| 2018-11-14 15:25:42 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110072 |
| | 11/14/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A COMPLETE SET OF BURGER KING BUILDING PLANS HAVE |
| | BEEN SUBMITTED FOR REVIEW OF A KITCHEN HOOD EXHAUST |
| | PROJECT. PLEASE REMOVE ALL PLAN SHEETS NOT ASSOCIATED |
| | WITH THE HOOD INCLUDING THE ARCHITECTURAL, PLUMBING, |
| | AND ELECTRICAL SHEETS AND RESUBMIT THE H-1, H-2, H-3 |
| | SHEETS THAT ARE INCLUDED WITH THE SETS, ALONG WITH THE |
| | K-1, K-2, AND K-3 SHEETS THAT WERE NOT INCLUDED IN THE |
| | SETS, BUT ARE LISTED IN THE INDEX ON THE COVER SHEET |
| | CS- SECTIONS 107.1 & 107.2.1 WPB |
| | |
| | 2) PROVIDE A DUPLICATE SET OF FRANKECANOPY HOOD SHOP |
| | DRAWINGS (ONLY ONE SET WAS SUBMITTED). EACH SET SHALL |
| | BEAR THE APPROVAL STAMP OF THE ENGINEER OF RECORD- |
| | SHANER HAMILITON P.E ( SEE SHEETS H-1, H-2, AND H-3). |
| | |
| | 3) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| | SUPPRESSION SYSTEM, AND THE NEW BROILER- SECTIONS 107.1 |
| | & 107.2.1.3 WPB. |
| | |
| | 4) THE $10,000.00 VALUE LISTED ON THE APPLICATION IS |
| | LOW. PERMIT VALUE IS BASED ON LABOR, MATERIALS, AND |
| | EQUIPMENT REGARDLESS OF WHO PURCHASES THE EQUIPMENT AND |
| | MATERIALS. PLEASE PROVIDE SIGNED CONTRACTS AND INVOICES |
| | TO VERIFY TOTAL COSTS- SECTION 109.3 WPB. |
| | |
| | 5) SHEET H-2: INDICATE THE TERMINATION HEIGHT OF THE |
| | EXHAUST FAN OUTLET ABOVE THE FINISHED ROOF- SEE SECTION |
| | 506.3.13.1 FBC M. |
| | |
| | 6) H-2: CLARIFY WHICH GREASE DUCT WRAP WILL BE |
| | INSTALLED, AND SUBMIT SPECS FOR THE CORRECT ONE. THE |
| | NOTES ON THE PLAN CALL OUT 3M AND THE LEGEND CALLS OUT |
| | FIREMASTER- TWO DIFFERENT BRANDS- SECTION 506.3.11.2 |
| | FBC M. |
| | |
| | 7) H-2: PROVIDE AN EXHAUST HOOD SCHEDULE ON THE PLAN |
| | THAT LISTS THE MAKE AND MODEL, MAX COOKING TEMP, TOTAL |
| | EXHAUST CFMS, TOTAL SUPPLY CFMS, AND HOOD DIMENSIONS- |
| | 107.2.1 WPB. |
| | |
| | 8) H-2: INDICATE THE TYPE AND SIZE OF GREASE EXHAUST |
| | DUCT- THE PLAN INDICATES "BY OTHERS" WHICH IS |
| | UNACCEPTABLE FOR PERMITTING. REMOVE THE NOTE AND REFER |
| | TO SECTION 506.3.1.1 FBC M FOR DUCT MATERIAL |
| | REQUIREMENTS. |
| | |
| | 9) SHOW HOW MAKE UP AIR IS BEING PROVIDED FOR THE |
| | EXHAUST AND PROVIDE AN AIR BALANCE SCHEDULE PER SECTION |
| | 508.1.2 FBC M. |
| | |
| | 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR |
| | TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL |
| | NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE |
| | ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO |
| | NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 11) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE |
| | ROOFTOP CURB AND FAN- SECTION 301.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |