Plan Review Details - Permit 18110071
Plan Review Stops For Permit 18110071
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-12-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-14 Time 15:20 Sent To  
Notes
2018-11-15 15:20:41RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By hmoser Date 2018-11-07 Time 11:17 Rev Time 0.00
Received By hmoser Date 2018-11-02 Time 12:45 Sent To  
Notes
2018-11-06 12:45:56ROUTED TO MECHANICAL INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-03 Cont ID  
Sent By ccole Date 2018-12-03 Time 10:44 Rev Time 0.00
Received By ccole Date 2018-12-03 Time 10:44 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By hmoser Date 2018-11-07 Time 10:46 Rev Time 0.00
Received By hmoser Date 2018-11-07 Time 10:45 Sent To I
Notes
2018-11-07 11:16:40PLAN DENIED
 PROVIDE INFORMATION ON THE CONDENSER'S ARE THEY ON THE
 ROOF
 OR ON TOP OF THE COOLER. IF ON THE ROOF PROVIDE AN NOA
 ON THE
 STAND SHOWING TIE DOWN TO ROOF AND WIND LOADS. PROVIDE
 ENGINEERING FOR CONDENSER ANCHORING TO STAND. PER
 SECTION 301.15 FBC (M) 2017
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676