| 2018-11-21 14:33:12 | RESIDENTIAL (R3) SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1-CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS AND |
| | TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE |
| | WITH THE EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING |
| | BUILDING. |
| | NOTE: CLEARLY IDENTIFY IN FLOOR PLAN ALL ROOMS |
| | (SPECIALLY ALL THE BEDROOMS). |
| | |
| | RESPONSE: |
| | SKETCH SUBMITTED IS NOT CLEAR. IT DOESN'T SPECIFY TYPE |
| | AND SIZE OF EXISTING WINDOW. IT ONLY SPECIFIES THE |
| | PROPOSED WINDOWS. UNABLE TO VERIFY COMPLIANCE WITH THE |
| | BEDROOMS EGRESS REQUIREMENTS AS REQUIRED BY SEC. 702.5 |
| | FBC-EXISTING BUILDING. |
| | NOTE: NEED TO VERIFY MANUFACTURER'S LARGEST STANDARD |
| | SIZE WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR |
| | EXISTING ROUGH OPENING AND THAT WILL NOT REDUCE THE |
| | EGRESS SIZE OPENING OF EXISTING WINDOW AS REQUIRED BY |
| | SEC. 702.5. |
| | |
| | 702.5 EMERGENCY ESCAPE AND RESCUE OPENINGS. |
| | |
| | WHERE WINDOWS ARE REQUIRED TO PROVIDE EMERGENCY ESCAPE |
| | AND RESCUE OPENINGS IN GROUP R-2 AND R-3 OCCUPANCIES |
| | AND ONE- AND TWO-FAMILY DWELLINGS AND TOWNHOUSES |
| | REGULATED BY THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| | REPLACEMENT WINDOWS SHALL BE EXEMPT FROM THE |
| | REQUIREMENTS OF SECTIONS 1030.2, 1030.3 AND 1030.5 OF |
| | THE FLORIDA BUILDING CODE, BUILDING AND SECTIONS |
| | R310.21 AND R310.2.3 OF THE FLORIDA BUILDING CODE, |
| | RESIDENTIAL ACCORDINGLY, PROVIDED THE REPLACEMENT |
| | WINDOW IS THE MANUFACTURER'S LARGEST STANDARD SIZE |
| | WINDOW THAT WILL FIT WITHIN THE EXISTING FRAME OR |
| | EXISTING ROUGH OPENING. THE REPLACEMENT WINDOW SHALL BE |
| | PERMITTED TO BE OF THE SAME OPERATING STYLE AS THE |
| | EXISTING WINDOW OR A STYLE THAT PROVIDES FOR AN EQUAL |
| | OR GREATER WINDOW OPENING AREA THAN THE EXISTING |
| | WINDOW. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE (2 |
| | COPIES) THAT CORRESPOND TO SINGLE HUNG DRAWINGS NO |
| | 08-02545 SUBMITTED. NOTE: NEED PRODUCT APPROVAL FOR |
| | CURRENT 2017 CODE VERSION. |
| | FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED AT ALL. |
| | |