Plan Review Details - Permit 18110176
Plan Review Stops For Permit 18110176
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-15 Cont ID  
Sent By dbattles Date 2019-01-15 Time 08:12 Rev Time 0.00
Received By dbattles Date 2019-01-15 Time 08:12 Sent To  
Notes
2019-01-15 08:15:59PROVISO:
 PROVIDE PROCUCT APPROVAL FOR FRONT DOOR/STOREFRONT
 SUBMITTAL.
2019-01-04 13:26:12PLEASE EVALUATE 16040412, 16040415, & 17080987 FOR
 REVOCATION. CANCELLATION REQUESTS ARE ON FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-07 Cont ID  
Sent By dbattles Date 2018-12-07 Time 10:47 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 10:44 Sent To  
Notes
2018-12-07 10:50:44****CORRECTIONS****
 W.P.B. PERMIT: 18110176
 REVIEWED: DECEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC ENERGY C401.2]APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 A. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 B. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 C. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 2. [FBC EXISTING 501]STATE CLASSIFICATION FOR WORK
 BEING PERFORMED.
 STATE THE EXISTING OCCUPANCY OF THE BUILDING.
 THE CLASSIFICATION SHOULD BE CHANGE OF OCCUPANCY OR
 LEVEL OF ALTERATION.
  
 3. [FBC 303.3]ASSEMBLY GROUP A-2
 SHOW OCCUPANCY AS A-2 FOR THE 1634 SQ. FT.
 THE AMOUNT OF OCCUPANT LOAD IN THE COMMERCIAL KITCHEN
 SHOULD BE DETERMINED IN TABLE 1004.1.2. COMMERCIAL
 KITCHENS USE 200 SQ. FT. GROSS.
 A) PLEASE UPDATE SHEET 1.3A TO SHOW OCCUPANCY TYPES AND
 OCCUPANT LOADS.
 B) ADJUST NOTE #11 TO MATCH OCCUPANT LOAD.
  
 4. [FBC 107.3.5.3]SHEET C-1
 A) UPDATE CODE VERSIONS IN GENERAL NOTES TO USE THE
 FLORIDA BUILDING CODE, 6TH EDITION (2017)
 B) UNDER OCCUPANCY TYPE CHANGE TO A-2.
 C) CHANGE NUMBER OF SEATS TO MATCH 1.3A
 D) ADD SHEETS 1.5A AND 4.1M TO INDEX
  
  
 5. [FBC P403.2]SEPARATE FACILITIES. WHERE PLUMBING
 FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 LABEL MENS AND WOMENS RESTROOMS.
  
 6. [FBC 456.3.2.2]PUBLIC BATHROOMS SHALL BE COMPLETELY
 ENCLOSED AND SHALL HAVE TIGHT-FITTING, SELF-CLOSING
 DOORS.
 UPDATE DOOR SCHEDULE AS APPLICABLE.
  
 7. [FBC 1210.2.2]WALLS AND PARTITIONS. WALLS AND
 PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO
 A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE
 FLOOR,
 AND EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED
 IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED
 BY MOISTURE.
  
 8. [FBC TABLE 2902.1]WHERE IS SERVICE SINK LOCATED?
  
 9. [FBC A206.1]GENERAL.
 ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH
 206 AND SHALL COMPLY WITH CHAPTER 4.
 A) PROVIDE SITE PLAN WITH PARKING LAYOUT.
 B) SHOW ACCESSIBLE PATH FROM PARKING TO ACCESSIBLE
 ENTRY.
  
 10. [FBC A226.1]THE ACCESSIBILITY CODE REQUIRES 0.05 %
 OF ALL SEATING TO BE ACCESSIBLE.
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902.
 SHOW 5% OF SEATING TO COMPLY WITH 226.1 AND 902.
  
 11. [FBC A(FIGURE 404.2.4.1)]SHOW DOOR CLEARANCE IN
 RESTROOMS FOR APPLICABLE APPROACH WITH CLOSER AND
 LATCH.
  
 12. [FBC 107.3.5]SECTION 2-1.2A DOESN?T MATCH FLOOR
 PLAN 1.0A WHERE IT IS CALLED OUT.
 HOW DOES WOOD BURNING PIZZA OVEN WORK IN PLAN VIEW?
  
 13. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL FOR
 OPENING #6, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 14. [FBC 107.5.1]EXPIRED PERMITS NEED TO BE ADDRESSED.
 SEE THE EXPIRED PERMITS LISTED BELOW.
 17080987, 15070429, 14030723, 11100171, 10090416 AND
 09070635.
 ANY OF THESE THAT AFFECT THIS PROJECT SHOULD BE
 ADDRESSED PRIOR TO PERMIT ISSUANCE AND THE PERMITS FROM
 OTHER UNITS CAN BE A PROVISO OF PERMIT TO BE COMPLETED
 PRIOR TO CERTIFICATE OF OCCUPANCY.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  
2018-11-21 14:30:47BUILDING PLANS EXAMINER, PLEASE NOTE THERE ARE SEVERAL
 EXPIRED PERMITS ON RECORD FOR THIS SPACE. PLEASE
 COORDINATE WITH APPLICANT TO ADDRESS THE STATUS OF EACH
 AND EVALUATE RESOLUTION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-17 Cont ID  
Sent By jleahy Date 2019-01-17 Time 10:52 Rev Time 0.00
Received By jleahy Date 2019-01-17 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-19 Cont ID  
Sent By jleahy Date 2018-11-19 Time 15:45 Rev Time 0.00
Received By jleahy Date 2018-11-19 Time 15:45 Sent To  
Notes
2018-11-19 16:59:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE 1.5A
  
 NO TYPE "H" FIXTURE
 TYPE "B" SHOWS NO WATTAGE
  
 PAGE 2.0E
  
 NEED AIC CALCULATION FOR NEW K7 AND PANELS
 CIRCUIT B-1 SHOW AUDIO VISUAL, NEXT PAGE SHOWS ALL THE
 LIGHTING ON THIS CORCUIT.
 CIRCUIT B-SHOWS AS A SPARE
  
 PAGE 2.1E
  
 B-3 IS LIGHTING CIRCUIT
 B-15 IS TRACK CIRCUIT
  
 PAGE 2.2E
  
 ALL RTUS HAVE SAME CIRCUIT DESIGNATION
 WINEN ACC NO CKT DESIGNATION
 SUPPLY FAN AND EXHAUST FAN SHOW SAME CIRCUIT
 DESIGNATION
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-18 Cont ID  
Sent By pleduc Date 2019-01-18 Time   Rev Time 0.00
Received By pleduc Date 2019-01-18 Time 12:23 Sent To Z
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By pleduc Date 2018-11-07 Time   Rev Time 0.00
Received By pleduc Date 2018-11-07 Time 14:35 Sent To  
Notes
2018-11-07 15:26:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET C 1 - THERE IA AN INDICATION THAT THIS IS A
 MERCANTILE OCCUPANCY.
  
 PER THE FLORIDA FIRE PREVENTION CODE, 6TH ED THIS IS AN
 ASSEMBLY OCCUPANCY.
  
 NFPA 101, CHAPTER 6, OCCUPANCY CLSSIFICATION
  
 6.1.2.1* DEFINITION ? ASSEMBLY OCCUPANCY. AN OCCUPANCY
 (1) USED
 FOR A GATHERING OF 50 OR MORE PERSONS FOR DELIBERATION,
 WORSHIP,
 ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING
 TRANSPORTATION, OR
 SIMILAR USES; OR (2) USED AS A SPECIAL AMUSEMENT
 BUILDING, REGARDLESS OF
 OCCUPANT LOAD.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 2) SHEET C 1 - THERE ARE INDICATION OF INCORRECT
 REFERNCES TO THE FLORIDA FIRE PREVEENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
  
 PLEASE REIVEW AND CORRECT.
  
  
  
  
 3) SHEET 1.1A - THERE IS A PIZZA OVEN INDICATED. THERE
 ARE NO MANUFACTURES SPECIFICATION AND REQUIREMENT
 SHEETS PROVIDED.
  
 PLEASE PROVIDE THE PROPOSED PIZZA OVEN SPEC SHEETS.
  
  
  
 4) SHEET 1.1A - THERE IS HOOD AND SUPPRESSION SYSTEM
 INDICATED. THESE SYSTEMS SHALL BE PROVIDED AND
 INSTALLED PER NFPA 96, 2014 ED., UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDEGMENT AND COMPLIANCE.
  
  
  
 5) SHEET 1.2A - THERE IS AN INDICATION OF A WOOD
 BURNING PIZZA OVEN, PLEASE PROVIDE FOR # 3 ABOVE AS
 WELL AS WHERE AND HOW MUCH WOOD WILL BE STORED ON SITE.
  
 PLEASE REVIEW NFPA 211, STANDARD FOR CHIMNEYS,
 FIREPLACES, VENTS, AND SOLID FUEL?, BURNING APPLIANCES,
 2013 EDITION.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENTS BASED ON
 YOUR NEEDS AND PROVIDE APPLICABLE SPECIFIC SITE DETAILS
 AND NARRATIVE NOTES.
  
  
  
 6) SHEET 1.3A - THERE IS A NOTE, # 6, INDICATING DUCT
 SMOKE DETECTORS WITH AN INCORRECT EDITION.
  
 AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B,
 2015 EDITION.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 7) SHEET 1.3A - THERE IS A NOTE, # 11 INDICATING A
 OCCUPANCY LOAD SIGN OF 88. THERE IS A CONFLICT WITH THE
 OCCUPANCY LOAD CALCULATION TABLE OF 109 + 21 BAR = 130
  
 PLEAE REVIEW AND EXPLAIN AND CORRECT.
  
  
  
 8) SHEET 1.3A - SHEET C 1 & 1.3A - SHEET C 1 INDICATES
 150 SEATS. SHEETS 1.3A INDICATES 134 ACTUAL SEATA AND
 15 BAR STOOLS FOR A TOTAL OF 149.
  
 THE OCCUPANCY LOAD CALCULATIONS INDICATED 109 TOTAL
 PEOPLE FOR THE PROPOSEDSQ FT. WHICH INCLUDES THE BAR.
  
 THERE ARE MULTIPLE CONFLICTS WITH THE OCCUPANCY LOAD
 CALCULATIONS AND INFO ON MULTIPLE SHEETS.
  
 PLEASE REVIEW AND CORRECT AND JUSTIFY WITH SPECIFIC
 CODE REFERENCES.
  
  
  
 9) SHEET 1.3A - THERE ARE NO DIMENSIONS OS AISLES AND
 BETWEEN SEATS AND TABLES THAT MEET THE REQUIRMENTS OF
 THE CODE.
  
 PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES.
  
 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT
 TABLES SHALL BE
 NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN
 OCCUPANT LOAD
 EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN
 OCCUPANT
 LOAD OF 50 OR FEWER.
 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF
 THE AISLE SHALL
 BE MADE TO A LINE 19 IN. (485 MM), MEASURED
 PERPENDICULARLY TO
 THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID
 TABLE.
 12.2.5.9 APPROVAL OF LAYOUTS.
 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF
 FURNISHINGS OR
 EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE
 BUILDING
 OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE
 WITH THE PROVISIONS OF 12.2.5.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED DIMENSIONS
  
  
 10) SHEET 1.3A - THERE ARE 14 STOOLS INDICATED AT THE
 BAR. THE OCCUPANCY LOEAD INDICATES 21. WHICH IS
 CORRECT?
  
 PLEASE PROVIDE FOR THE ACCURATE ACCOUNTING OF BAR
 STOOLS PER THE CALULATION AND # 8 ABOVE.
  
  
  
 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-01-17 Cont ID  
Sent By jesmith Date 2018-12-06 Time 16:26 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 16:08 Sent To  
Notes
2019-01-22 08:15:51SUBMITTED GAS RISER DIAGRAM DOES NOT MATCH SUBMITTED
 GAS EQUIPMENT; DESIGNER WAS ADVISED BY CCOLE ON
 1/18/2019
2018-12-06 16:09:06GAS PERMIT IS REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-27 Cont ID  
Sent By cpuell Date 2019-01-27 Time 09:33 Rev Time 0.00
Received By cpuell Date 2019-01-07 Time 13:43 Sent To  
Notes
2019-01-08 13:44:01B25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-19 Cont ID  
Sent By cpuell Date 2018-12-19 Time 16:02 Rev Time 0.00
Received By cpuell Date 2018-11-05 Time 14:36 Sent To  
Notes
2018-12-08 11:10:2312/8 TO ZONING BOX; SENT EMAIL TO ES/DB
  
  
2018-11-06 14:36:45B11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-04-02 Cont ID  
Sent By dbattles Date 2019-04-02 Time 11:55 Rev Time 0.00
Received By dbattles Date 2019-04-02 Time 11:55 Sent To  
Notes
2019-04-02 11:58:03OK - STAMP ON PLANS
 MU-2019-002811-0000 RECEIPT PROVIDED

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-12-07 Cont ID  
Sent By dbattles Date 2018-12-07 Time 10:51 Rev Time 0.00
Received By dbattles Date 2018-12-07 Time 10:51 Sent To  
Notes
2019-01-15 08:17:01UPON APPROVAL OF ALL TRADES CHECK OUT ONE SET FOR THE
 PBC IMPACT REVIEW.
 SEE PREVIOUS NOTE FOR DETAILS.
2018-12-07 10:51:35DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 [FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-17 Cont ID  
Sent By ccole Date 2019-01-17 Time 10:46 Rev Time 0.00
Received By ccole Date 2019-01-16 Time 17:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By ccole Date 2018-11-27 Time 16:27 Rev Time 0.00
Received By ccole Date 2018-11-27 Time 16:27 Sent To  
Notes
2018-11-27 16:39:091ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110176
 11/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0M: PLEASE LABEL THE RTU'S ON THE PLAN AS
 EITHER NEW OR EXISTING. IT APPEARS BY THE SCHEDULE THAT
 ONLY RTU-1 IS BEING REPLACED. IS THAT CORRECT, OR ARE
 ALL THE RTU'S BEING REPLACED?
  
 2) 4.0M: PLEASE INCLUDE EF-3 IN THE AIR BALANCE
 CALCULATION.
  
 3) 4.0M: PLEASE INCLUDE THE PIZZA OVEN AND EXHAUST
 SYSTEM IN THE SEPARATE PERMIT LIST.
  
 4) 4.0M: ALTHOUGH SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOOD, PIZZA OVEN AND FIRE SUPPRESSION
 SYSTEM, PLEASE BE ADVISED THAT SECTION 508.1.1 FBC M IS
 APPLICABLE TO THIS PROJECT.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
  
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
  
 6) 4.0M: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 7) 4.0M: CLARIFY IF THE BTUH LOAD OF THE PIZZA OVEN IS
 INCLUDED IN THE TOTAL BTUH LOAD SHOWN IN THE COMBUSTION
 AIR CALCULATION- SECTION 304.9 FBC FG.
  
 8) SHEETS 1.2A & M4.0M: ALTHOUGH UNDER SEPARATE PERMIT,
 THE WOOD-FIRED PIZZA OVEN SHALL BE UL 2162 LISTED AND
 LABELED PER SECTION 917.1 FBC M. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS OR A UL CERTIFICATE TO
 VERIFY COMPLIANCE.
  
 9) M4.0M: THE PLAN INDICATES A B-VENT WILL BE USED AS
 AN EXHAUST FLUE FOR THE OVEN. THIS TYPE OF VENT IS
 TYPICALLY NOT PERMITTED FOR HIGH HEAT COOKING
 APPLIANCES. PLEASE INDICATE THE CORRECT FLUE VENT PER
 THE MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE OVEN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-17 Cont ID  
Sent By jesmith Date 2019-01-17 Time 15:40 Rev Time 0.00
Received By jesmith Date   Time   Sent To  
Notes
2019-01-22 08:04:00RE: GREASE INTERCEPTOR CALCULATIONS; PER WPB FBC
 107.3.4.1 MAY BE PROVIDED AS DEFERRED SUBMITTALS PRIOR
 TO ISSUE OF GREASE INTERCEPTOR PERMIT. RECEIVED AND
 APPROVED 1/22/2019
2019-01-17 15:40:15APPROVED
 PROVISO
 1. RE: MEN'S TOILET ROOM; URINAL SHALL NOT DISCHARGE
 INTO THE WET VENT FOR THE WATER CLOSET PER FBC PL
 912.1. SEE REDLINED DRAWINGS 3.0P AND 3.1P FOR
 CORRECTION.
 2. RE: GREASE INTERCEPTOR CALCULATIONS; PER WPB FBC
 107.3.4.1 MAY BE PROVIDED AS DEFERRED SUBMITTALS PRIOR
 TO ISSUE OF GREASE INTERCEPTOR PERMIT.
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 THROUGH AN APPROVED WATER-TEMPERATURE LIMITING DEVICE
 THAT CONFORMS TO ASSE 1070 OR CSA B125.3 PERFBC 416.5.
 4. BACKFLOW PREVENTION ISREQUIRED FOR COFFEEMAKERS, ICE
 MAKERS AND FILTERS PER FBC 608.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By jesmith Date 2018-12-06 Time 16:07 Rev Time 0.00
Received By jesmith Date 2018-12-06 Time 16:00 Sent To  
Notes
2018-12-06 16:07:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES1ST
  
 REVIEW: DENIED
  
 1. PROVIDE THE FOLLOWING PER WPB FBC
 A) SANITARY PLUMBING RISER DIAGRAM
 B) POTABLE WATER DISTRIBUTION RISER DIAGRAM
 C) FIXTURE SCHEDULE NOTING WATER USAGE, WATER SUPPLY
 AND DRAIN REQUIREMENTS. INDICATE TEMPERATURE LIMITING
 DEVICES ON FIXTURES THAT REQUIRE THE SAME.
 D) KITCHEN EQUIPMENT SCHEDULE NOTING WATER USAGE, WATER
 SUPPLY AND DRAIN REQUIREMENTS (ALSO FUEL GAS CONN IF
 APPLICABLE).
 E) FLOOR DRAIN/FLOOR SINK SCHEDULE NOTING USAGE AND
 TRAP PRIMER REQUIREMENTS
 F) PROVIDE A TRAP PRIMER DETAIL FOR FLOOR DRAINS
 G) PROVIDE CALCULATIONS FOR SIZING OF GREASE
 INTERCEPTOR ALONG WITH GREASE INTERCEPTOR DETAIL
 SHOWING SAMPLING PORT, CLEANOUTS AND LID TRAFFIC
 RATING.
 H) REMOVE COMMENTS THAT ARE NOT APPLICABLE SUCH AS
 ?TANKLESS WATER HEATER LOCATION ON ROOF?.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-25 Cont ID  
Sent By eschneid Date 2019-01-25 Time 16:47 Rev Time 0.25
Received By eschneid Date 2019-01-25 Time 16:33 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-19 Cont ID  
Sent By eschnide Date 2018-12-19 Time 14:21 Rev Time 0.75
Received By eschneid Date 2018-12-14 Time 09:13 Sent To  
Notes
2018-12-19 15:16:58FAILED
  
 PROVIDE WRITTEN RESPONSES TO THE COMMENTS. PLEASE NOTE
 THAT THE SUBMITTAL OF THE REQUIRED ITEMS MAY RESULT IN
 ADDITIONAL COMMENTS
  
 1) THE PARKING LOT FOR THIS BUILDING IS REQUIRED TO BE
 RESTORED PRIOR TO THE ISSUANCE OF THE FIRST CERTIFICATE
 OF OCCUPANCY FOR THE BUILDING. THE RESTORED PARKING LOT
 REQUIRES THE SUBMITTAL AND APPROVAL OF A PERMIT FOR THE
 WORK. THE PREVIOUS PERMIT FOR PARKING LOT IMPROVEMENTS
 DID NOT MEET CODE REQUIREMENTS AND THUS WAS NOT ISSUED
 AND THEN WAS LATER REVOKED, MEANING THAT THERE IS NO
 ACTIVE PERMIT FOR THE RESTORED PARKING LOT. ZONING WILL
 NOT APPROVE THIS PERMIT UNTIL A PARKING LOT PERMIT,
 WITH PLANS, IS SUBMITTED TO THE CONSTRUCTION SERVICES
 DIVISION.
  
 2) THE RENOVATIONS TO 1600 NORTH DIXIE HIGHWAY REQUIRE
 THE INSTALLATION OF CODE COMPLIANT LANDSCAPE. LANDSCAPE
 PERMIT NO. 17071228 WAS SUBMITTED TO THE CONSTRUCTION
 SERVICES DIVISION, BUT IT IS NOT CODE COMPLIANT AND HAS
 NOT BEEN APPROVED. PLEASE NOTE THAT THE LANDSCAPE
 PERMIT AND THE PARKING LOT PERMIT WILL NOT BE APPROVED
 UNTIL THEY SHOW IDENTICAL CODE COMPLIANT CONDITIONS.
 THE LANDSCAPE WORK AS PART OF THE APPROVE LANDSCAPE
 PERMIT MUST BE COMPLETED PRIOR TO THE FIRST CERTIFICATE
 OF OCCUPANCY FOR THE BUILDING.
  
 3) THE PLANS SHOW A BAR INCLUDING LIQUOR RACKS. WHAT
 ALCOHOL LICENSE IS ANTICIPATED FOR THIS ESTABLISHMENT?
 IF YOU PLAN TO APPLY FOR A 4COP SFS, PROVIDE
 VERIFICATION THAT THERE IS 2,500 SQUARE FEET OF SERVICE
 AREA. PLEASE NOTE THAT BASED ON THE INFORMATION
 PROVIDED ON THE LIGHTING BUDGET TABLE, THE ENTIRE SPACE
 ONLY HAS 2,413 SQUARE FEET WHICH FALLS BELOW THE 2,500
 SQUARE FEET OF SERVICE AREA REQUIREMENT.
  
 4) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR:
  
 A. PARKING LOT
 B. LANDSCAPE
 C. IRRIGATION
 D. DUMPSTER ENCLOSURE
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
2018-12-14 09:31:15ROUTED TO ES