| 2018-11-14 10:00:36 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110073 |
| | 11/14/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: REFER TO SECTIONS 809.1 & 809.2 FBC-17 |
| | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE |
| | 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | |
| | 2) M1: PROVIDE THE SUPPLY CFMS AT EACH RELOCATED |
| | DIFFUSER- SECTION 603.1 FBC M. |
| | |
| | 3) M1: CLARIFY THE SEQUENCE OF OPERATION FOR THE |
| | MOTORIZED DAMPERS ON THE RETURN DUCTS. PLEASE NOTE THAT |
| | AUTOMATIC DAMPERS ARE REQUIRED FOR O/A INTAKE DUCTS PER |
| | SECTION C403.2.4.3 FMC EC, HOWEVER THIS REQUIREMENT |
| | DOES NOT APPLY TO RETURN DUCTS. |
| | |
| | 4) M1: THE 10" RETURN DUCT FROM THE CREW ROOM APPEARS |
| | TO BE TRANSFERRING AIR INTO THE CORRIDOR AS A MEANS OF |
| | RETUN TO THE AIR HANDLER, WHICH IS PROHIBITED PER |
| | SECTION 601.2 FBC M. PLEASE CONNECT THE DUCT DIRECTLY |
| | TO THE AIR HANDLER. |
| | |
| | 5) M1: PLEASE BE ADVISED THAT DUCT SMOKE DECTORS ARE |
| | REQUIRED IN THE SUPPLY AIR SYSTEMS OF AIR HANDLER |
| | SUPPLY SYSTEMS WITH CAPACITIES GREATER THAN 2000 CFMS- |
| | SECTION 606.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |