Plan Review Details - Permit 18110199
Plan Review Stops For Permit 18110199
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-22 Cont ID  
Sent By jduprey Date 2019-02-22 Time 11:57 Rev Time 0.00
Received By jduprey Date 2019-02-22 Time 11:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 15:03 Rev Time 0.00
Received By shill Date 2018-12-08 Time 15:03 Sent To  
Notes
2018-12-08 15:19:51****CORRECTIONS****
  
 SAMANTHA HILL / JOSEAN DUPREY
 BUILDING PLANS EXAMINER
 [email protected], [email protected]
 561-805-6719
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A 1.1 HAS IRRELEVANT NOTES (OR NON COMPLIANT); FOR
 INSTANCE, ROUGH CARPENTRY SPECIFIED BUT THIS IS A NON
 COMBUSTIBLE BUILDING. REVISE TO REMOVE NOTES NOT
 APPLICABLE OR CLARIFY, FBC 107.
  
 2. A1.2 HAS INCORRECT NOTES; BROWARD COUNTY IS
 REFERENCED, ANSI/ASCE 7-10; CHECK ALL AND REVISE.
  
 3. A SIGNIFICANT PORTION OF THE FLOOR PLAN ON SHEET
 LS1.0 HAS BEEN HATCHED OFF AS "NO OCCUPANTS". GROSS
 SQUARE FOOT AREA IS TO BE USED TO CALCULATE OCCUPANCY,
 REVISE, SEE FBC B TABLE 1004.1.2.
  
 4. IT IS NOT CLEAR IF AN ACCESSIBLE ROUTE HAS BEEN
 PROVIDED TO THE MANICURE AREA, FBC A 202.4. THERE IS A
 SHELF BEHIND THE MANICURE AREA WHICH APPEARS TO
 OBSTRUCT THE ACCESSIBLE ROUTE. IF THIS IS THE "WORK
 AREA" SIDE, THE ABILITY TO ENTER AND EXIT IS TO BE
 PROVIDED FBC A 203.9. REVISE PLAN TO CLEARLY
 DEMONSTRATE COMPLIANCE.
  
 5. IT APPEARS THAT THE RECEPTION DESK WILL BE USED TO
 CHECK OUT; SEE FBC A 904.4.3, 904.4 AND REVISE PLAN TO
 SHOW COMPLIANCE.
  
 6. A MICROWAVE IS SHOWN BUT HEIGHT IS NOT CLEAR. REACH
 RANGE DETAILS WERE PROVIDED BUT IT IS NOT CLEAR IF THE
 PROPOSED LOCATION COMPLIES, AND IF NOT, IF THERE IS
 ANOTHER OPEN SHELF WITH OUTLET ACCESS WHICH DOES MEET
 THE REQUIREMENT IN THE EVENT ACCOMODATION WAS NEEDED,
 FBC A 804.6.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-04-08 Cont ID  
Sent By jpearson Date 2019-04-08 Time 10:04 Rev Time 0.00
Received By jpearson Date 2019-04-08 Time 10:04 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-05 Cont ID  
Sent By jpearson Date 2019-02-05 Time 13:34 Rev Time 0.00
Received By jpearson Date 2019-02-05 Time 07:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-30 Cont ID  
Sent By jpearson Date 2018-11-30 Time 12:47 Rev Time 0.00
Received By jpearson Date 2018-11-30 Time 09:37 Sent To  
Notes
2018-11-30 12:47:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. WILL THERE BE SHOW WINDOWS? IF SO, PROVIDE SHOW
 WINDOW OUTLETS AS REQUIRED PER CODE. NEC 210.62
 3. ALL OUTDOOR RECEPTACLE OUTLETS REQUIRED GFCI
 PROTECTION. PROVIDE CORRECTION FOR RECEPTACLE ADJACENT
 TO OUTSIDE AC UNITS. NEC 210.8
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By scaldero Date 2019-01-23 Time 08:25 Rev Time 0.00
Received By scaldero Date 2019-01-23 Time 08:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-08 Cont ID  
Sent By scaldero Date 2018-11-08 Time 10:30 Rev Time 0.00
Received By scaldero Date 2018-11-08 Time 10:15 Sent To  
Notes
2018-11-08 10:30:36PERMIT # 18110199
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) SHEET LS-1.0: GENERAL NOTES #6 REFERENCES "BROWARD
 COUNTY AMENDMENTS". PLEASE REMOVE THIS LANGUAGE AS THE
 PROJECT IS LOCATED IN PALM BEACH COUNTY.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-04-10 Time   Rev Time 0.00
Received By lmarchan Date 2019-04-02 Time 15:40 Sent To  
Notes
2019-04-03 15:40:12RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-22 Cont ID  
Sent By jduprey Date 2019-02-22 Time 11:57 Rev Time 0.00
Received By jduprey Date 2019-01-18 Time 15:39 Sent To  
Notes
2019-02-16 11:34:402/16 REMOVED FROM BOARD, ROUTED TO JD DESK / S.HILL
2019-01-31 11:00:49ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/31/19 EL
2019-01-22 15:39:48B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2018-12-27 Cont ID  
Sent By gjohnson Date 2018-12-27 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2018-11-06 Time 14:30 Sent To  
Notes
2018-11-20 09:53:06ROUTED FROM ZONING TO PERMIT LIBRARIAN 11/20/18
2018-11-07 14:30:17B31

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-04-10 Cont ID  
Sent By ccole Date 2019-04-10 Time 14:30 Rev Time 0.00
Received By ccole Date 2019-04-10 Time 14:30 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-01 Cont ID  
Sent By ccole Date 2019-02-01 Time 12:15 Rev Time 0.00
Received By ccole Date 2019-01-31 Time 17:17 Sent To  
Notes
2019-02-01 12:21:372ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110199
 2/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE AN AIR BALANCE CALCULATION- SEE
 SECTION 501.4 FBC M.
  
 2) M-1: ONE OF THE PEDICURE CHAIRS HAS NOT BEEN
 INCLUDED IN THE VENTILATION CALCULATIONS, OR IN THE
 SOURCE CAPTURE LAYOUT PLAN. PLEASE REVISE THE PLAN
 ACCORDINGLY.
  
 3) M-1: THE EXHAUST FAN AND AHU'S ABOVE THE GYPSUM
 CEILINGS REQUIRE ACCESS PANELS LARGE ENOUGH FOR
 MANINTENANCE AND REPLACEMENT OF THE UNITS- SECTION
 306.1 FBC M.
  
 4) M-1: VERIFY THE NAIL EXHAUST DUCT OUTLET IS IN
 COMPLIANCE WITH THE REQUIRED CLEARANCES LISTED IN
 SECTION 501.3.1 (2) FBC M.
  
 5) M-1: THE OUTTDOOR CONDENSER UNITS CANNOT BE
 INSTALLED INSIDE THE PARKING GARAGE UNLESS CERTIFIED BY
 THE MANUFACTURER TO BE INCOMPLIANCE WOTH THE
 INSTALLATIO GUIDELINES AND IN ACCORDANCE WITH THE
 CONDITIONS OF THEIR LISTING- SECTION 304.1 FBC M.
  
 6) M-1: SUBMIT A FL. PRODUCT APPROVAL AND/OR A
 MIAMI-DADE NOA FOR THE LOUVER- RULE 9N-3 FAC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-29 Cont ID  
Sent By ccole Date 2018-11-29 Time 16:11 Rev Time 0.00
Received By ccole Date 2018-11-29 Time 16:11 Sent To  
Notes
2018-11-29 17:20:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110199
 11/29/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: PROVIDE THE SEQUENCE OF OPERATION FOR THE
 SALON EXHAUST SYSTEM- TABLE 403.3.1.1 FOOTNOTE H, AND
 SECTION 501.3.2 FBC M.
  
 2) M-1 & M-2: PROVIDE A DETAIL SHOWING HOW THE MANICURE
 EXHAUST INLETS WILL BE ATTACHED TO THE TABLES- SECTION
 502.20 FBC M.
  
 3) M-1 & M-2:SHOW THE DIMENSIONS OF THE ACCESS PANELS
 AND VERIFY THEY ARE LARGE ENOUGH TO REMOVE AND REPLACE
 THE AIR HANDLERS ABOVE THE CEILINGS- SECTION 306.1 FBC
 M.
  
 4) M-1: RECIRCULATION OF AIR FROM THE SALON TO THE
 BREAKROOM AND RESTOOM IS PROHIBITED PER TABLE 403.3.1.1
 FOOTNOTE B.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE GULFSTREAM AIR VENT
 SYSTEM- SECTION 304.1 FBC M.
  
 6) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE WALL BRACKET AND CONDENSER
 INSTALLATION- SECTION 301.15 FBC M & SECTION 1609 FBC
 B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By jesmith Date 2019-02-07 Time 15:16 Rev Time 0.00
Received By jesmith Date 2019-02-07 Time 15:15 Sent To  
Notes
2019-02-07 15:16:09APPROVED
 PROVISO
 1. THE CIRCUIT VENTED BRANCH FOR THE 5 PEDICURE SPA
 CHAIRS REQUIRES THE VENT CONNECTION BETWEEN THE TWO
 MOST UPSTREAM FIXTURE DRAIN AND A RELIEF VENT
 DOWNSTREAM OF THE FIXTURES PER FBC PL 914.2 & 914.4
 2. PROVIDE ACCESS TO THE INTERCEPTOR FOR THE WASHER
 THROUGH THE BACKSIDE OF THE WALL PER FBC PL 1003.10
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-27 Cont ID  
Sent By gjohnson Date 2018-12-27 Time 11:56 Rev Time 0.00
Received By gjohnson Date 2018-12-27 Time 11:56 Sent To  
Notes
2018-12-27 12:44:311ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE DETAIL FOR THE WATER FOUNTAIN WITH
 DIMENSIONS COMPILING WITH BC ACC 602.2, 602.4, 602.7
  
 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. PER FBC
 ACC 604.7
  
 3. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE. PER FBC ACC 609.4
  
 4. A SERVICE SINK IS REQUIRED INDICATE ON THE PLAN
 LOCATION. PER FBC PL TABLE 403.1
  
 5. TWO ACCESSIBLE BATHROOMS ARE REQUIRED THEY SHALL BE
 SEPARATE FACILITIES SHALL BE PROVIDED FOR EACH SEX. PER
 FBC PL TABLE 403.1 AND 403.2 FBC ACC 213
  
 6. THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. FOR THE 5
 PEDICURE SPA CHARS. PER FBC 914.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-31 Cont ID  
Sent By elevesqu Date 2019-01-31 Time 11:00 Rev Time 0.00
Received By elevesqu Date 2019-01-31 Time 11:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By aaponte Date 2018-11-20 Time 09:52 Rev Time 0.00
Received By elevesqu Date 2018-11-20 Time 09:50 Sent To  
Notes
2018-11-20 09:52:49PLEASE SUBMIT FLOOR PLAN OR PARTIAL FLOOR PLAN THAT
 INDICATES THE TENANT SPACE THAT THIS BUSINESS WILL BE
 OCCUPYING.
 PLEASE LABEL STREET NAMES ON FLOOR PLAN FOR
 CLARIFICATION.
  
 IF THE FLOOR PLAN IS CHANGING FOR THIS TENANT
 (SPLITTING RETAIL BAYS, EXPANDING, ETC), PLEASE INCLUDE
 DETAIL FOR CLARIFICATION.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]