| 2018-11-14 17:16:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18110069 |
| | 11/14/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A COMPLETE SET OF MOE'S SOUTHWEST GRILL BUILDING |
| | PLANS HAVE BEEN SUBMITTED FOR REVIEW OF A KITCHEN |
| | EXHAUST HOODS PROJECT. PLEASE REMOVE ALL PLAN SHEETS |
| | NOT ASSOCIATED WITH THE HOODS INCLUDING THE |
| | ARCHITECTURAL, PLUMBING, AND ELECTRICAL SHEETS- |
| | SECTIONS 107.1 & 107.2.1 WPB |
| | |
| | 2) THE HOOD DRAWINGS M5.0, M5.1, M5.2, M5.3, M5.4, AND |
| | M5.5 HAVE BEEN STAMPED "FOR INFORMATION ONLY" AND DO |
| | NOT BEAR THE ORIGINAL SIGNATURE AND SEAL OF THE |
| | ENGINEER WHO PREPARED THEM- SECTION 61G15-23.002 FAC |
| | |
| | 3) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| | SUPPRESSION SYSTEM- SECTIONS 107.1 & 107.2.1.3 WPB. |
| | |
| | 4) THE $18,000.00 VALUE LISTED ON THE APPLICATION IS |
| | LOW. PERMIT VALUE IS BASED ON LABOR, MATERIALS, AND |
| | EQUIPMENT REGARDLESS OF WHO PURCHASES THE EQUIPMENT AND |
| | MATERIALS. PLEASE PROVIDE SIGNED CONTRACTS AND INVOICES |
| | TO VERIFY TOTAL COSTS- SECTION 109.3 WPB. |
| | |
| | 5) INDICATE THE TYPE AND SIZE OF GREASE EXHAUST DUCTS |
| | TO BE INSTALLED. NO INFORMATION HAS BEEN PROVIDED ON |
| | THE PLANS- SEE SECTION 506.3.1.1 FBC M FOR DUCT |
| | MATERIAL REQUIREMENTS. |
| | |
| | 6) VERIFY THE GREASE DUCTS WILL BE INSTALLED WITH A |
| | MINIMUM 18" CLEARANCE TO COMBUSTIBLES PER SECTION |
| | 506.3.6 FBC M. |
| | |
| | 7) VERIFY THE GREASE DUCTS SHALL BE IN COMPLIANCE WITH |
| | SECTION 506.3.11 FBC M: |
| | A COMMERCIAL KITCHEN GREASE DUCT SERVING A TYPE I HOOD |
| | THAT PENETRATES A CEILING, WALL, FLOOR OR ANY CONCEALED |
| | SPACE SHALL BE ENCLOSED FROM THE POINT OF PENETRATION |
| | TO THE OUTLET TERMINAL. IF THE GREASE DUCT IS TO BE |
| | FIRE-WRAPPED TO MEET COMPLIANCE, PLEASE REVIEW SECTION |
| | 506.3.11.2 FBC M, AND A) INDICATE THE DUCT WRAPPING ON |
| | THE PLAN. B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 8) SHEET M1.1: VERIFY THE ROOFTOP FANS WILL BE |
| | INSTALLED A MINIMUM 10' FROM THE ROOF EDGES OR PROVIDE |
| | A GUARD OR PARAPET AT A MINIMUM OF 42" ABOVE THE ROOF |
| | SURFACE- SECTION 304.11 FBC M. |
| | |
| | 9) M1.1: INDICATE THE TYPE AND SIZE OF MAKEUP AIR DUCT |
| | TO BE INSTALLED. NO INFORMATION HAS BEEN PROVIDED ON |
| | THE PLANS- SEE SECTION 506.3.1.2 FBC M FOR |
| | REQUIREMENTS. |
| | |
| | 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR |
| | TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL |
| | NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE |
| | ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO |
| | NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 11) M1.1: SEE NOTE #10 AND PROVIDE WIND LOAD |
| | ENGINEERING FOR TIE DOWN OF THE ROOFTOP CURBS AND FANS- |
| | SECTION 301.15 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |