Plan Review Details - Permit 18110069
Plan Review Stops For Permit 18110069
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-11-28 Cont ID  
Sent By scaldero Date 2018-11-28 Time 11:01 Rev Time 0.00
Received By scaldero Date 2018-11-28 Time 10:57 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-11-20 Cont ID  
Sent By scaldero Date 2018-11-20 Time 10:29 Rev Time 0.00
Received By scaldero Date 2018-11-20 Time 10:28 Sent To I
Notes
2018-11-20 10:29:19PERMIT # 18110069
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PLEASE REVIEW AND RESPOND TO MECHANICAL REVIEW
 COMMENTS,
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By pleduc Date 2018-11-06 Time   Rev Time 0.00
Received By pleduc Date 2018-11-06 Time 14:12 Sent To M
Notes
2018-11-06 14:18:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE TOO SMALL AND UNREADABLE.
  
 PLEASE ENLARGE TO AT LEAST 18 X 24 AND RESUBMITT.
  
  
  
 2) THE SUBMITTED PLAN SHEETS APPEAR TO BE GENERAL
 INFORMATION AND NOT SITE SPECIFIC.
  
 PLEASE REVIEW AND SUBMIT PLAN SHEETS WITH FLOOR,
 CEILING AND ROOF LAYOUTS THAT REFLECT THE ACTUAL SPACE
 AND AREA OF THE INSTALL, INCLUDING ROOF TOP DETAILS
 WITH ALL DIMENSIONS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-11-30 Time   Rev Time 0.00
Received By cpuell Date 2018-11-21 Time 16:46 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-20 Cont ID  
Sent By cpuell Date 2018-11-20 Time 11:16 Rev Time 0.00
Received By cpuell Date 2018-11-14 Time 15:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By hmoser Date 2018-11-07 Time 11:32 Rev Time 0.00
Received By hmoser Date 2018-11-02 Time 12:46 Sent To  
Notes
2018-11-06 12:46:31ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-30 Cont ID  
Sent By ccole Date 2018-11-30 Time 14:37 Rev Time 0.00
Received By ccole Date 2018-11-30 Time 11:58 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-11-14 Cont ID  
Sent By ccole Date 2018-11-14 Time 17:15 Rev Time 0.00
Received By ccole Date 2018-11-14 Time 15:48 Sent To FIRE
Notes
2018-11-14 17:16:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18110069
 11/14/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A COMPLETE SET OF MOE'S SOUTHWEST GRILL BUILDING
 PLANS HAVE BEEN SUBMITTED FOR REVIEW OF A KITCHEN
 EXHAUST HOODS PROJECT. PLEASE REMOVE ALL PLAN SHEETS
 NOT ASSOCIATED WITH THE HOODS INCLUDING THE
 ARCHITECTURAL, PLUMBING, AND ELECTRICAL SHEETS-
 SECTIONS 107.1 & 107.2.1 WPB
  
 2) THE HOOD DRAWINGS M5.0, M5.1, M5.2, M5.3, M5.4, AND
 M5.5 HAVE BEEN STAMPED "FOR INFORMATION ONLY" AND DO
 NOT BEAR THE ORIGINAL SIGNATURE AND SEAL OF THE
 ENGINEER WHO PREPARED THEM- SECTION 61G15-23.002 FAC
  
 3) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 SUPPRESSION SYSTEM- SECTIONS 107.1 & 107.2.1.3 WPB.
  
 4) THE $18,000.00 VALUE LISTED ON THE APPLICATION IS
 LOW. PERMIT VALUE IS BASED ON LABOR, MATERIALS, AND
 EQUIPMENT REGARDLESS OF WHO PURCHASES THE EQUIPMENT AND
 MATERIALS. PLEASE PROVIDE SIGNED CONTRACTS AND INVOICES
 TO VERIFY TOTAL COSTS- SECTION 109.3 WPB.
  
 5) INDICATE THE TYPE AND SIZE OF GREASE EXHAUST DUCTS
 TO BE INSTALLED. NO INFORMATION HAS BEEN PROVIDED ON
 THE PLANS- SEE SECTION 506.3.1.1 FBC M FOR DUCT
 MATERIAL REQUIREMENTS.
  
 6) VERIFY THE GREASE DUCTS WILL BE INSTALLED WITH A
 MINIMUM 18" CLEARANCE TO COMBUSTIBLES PER SECTION
 506.3.6 FBC M.
  
 7) VERIFY THE GREASE DUCTS SHALL BE IN COMPLIANCE WITH
 SECTION 506.3.11 FBC M:
 A COMMERCIAL KITCHEN GREASE DUCT SERVING A TYPE I HOOD
 THAT PENETRATES A CEILING, WALL, FLOOR OR ANY CONCEALED
 SPACE SHALL BE ENCLOSED FROM THE POINT OF PENETRATION
 TO THE OUTLET TERMINAL. IF THE GREASE DUCT IS TO BE
 FIRE-WRAPPED TO MEET COMPLIANCE, PLEASE REVIEW SECTION
 506.3.11.2 FBC M, AND A) INDICATE THE DUCT WRAPPING ON
 THE PLAN. B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS.
  
 8) SHEET M1.1: VERIFY THE ROOFTOP FANS WILL BE
 INSTALLED A MINIMUM 10' FROM THE ROOF EDGES OR PROVIDE
 A GUARD OR PARAPET AT A MINIMUM OF 42" ABOVE THE ROOF
 SURFACE- SECTION 304.11 FBC M.
  
 9) M1.1: INDICATE THE TYPE AND SIZE OF MAKEUP AIR DUCT
 TO BE INSTALLED. NO INFORMATION HAS BEEN PROVIDED ON
 THE PLANS- SEE SECTION 506.3.1.2 FBC M FOR
 REQUIREMENTS.
  
 10) VERIFY COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE: THE TEMPERATURE DIFFERENTIAL BETWEEN
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES F (6 DEGREES C) EXCEPT WHERE THE
 ADDED HEATING AND COOLING LOADS OF THE MAKEUP AIR DO
 NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM.
  
 11) M1.1: SEE NOTE #10 AND PROVIDE WIND LOAD
 ENGINEERING FOR TIE DOWN OF THE ROOFTOP CURBS AND FANS-
 SECTION 301.15 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By hmoser Date 2018-11-07 Time 11:32 Rev Time 0.00
Received By hmoser Date 2018-11-07 Time 11:25 Sent To I
Notes
2018-11-07 11:32:13PLAN DENIED
 NO PLAN SUBMITTED. SUBMIT TWO SETS OF
 PLANS FOR THE HOOD AND GREASE DUCT AND
 FANS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676