Plan Review Details - Permit 18110181
Plan Review Stops For Permit 18110181
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-07 Cont ID  
Sent By shill Date 2019-01-07 Time 10:56 Rev Time 0.00
Received By shill Date 2019-01-03 Time 18:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 14:18 Rev Time 0.00
Received By shill Date 2018-12-08 Time 14:18 Sent To  
Notes
2018-12-08 14:18:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FOR THE FLOORING UNDERLAYMENT PROPOSED, PLEASE
 PROVIDE THE FOLLOWING THREE TEST REPORTS:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 THIS INFORMATION MAY BE SENT VIA EMAIL FOR PRELIMINARY
 REVIEW.
  
 2. SPECIFY THE DRYWALL IN THE BATHROOM; SEE FBC B 2509.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-25 Cont ID  
Sent By jpearson Date 2018-12-25 Time 08:23 Rev Time 0.00
Received By jpearson Date 2018-12-25 Time 08:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-29 Cont ID  
Sent By jpearson Date 2018-11-29 Time 17:51 Rev Time 0.00
Received By jpearson Date 2018-11-29 Time 16:59 Sent To  
Notes
2018-11-29 17:51:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. ELECTRICAL PANEL IS SHOWN OVER A KITCHEN COUNTER.
 ELECTRICAL PANELS ARE REQUIRED TO HAVE 3 FEET OF
 CLEARANCE IN FRONT. PROVIDE CORRECTION. NEC 110.26
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 4. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-11-08 Cont ID  
Sent By scaldero Date 2018-11-08 Time 10:04 Rev Time 0.00
Received By scaldero Date 2018-11-08 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-07 Cont ID  
Sent By shill Date 2019-01-07 Time 10:56 Rev Time 0.00
Received By shill Date 2018-12-18 Time 13:27 Sent To  
Notes
2019-01-03 18:01:251/3 REMOVED FROM BOARD; ON SH DESK
  
  
2018-12-19 13:27:57B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 13:03 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 13:03 Sent To  
Notes
2018-12-08 14:19:2612/8 TOOK OF BOARD AND ROUTED TO JES DESK / S.HILL
  
  
2018-11-06 14:43:02B16

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-02 Cont ID  
Sent By jesmith Date 2019-01-02 Time 15:30 Rev Time 0.00
Received By jesmith Date 2019-01-02 Time 15:30 Sent To  
Notes
2019-01-02 15:30:36APPROVED

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 13:02 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 12:42 Sent To  
Notes
2018-12-11 13:01:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. CHANGING BATHTUB TO A SHOWER REQUIRES CHANGE OF
 PIPING BELOW FLOOR. PROVIDE FIRE RATING OF ELEVATED
 FLOOR AND PROVIDE ASSEMBLY FOR DEALING WITH THE FLOOR
 PENETRATION COMPLYING WITH FBC 714.4 THROUGH 714.4.1.2.
 2. PROVIDE SHOWER PAN DETAIL, SHOWING COMPLIANCE WITH
 THE REQUIREMENTS OF FBC PL 417.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715