03-26 |
Time |
08:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-30 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-30 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2018-11-30 10:49:55 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | | 250.50, 250.94, 408.30 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4 | | | 3. IS THERE ANY LOAD BEING ADDED TO THE SERVICE? IF SO, | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-05-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-05-28 |
Time |
13:10 |
Sent To |
I |
|
| Notes |
| 2019-05-28 13:36:26 | 6/20/19 | | | | | | ON REVIEW OF THE PREVIOUS REVIEWS THE FOLLOWING | | | COMMENTS WILL BE PROVISED: | | | | | | PLEASE ENSURE COMPLIANCE WITH THE BELOW COMMENTS AS | | | THEY WILL INSPECTED BY A FIRE ISNPECTOR FOR | | | VERIFICATION PURPOSES. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | 5/28/19 | | | | | | THE PREVIOUS FIRE PLAN REVIEWER IS NO LONGER WITH THE | | | CITY. | | | | | | BASED ON MY REVIEW OF THE PREVIOUSLY SUBMITTED | | | INFORMATION, UNFORTUNATLY, THE FOLLOWING COMMENTS ARE | | | NEEDED FOR CLARIFICATION PURPOSES. | | | | | | | | | | | | 1) BASED ON WHAT HAS BEEN PREVIOUSLY SUBMITTED, THIS | | | OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE | | | PREVENTION CODE IS LODGING AND ROOMING HOUSE PER NFPA | | | 101, CH 26. | | | | | | PER NFPA 101, CH 3 , DEFINITIONS | | | | | | 3.3.167 LODGING OR ROOMING HOUSE. A BUILDING OR PORTION | | | THEREOF | | | THAT DOES NOT QUALIFY AS A ONE- OR TWO-FAMILY DWELLING, | | | THAT PROVIDES | | | SLEEPING ACCOMMODATIONS FOR A TOTAL OF 16 OR FEWER | | | PEOPLE ON A | | | TRANSIENT OR PERMANENT BASIS, WITHOUT PERSONAL CARE | | | SERVICES, WITH OR | | | WITHOUT MEALS, BUT WITHOUT SEPARATE COOKING FACILITIES | | | FOR INDIVIDUAL | | | OCCUPANTS | | | | | | SHOULD YOU DISAGREE PLEASE PROVIDE A DETAILED NARRATIVE | | | WITH SPECIFIC CODE REFERENCES. | | | | | | | | | 2) THERE ARE NO INDICATION OF A FIRE ALARM SYSTEM. | | | | | | PER NFPA 101, CH 26 | | | | | | 26.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | | 26.3.4.1 GENERAL. | | | 26.3.4.1.1 LODGING AND ROOMING HOUSES, OTHER THAN THOSE | | | MEETING | | | 26.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM | | | IN ACCORDANCE | | | WITH SECTION 9.6. | | | 26.3.4.1.2 A FIRE ALARM SYSTEM IN ACCORDANCE WITH | | | SECTION 9.6 SHALL | | | NOT BE REQUIRED IN EXISTING LODGING AND ROOMING HOUSES | | | THAT HAVE AN | | | EXISTING SMOKE DETECTION SYSTEM MEETING OR EXCEEDING | | | THE | | | REQUIREMENTS OF 26.3.4.5.1 WHERE THAT DETECTION SYSTEM | | | INCLUDES NOT | | | LESS THAN ONE MANUAL FIRE ALARM BOX PER FLOOR ARRANGED | | | TO INITIATE THE | | | SMOKE DETECTION ALARM. | | | | | | PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT. | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM. | | | | | | PER NFPA 101, CH 26 | | | | | | 26.3.6 EXTINGUISHMENT REQUIREMENTS. | | | 26.3.6.1 ALL NEW LODGING OR ROOMING HOUSES SHALL BE | | | PROTECTED | | | THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN | | | ACCORDANCE WITH 26.3.6.2. | | | | | | PLEASE PROVIDE DETAILS AND/OR A NOTE OF ACKNOWLEDGMENT. | | | | | | | | | | | | | | | 4) THERE IS ONLY 1 EXIT INDICATED FRON THE 2ND FLOOR. | | | | | | PER NFPA 101, CH 26 | | | | | | 26.2.1 NUMBER AND TYPES OF MEANS OF ESCAPE. | | | 26.2.1.1 PRIMARY MEANS OF ESCAPE. | | | 26.2.1.1.1 EVERY SLEEPING ROOM AND LIVING AREA SHALL | | | HAVE ACCESS | | | TO A PRIMARY MEANS OF ESCAPE COMPLYING WITH CHAPTER 24 | | | AND | | | LOCATED TO PROVIDE A SAFE PATH OF TRAVEL TO THE | | | OUTSIDE. | | | 26.2.1.1.2 WHERE THE SLEEPING ROOM IS ABOVE OR BELOW | | | THE LEVEL OF | | | EXIT DISCHARGE, THE PRIMARY MEANS OF ESCAPE SHALL BE AN | | | INTERIOR | | | STAIR IN ACCORDANCE WITH 26.2.2, AN EXTERIOR STAIR, A | | | HORIZONTAL EXIT | | | IN ACCORDANCE WITH 7.2.4, OR AN EXISTING FIRE ESCAPE | | | STAIR IN | | | ACCORDANCE WITH 7.2.8. | | | 26.2.1.2 SECONDARY MEANS OF ESCAPE. IN ADDITION TO THE | | | PRIMARY | | | ROUTE, EACH SLEEPING ROOM AND LIVING AREA SHALL HAVE A | | | SECOND | | | MEANS OF ESCAPE IN ACCORDANCE WITH 24.2.2, UNLESS THE | | | SLEEPING | | | ROOM OR LIVING AREA HAS A DOOR LEADING DIRECTLY OUTSIDE | | | THE | | | BUILDING WITH ACCESS TO THE FINISHED GROUND LEVEL OR TO | | | A STAIRWAY | | | THAT MEETS THE REQUIREMENTS FOR EXTERIOR STAIRS IN | | | 26.2.1.1.2. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS IN COMPLIANCE WITH THE | | | ABOVE. | | | | | | | | | | | | 6) THE STAIRWAY FROM THE 2ND FLOOR APPEARS TO BE | | | UNINCLOSED. | | | | | | PER NFPA 101, CH 26 | | | | | | 26.2.2 STAIRWAYS. | | | 26.2.2.1 INTERIOR STAIRWAYS, OTHER THAN THOSE IN | | | ACCORDANCE WITH | | | 26.2.2.2 OR 26.2.2.3, SHALL COMPLY WITH 7.2.2.5.3 AND | | | SHALL BE | | | ENCLOSED BY FIRE BARRIERS HAVING A MINIMUM ?-HOUR FIRE | | | RESISTANCE | | | RATING, WITH ALL OPENINGS PROTECTED WITH SMOKE-ACTUATED | | | AUTOMATIC-CLOSING OR SELF-CLOSING DOORS HAVING A FIRE | | | RESISTANCE | | | COMPARABLE TO THAT REQUIRED FOR THE ENCLOSURE. | | | 26.2.2.2 WHERE AN INTERIOR STAIR CONNECTS THE STREET | | | FLOOR WITH THE | | | STORY NEXT ABOVE OR BELOW ONLY, BUT NOT WITH BOTH, THE | | | INTERIOR | | | STAIR SHALL BE REQUIRED TO BE ENCLOSED ONLY ON THE | | | STREET FLOOR. | | | 26.2.2.3 STAIRWAYS SHALL BE PERMITTED TO BE UNENCLOSED | | | IN | | | ACCORDANCE WITH 26.3.1.1.2 AND 26.3.1.1.3. | | | | | | PLEASE PROVIDE SPECIFIC DETAILS IN COMPLIANCE WITH THE | | | ABOVE. | | | | | | | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2019-04-26 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-04-26 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-04-26 |
Time |
10:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2019-03-11 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2019-03-11 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2019-03-11 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-11-08 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-11-08 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-11-08 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2018-11-08 10:14:24 | PERMIT #18110241 | | | FIRE REVIEW COMMENTS: | | | | | | APPROVED WITH COMMENTSL: | | | | | | 1) SHEET A-1: BOTH LAYOUTS ARE MARKED AS "EXISTING | | | SECOND FLOOR". PLEASE CORRECT AS THE FIRST DIAGRAM | | | SHOULD BE LABELED "EXISTING FIRST FLOOR". | | | | | | 2) SCOPE OF WORK APPEARS TO BE LIMITED TO ELECTRICAL | | | AND PLUMBING RENOVATIONS ONLY. THERE ARE NO STRUCTURAL | | | CHANGES IDENTIFIED. | | | | | | SUE ELLEN CALDERON | | | [email protected] | | | ASST. FIRE MARSHAL | | | WPBFR |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-11 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-11 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2018-12-11 10:42:22 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | IT APPEARS THAT THE DRYERS WILL BE GAS OPERATED; A GAS | | | PERMIT IS REQUIRED | | | GAS COMMENTS FOR YOUR USE | | | SUBMIT THE FOLLOWING PER WPB FBC 107.2.1 | | | 1. SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES, | | | TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS | | | OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE | | | SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE | | | SYSTEM. FBC FG 402.4.1, 402.4.2 | | | 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR | | | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | 3. TYPE OF GAS (LP OR NATURAL). | | | 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE FBC FG SECS.401.8, | | | 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC FG | | | 402.4.1, 402.4.2 | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER FBC FG | | | 304.1 | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER FBC FG 402.1, 402.4.3 THRU 402. | | | 8. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG | | | 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND | | | LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FBC FG305.1. | | | 9. SUBMIT APPLICABLE SIZING TABLES USED TO SIZE THE GAS | | | SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS SPECIFYING | | | WHICH SIZING TABLE(S) FROM THE GAS CODE OR OTHER | | | STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS | | | SYSTEM. REFER TO THE FBC FG 401.4, 401.8, 402.3, AND | | | TABLES 402.4 (1) THRU 402.4 (37) | | | 11. SHOW THE LOCATION OF ANY AND ALL MP (STEP-DOWN) | | | REGULATORS. A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC FG 409.4, | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-06-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2019-06-20 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-05-22 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2019-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-05-16 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-04-23 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-03-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-03-26 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-03-07 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-11 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-11 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2018-12-08 14:32:57 | 12/8 REMOVED FROM BOARD, ROUTED TO JES DESK / S.HILL | | | | | | | | 2018-11-07 14:22:56 | B29 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2019-06-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-06-06 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-06-06 |
Time |
15:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-05-03 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-05-03 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-03-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-03-21 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-03-21 |
Time |
14:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-27 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-27 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2018-11-27 11:52:58 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18110241 | | | 11/27/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. | | | PLEASE CLARIFY IF ANY MECHANICAL ALTERATIONS ARE | | | PROPOSED, AND PROVIDE A SCOPE OF WORK WITH | | | CORRESPONDING DRAWINGS AND DETAILS- SECTION 107.1 WPB. | | | | | | 2) SUBMIT MANUFACTURER'S FOR THE NEW DRYERS- SECTION | | | 504 FBC M, AND ANY NEW KITCHEN COOKING APPLIANCES OR | | | EXHAUST HOODS IF APPLICABLE- SECTION 107.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2019-06-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-06-04 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-06-04 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2019-06-04 15:23:45 | LUMBING COMMEMTS: APPROVED WITH PROVISO | | | 1. PLAN PAGE DET-1, DETAIL 7: SEE REDLINED COMMENTS | | | SIDE WALL HAND RAIL SHALL FALL INTO THE 27" MAXIMUM | | | SPACE CALLED OUT FOR CONTROLS IN ORDER CONFORM TO FBC | | | ACC FIGURE 608.5.2 (B) AS WELL AS FIGURES 608.3.2 (B) | | | AND 608.2.2. | | | 2. PLAN SHEET DET-1, DETAIL 3, 4 AND 8: SEE REDLINED | | | COMMENTS | | | KITCHEN SINK IS PROVIDED WITH A FORWARD APPROACH; | | | PROVIDE KNEE AND TOE CLEARANCE TO CONFORMTO THE | | | REQUIREMENTS OF FBC ACC 306.2 AND 306.3. REFER TO | | | DETAIL 3 WHICH IS APPLICABLE TO BOTH LAVATORIIES AND | | | SINKS. | | | 3. PLAN SHEET P-3, DETAIL 6; SEE REDLINED COMMENT. SINK | | | SHALL MEET DIMENSIONAL REQUIREMENT TO ALLOW IT TO | | | COMPLY WITH THE REQUIREMENTS OF FBC ACC 306.3 | | | | | | | | | A SPECIAL NOTE: THERE IS AN EXISTING GAS METER SHOWN ON | | | A-1. THERE DOES NOT APPEAR TO BE ANY GAS APPLIANCES OR | | | EQUIPMENT IN THE STRUCTURE. IF THERE IS EXISTING GAS | | | PIPING IN THE BUILDING IT MUST BGE RENDERED HARMLESS | | | AND CAPPED TO COMPLIY WITH THE REQUIREMENTS OF THE | | | PUBLIC GAS UTILITIES. A SEPARATE PERMIT WILL BE | | | REQUIRED. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2019-04-29 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-04-29 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-04-29 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2019-04-29 17:14:42 | PLUMBING 3RD REVIEW**DENIED**FL ST 553.80 (B)2B WITH | | | RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? | | | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN | | | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING | | | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS | | | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO | | | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY | | | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, | | | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. | | | | | | 1) THE SHOWER DOES NOT COMPLY AS A STANDARD ROLL IN AS | | | CALLED OUT ON SHEET P-1 AS THE SEAT/ CONTROLS IS NOT | | | PERMITTED TO BE ADJACENT TO THE SINK. FBC-ACC 608.2.1. | | | SHT DET-1 SHOWS HOW IT SHOULD BE IF THE SINK WAS ON THE | | | OPPOSITE WALL.SEE FBC-ACC 608.2.2.1 EXCEPTION. | | | | | | 2) PROVIDE CLEAR FLOOR SPACE FOR THE SHOWER. I WAS NOT | | | ABLE TO LOCATE IT ON ANY SHEETS. FBC 107.3.5 | | | | | | 3) SHT. P-2 DETAIL #1 SHOWER PAN DETAIL IS SHOWING A | | | CURB 2"-9". CURB'S/ THRESHOLDS OVER 1/2" ARE NOT | | | PERMITTED (ROLL IN). FBC-ACC 608.7 | | | | | | 4) DRINKING FOUNTAIN SHALL BE A HIGH/ LOW DRINKING | | | FOUNTAIN. FBC-PLUMBING 410.3 | | | | | | 5) SHT DET-1 SHOWS THE WASHING MACHINES AND DRYERS AS | | | HAVING A FORWARD APPROACH. PER FBC-ACC 611.2 ONLY A | | | PARALLEL APPROACH IS PERMITTED. | | | | | | 6) SHOW ALL CLEAR FLOOR SPACE ON SHT.A-1. YOU ARE | | | MISSING THE WASHING MACHINES, DRYERS, KITCHEN SINK, AND | | | SHOWER. NOTE WASHING MACHINES AND DRYERS MUST BE | | | PARALLEL. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2019-03-25 |
|
|
Cont ID |
|
| Sent By |
thunt |
Date |
2019-03-25 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
thunt |
Date |
2019-03-25 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2019-03-25 17:13:46 | PLUMBING 2ND REVIEW**DENIED** | | | | | | 1) COMPLIED | | | | | | 2A) COMPLIED | | | | | | 2B) COMPLIED | | | | | | 2C) COMPLIED | | | | | | 2D) COMPLIED | | | | | | 2E) COMPLIED | | | | | | 2F) PENDING**PROVIDE TOTAL PIPE DEVELOPED LENGTH FROM | | | THE WATER HEATER TO THE FURTHEST FIXTURE. IF OVER 50' A | | | HOT WATER RETURN SYSTEM MUST BE INCORPORATED INTO THE | | | SYSTEM AND COMPLY WITH BOTH FBC-P 607.2, 607.2.1 | | | | | | 2G) COMPLIED | | | | | | 2H) COMPLIED | | | | | | 2I) DISAGREE. FLORIDA ACCESSIBILITY DOES COVER R-4 | | | RESIDENTIAL DWELLING UNIT SUCH AS THIS. YOU ARE | | | COMPLYING WITH THE BATHROOMS WHY WOULD THE KITCHEN AND | | | LAUNDRY AREA NOT ALSO HAVE TO COMPLY? PROVIDE | | | COMPLIANCE WITH FBC-ACCESSIBILITY 809, 809.2.2, 809.3, | | | 804, AND 611 SHOWING COMPLETE DETAIL TO INCLUDE, | | | CABINET/ WASHER AND DRYER HEIGHT, TURNING RADIUS, CLEAR | | | FLOOR SPACE SHOWING THE ENTIRE KITCHEN MEETS THE | | | FLORIDA ACCESSIBILITY CODE. | | | | | | 2J) COMPLIED | | | | | | 3 AND 4) DISAGREE. THE RESIDENTIAL CODE DOES NOT | | | ADDRESS OCCUPANCY CLASSIFICATION OR MIN PLUMBING | | | FIXTURE REQUIREMENTS. THE FBC-PLB 403.1 UNDER R-4 | | | CLASSIFICATION REQUIRES BOTH A DRINKING FOUNTAIN AND A | | | SERVICE SINK. THERE ARE NO EXCEPTION FOR R-4 OCCUPANCY | | | ON THIS ONE . PROVIDE A SERVICE SINK AND DRINKING | | | FOUNTAIN AS REQUIRED BY FBC 403.1 | | | | | | | | | NEW COMMENT: | | | | | | 5) PROVIDE DIMENSIONS FOR THE ADA 1ST FLOOR SHOWER. | | | PROVIDE A COMPLETE DETAIL OF GRAB BAR'S, SHOWER VALVE | | | CONTROLS AND HAND HELD. PROVIDE CLEAR FLOOR SPACE AND | | | LIST WHAT SHOWER COMPARTMENT YOU ARE DESIGNING TO. | | | FBC-ACCESSSIBILITY 608 | | | | | | 6) PROVIDE NOTE AND LOCATION THAT TEMPERED WATER IS | | | GOING TO BE PROVIDE TO ALL HAND WASHING SINKS. | | | FBC-P607.1.2 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS.** | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-11 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-11 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2018-12-11 10:32:50 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH | | | EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES | | | | | | 1ST REVIEW: DENIED | | | 1. PLUMBING PLANS SHALL BE STAMPED/SEALED AND SIGNED BY | | | DESIGNER OF RECORD AS DESCRIBED BY WPB FBC 107.1 AND IN | | | ACCORDANCE WITH FS 471 AND FAC 61G15. | | | 2. PROVIDE A DETAILED SCOPE OF WORK IN ACCORDANCE WITH | | | WPB FPC 107.2.1 WHICH ADDRESSING THE FOLLOWING | | | COMMENTS. | | | A) THE SANITARY BUILDING DRAIN BRANCH SERVICING THE | | | KITCHEN AND LAUNDRY FACILITIES AND THE P-2 FIXTURE | | | APPEAR NOT TO BE EXISTING, BUT RATHER, ADDED. PLEASE | | | CLARIFY. | | | B) PROVIDE SANITARY PLUMBING RISER DIAGRAM FOR NEW | | | SANITARY BUILDING DRAIN BRANCH, P-2 FIXTURE AND POINTS | | | OF CONNECTION. PROVIDE SIZING AND FIXTURE UNIT LOAD FOR | | | EXISTING PIPING AND NEW FIXTURE UNIT LOAD (SEE FBC PL | | | 709) BEING ADDED SHOWING COMPLIANCE WITH FBC PL 710. | | | SHOW ALL FIXTURE DRAINS, BRANCHES, TRAPS AND VENTS. | | | C) PROVIDE FLOOR PLAN AND RISER DIAGRAM OF NEW POTABLE | | | WATER DISTRIBUTION AND POINT(S) OF CONNECTION. PROVIDE | | | SIZING AND LOAD/DEMAND FOR NEW AND EXISTING PIPING | | | SHOWING COMPLIANCE WITH FBC PL 604. | | | D) PROVIDE LOCATION OF EXISTING BACKFLOW PREVENTER FOR | | | THE WATER SUPPLY. PROVIDE DOCUMENTATION OF CURRENT | | | CERTIFICATION FOR THE SAME. | | | E) PROVIDE A FIXTURE SCHEDULE OF ALL AFFECTED FIXTURES | | | REPLACED OR ADDED. SPECIFY SHOWER CONTROL VALVES AND | | | VACUUM BREAKERS FOR HAND HELD SHOWERS. INDICATE ON THE | | | PLAN WHICH FIXTURES ARE ADDED AND WHICH ARE BEING | | | REPLACED. | | | F) PROVIDE WATER HEATER SCHEDULE NOTING STORAGE | | | CAPACITY AND ELECTRICAL CHARACTERISTICS. COORDINATE | | | WITH ELECTRICAL DESIGN. PROVIDE WATER HEATER DETAIL, | | | SHOWING COMPLIANCE WITH THE REQUIREMENTS OF FBC PL 504 | | | AND 607.3. | | | G) PROVIDE SHOWER PAN DETAIL, SHOWING COMPLIANCE WITH | | | THE REQUIREMENTS OF FBC PL 417. | | | H) PROVIDE DETAIL FOR WASHER BOX WITH FIXTURE DRAIN, | | | TRAP AND WATER OUTLETS. SHOW COMPLIANCE WITH FBC 604.9. | | | I) PROVIDE DETAIL FOR KITCHEN CABINET AND SINK SHOWING | | | COMPLIANCE WITH FBC ACC 233, 809, 804 AND 606. | | | J) PROVIDE DETAIL ON ICE LINE IF APPLICABLE. SHOW | | | COMPLIANCE WITH FBC 604.9. | | | K) SHOW DISHWASHER COMPLIANCE WITH FBC 604.9. | | | 3. PROVIDE A SERVICE SINK IN ACCORDANCE WITH FBC PL | | | TABLE 403.1 | | | 4. PROVIDE A DRINKING FOUNTAIN IN ACCORDANCE WITH FBC | | | PL TABLE 403.1. DRINKING FOUNTAIN SHALL BE BARRIER FREE | | | IN ACCORDANCE WITH FBC ACC 211 AND 602. | | | | | | END OF COMMENTS | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN | | | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED "VOID". | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2019-06-05 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-06-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-06-05 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-05 15:19:39 | - MAXIMUM # OF BEDS FOR THE ENTIRE FACILITY = 41 BEDS | | | - # OF BEDS PROPOSED FOR THE ENTIRE FACILITY = 34 BEDS | | | ( 317 N. LAKESIDE CT. = 26 BEDS + 313 N. LAKESIDE CT. = | | | 8 BEDS) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2019-05-03 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-05-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-04-30 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2019-05-03 13:49:45 | - MAXIMUM # OF BEDS FOR THE ENTIRE FACILITY = 41 BEDS | | | - # OF BEDS PROPOSED FOR THE ENTIRE FACILITY = 35 BEDS | | | ( 317 N. LAKESIDE CT. = 26 BEDS + 313 N. LAKESIDE CT. = | | | 9 BEDS) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2019-03-21 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2019-03-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2019-03-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-03-21 09:09:16 | MAXIMUM NUMBER OF BEDS FOR THE FACILITY = 41 BEDS | | | | | | APPROVED BED COUNT (#18050930): HIBISCUS HOUSE @ 313 | | | LAKESIDE CT. = 9 BEDS; LOTUS HOUSE @ 317 LAKESIDE CT. = | | | 26 BEDS | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2018-11-15 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2018-11-15 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-11-15 09:14:29 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY. SURVEY | | | IS MISSING FROM THE PERMIT APPLICATION. | | | | | | 2.) PER STAFF'S RECORDS, A MAXIMUM OF 41 BEDS IS | | | PERMITTED FOR THE ENTIRE FACILITY. SINCE MULTIPLE | | | BUILDING PERMITS HAVE BEEN SUBMITTED FOR THE RENOVATION | | | OF VARIOUS BUILDINGS WITHIN THE FACILITY, IT IS | | | IMPORTANT TO PROVIDE AN UPDATED/PROPOSED BED COUNT. | | | PLEASE PROVIDE A TABULAR WITH THE BED CALCULATIONS FOR | | | THE OVERALL FACILITY WITHIN THE PLANS. | | | | | | 3.) EXISTING FLOOR PLAN ON SHEET A-1 SEEMS TO BE | | | MISLABELED. PLEASE CORRECT. | | | | | | 4.) PROPOSED FLOOR PLAN IS MISSING FROM THE PERMIT SET. | | | PLEASE PROVIDE. ALSO INDICATE THE NUMBER OF BEDS | | | PROPOSED FOR THE SCOPE. | | | | | | 5.) ANY CHANGES TO THE ARCHITECTURAL PLANS SHALL BE | | | REFLECTED IN ALL PLANS FOR CONSISTENCY (I.E. ELECTRICAL | | | AND PLUMBING PLANS, ETC.). | | | | | | | | | NOTES: | | | | | | * EXISTING TREATMENT FACILITY. | | | | | | * MAXIMUM NUMBER OF BEDS FOR THE FACILITY = 41 BEDS | | | | | | * PER PERMIT #18050930: HIBISCUS HOUSE @ 313 LAKESIDE | | | CT. = 9 BEDS; LOTUS HOUSE @ 317 LAKESIDE CT. = 26 BEDS | | | | | | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * ZONE: GC AND POR | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|