Plan Review Details - Permit 18110072
Plan Review Stops For Permit 18110072
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-12-19 Cont ID  
Sent By scaldero Date 2018-12-19 Time 11:22 Rev Time 0.00
Received By scaldero Date 2018-12-19 Time 11:22 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-11-28 Cont ID  
Sent By scaldero Date 2018-11-28 Time 10:57 Rev Time 0.00
Received By scaldero Date 2018-11-28 Time 10:53 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By scaldero Date 2018-11-20 Time 10:25 Rev Time 0.00
Received By scaldero Date 2018-11-20 Time 10:24 Sent To I
Notes
2018-11-20 10:25:15PERMIT # 18110072
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PLEASE REVIEW AND RESPOND TO MECHANICAL REVIEW
 COMMENTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-12-19 Cont ID  
Sent By cpuell Date 2018-12-19 Time 13:13 Rev Time 0.00
Received By cpuell Date 2018-12-11 Time 14:22 Sent To  
Notes
2018-12-12 14:22:19GIVEN TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2018-12-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-06 Time 15:01 Sent To  
Notes
2018-12-07 15:01:56RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-11-30 Time   Rev Time 0.00
Received By cpuell Date 2018-11-21 Time 16:51 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-20 Cont ID  
Sent By cpuell Date 2018-11-20 Time 11:16 Rev Time 0.00
Received By cpuell Date 2018-11-08 Time 15:06 Sent To  
Notes
2018-11-13 10:23:2511/13 APPLICANT WAS ADVISED THAT SIGNED & SEALED PLANS
 ARE REQUIRED; BROUGHT IN NEW PLANS, ROUTED BACK TO
 HAROLD MOSER'S DESK
  
  
2018-11-09 15:06:19RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By hmoser Date 2018-11-07 Time 10:37 Rev Time 0.00
Received By hmoser Date 2018-11-02 Time 12:44 Sent To  
Notes
2018-11-06 12:44:36ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-12-12 Cont ID  
Sent By ccole Date 2018-12-12 Time 17:01 Rev Time 0.00
Received By ccole Date 2018-12-12 Time 16:25 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-12-10 Cont ID  
Sent By ccole Date 2018-12-10 Time 08:48 Rev Time 0.00
Received By ccole Date 2018-12-10 Time 07:45 Sent To I
Notes
2018-12-10 08:55:063RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18110072
 12/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ONE SET OF UPDATED, CORRECTED PLANS WAS SUBMITTED
 FOR REVIEW. TWO COMPLETE SETS ARE REQUIRED PER SECTION
 107.1 WPB.
  
 MISSING FROM THE SECOND SET ARE UPDATED SHEETS CS,
 A1.0, H-1, & H-2.2. PLEASE PROVIDE THE SHEETS.
  
 2) THE $10,000 JOB VALUE LISTED ON THE PERMIT
 APPLICATION APPEARS LOW FOR THE SCOPE OF THE PROJECT.
 PLEASE PROVIDE THE ACTUAL COST OF THE PROJECT BASED ON
 LABOR, MATERIALS, AND EQUIPMENT- SECTION 109.3 WPB,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-11-30 Cont ID  
Sent By ccole Date 2018-11-30 Time 15:42 Rev Time 0.00
Received By ccole Date 2018-11-30 Time 15:42 Sent To  
Notes
2018-11-30 15:44:592ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18110072
 11/30/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME COMMENTS FROM THE 1ST REVIEW HAVE NOT COMPLETELY
 ADDRESSED- SEE BELOW.
  
 9) SHOW HOW MAKE UP AIR IS BEING PROVIDED FOR THE
 EXHAUST AND PROVIDE AN AIR BALANCE SCHEDULE PER SECTION
 508.1.2 FBC M. ( THE ENGINEER IS STATING IN THE COMMENT
 RESPONSE NARRATIVE THAT MAKE UP AIR IS PROVIDED BY THE
 FOOD COURT, HOWEVER THE DRAWINGS IINDICATE THAT THE
 HOOD IS IN THE BACK OF HOUSE AREA AND NOT IN A LOCATION
 OPEN TO THE FOOD COURT. ALSO THE REQUESTED AIR BALANCE
 CALCULATION WAS NOT PROVIDED)
  
 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE
 ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO
 NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. (COMPLIANCE
 WILL DEPEND ON HOW MAKEUP AIR WILL BE PROVIDED PER
 COMMENT #9 ABOVE).
  
 11) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 ROOFTOP CURB AND FAN- SECTION 301.15 FBC M. ( PLEASE
 PROVIDE COMPLETE ENGINEERING ON THE PLAN INCLUDING THE
 DESIGN CRITERIA, AND/OR A COMPLETE FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA FOR THE EXHAUST FAN THAT
 INCLUDES THE COVER SHEET THAT BEARING EITHER THE
 CURRENT PRODUCT APPROVAL OR NOA NUMBER.)
  
 1) NEW COMMENT- SHEET A1.0: THE RETURN AIR GRILLES MUST
 BE LOCATED A MINIMUM OF 10' FROM THE COOKING APPLIANCE
 UNDER THE HOOD
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-14 Cont ID  
Sent By ccole Date 2018-11-14 Time 15:13 Rev Time 0.00
Received By ccole Date 2018-11-14 Time 15:05 Sent To FIRE
Notes
2018-11-14 15:25:421ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110072
 11/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A COMPLETE SET OF BURGER KING BUILDING PLANS HAVE
 BEEN SUBMITTED FOR REVIEW OF A KITCHEN HOOD EXHAUST
 PROJECT. PLEASE REMOVE ALL PLAN SHEETS NOT ASSOCIATED
 WITH THE HOOD INCLUDING THE ARCHITECTURAL, PLUMBING,
 AND ELECTRICAL SHEETS AND RESUBMIT THE H-1, H-2, H-3
 SHEETS THAT ARE INCLUDED WITH THE SETS, ALONG WITH THE
 K-1, K-2, AND K-3 SHEETS THAT WERE NOT INCLUDED IN THE
 SETS, BUT ARE LISTED IN THE INDEX ON THE COVER SHEET
 CS- SECTIONS 107.1 & 107.2.1 WPB
  
 2) PROVIDE A DUPLICATE SET OF FRANKECANOPY HOOD SHOP
 DRAWINGS (ONLY ONE SET WAS SUBMITTED). EACH SET SHALL
 BEAR THE APPROVAL STAMP OF THE ENGINEER OF RECORD-
 SHANER HAMILITON P.E ( SEE SHEETS H-1, H-2, AND H-3).
  
 3) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 SUPPRESSION SYSTEM, AND THE NEW BROILER- SECTIONS 107.1
 & 107.2.1.3 WPB.
  
 4) THE $10,000.00 VALUE LISTED ON THE APPLICATION IS
 LOW. PERMIT VALUE IS BASED ON LABOR, MATERIALS, AND
 EQUIPMENT REGARDLESS OF WHO PURCHASES THE EQUIPMENT AND
 MATERIALS. PLEASE PROVIDE SIGNED CONTRACTS AND INVOICES
 TO VERIFY TOTAL COSTS- SECTION 109.3 WPB.
  
 5) SHEET H-2: INDICATE THE TERMINATION HEIGHT OF THE
 EXHAUST FAN OUTLET ABOVE THE FINISHED ROOF- SEE SECTION
 506.3.13.1 FBC M.
  
 6) H-2: CLARIFY WHICH GREASE DUCT WRAP WILL BE
 INSTALLED, AND SUBMIT SPECS FOR THE CORRECT ONE. THE
 NOTES ON THE PLAN CALL OUT 3M AND THE LEGEND CALLS OUT
 FIREMASTER- TWO DIFFERENT BRANDS- SECTION 506.3.11.2
 FBC M.
  
 7) H-2: PROVIDE AN EXHAUST HOOD SCHEDULE ON THE PLAN
 THAT LISTS THE MAKE AND MODEL, MAX COOKING TEMP, TOTAL
 EXHAUST CFMS, TOTAL SUPPLY CFMS, AND HOOD DIMENSIONS-
 107.2.1 WPB.
  
 8) H-2: INDICATE THE TYPE AND SIZE OF GREASE EXHAUST
 DUCT- THE PLAN INDICATES "BY OTHERS" WHICH IS
 UNACCEPTABLE FOR PERMITTING. REMOVE THE NOTE AND REFER
 TO SECTION 506.3.1.1 FBC M FOR DUCT MATERIAL
 REQUIREMENTS.
  
 9) SHOW HOW MAKE UP AIR IS BEING PROVIDED FOR THE
 EXHAUST AND PROVIDE AN AIR BALANCE SCHEDULE PER SECTION
 508.1.2 FBC M.
  
 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE
 ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO
 NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 11) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 ROOFTOP CURB AND FAN- SECTION 301.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By hmoser Date 2018-11-07 Time 10:37 Rev Time 0.00
Received By hmoser Date 2018-11-07 Time 09:57 Sent To I
Notes
2018-11-07 10:37:02PLAN DENIED
 NO PLAN SUBMITTED. PROVIDE TWO SETS OF PLANS
 PER SECTION 107 FBC 2017.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676