| Notes |
| 2019-01-22 15:53:23 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.) | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR | | | THE PREFABRICATED GENERATOR PAD THAT IS SPECIFIC TO THE | | | MAKE AND MODEL OF GENERATOR THAT WILL BE INSTALLED. FBC | | | 1609.1 | | | | | | 2) SPECIFY THE TYPE, NUMBER AND LOCATION OF ANCHORS | | | THAT WILL BE USED TO SECURE THE GENERATOR TO THE | | | GENERATOR PAD TO RESIST WIND LOADS. FBC 107.2.1 | | | | | | 3) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION | | | MANUAL FOR THE GENERATOR. FBC 107.2.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-12-10 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-12-10 |
Time |
17:11 |
Sent To |
FIRE |
|
| Notes |
| 2018-12-10 17:22:44 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR | | | THE PREFABRICATED GENERATOR PAD THAT IS SPECIFIC TO THE | | | MAKE AND MODEL OF GENERATOR THAT WILL BE INSTALLED. FBC | | | 1609.1 | | | | | | 2) SPECIFY THE TYPE, NUMBER AND LOCATION OF ANCHORS | | | THAT WILL BE USED TO SECURE THE GENERATOR TO THE | | | GENERATOR PAD TO RESIST WIND LOADS. FBC 107.2.1 | | | | | | 3) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION | | | MANUAL FOR THE GENERATOR. FBC 107.2.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-01-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-01-24 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-01-24 |
Time |
08:50 |
Sent To |
G |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-11-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-11-21 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-11-21 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2018-11-21 08:54:28 | RAISED VALUE OF WORK TO $16,500 JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-09 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-09 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2018-11-09 16:37:32 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | | SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY | | | THE ELECTRICAL CONTRACTOR QUALIFIER. THIS INCLUDES | | | SHEETS PROVIDED FOR LOAD CALCULATION, ETC. PROVIDE | | | CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 | | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | | LOADS. THERE ARE TWO DIFFERENT LOAD CALCULATIONS | | | PROVIDED IN PACKAGE THAT HAVE DIFFERENT TOTALS. BOTH | | | LOAD CALCULATIONS USE DEMAND FACTORS THAT ARE ONLY | | | PERMITTED FOR RESIDENTIAL CALCULATIONS AND CANNOT BE | | | USED FOR THIS PROJECT. PROVIDE COMMERCIAL LOAD | | | CALCULATION. NEC 220 | | | 4. PROVIDE GENERATOR AND TRANSFER SWITCH SIZED TO | | | HANDLE THE LOAD CALCULATED IN COMMENT 3. NEC 701.4 | | | 5. PROVIDE ACCURATE RISER DIAGRAM. THE RISER CURRENTLY | | | SHOWS A 200 AMP METER/MAIN WITH TWO 100 AMP BREAKERS | | | AND ONE 50 AMP BREAKER. WHAT ARE THESE ITEMS FEEDING | | | AND HOW WILL A 200 AMP TRANSFER SWITCH BE TIED INTO | | | THESE CIRCUITS? WILL THE TRANSFER SWITCH BE THE MAIN? | | | IS IT SERVICE ENTRANCE RATED? NEED MORE DETAIL IN RISER | | | DIAGRAM. NEC 215.5, NEC 701.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2019-01-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-01-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-01-17 |
Time |
13:29 |
Sent To |
B |
|
| Notes |
| 2019-01-17 13:38:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | ALL PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED: | | | | | | PLEASE ADDRESS ALL FIRE COMMENTS NOT COMPLIED WITH. | | | | | | | | | 1) COMPLIED | | | | | | THIS INSTALLATION SHALL MEET THE REQUIREMENTS OF NFPA | | | 37. STANDARD FOR THE INSTALLATION AND USE OF STATIONARY | | | COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION | | | | | | THERE ARE NO INDICATION OR DIMENSIONS OF THE OPENINGS | | | ALONG THE WALL OF THE STRUCTURE. | | | | | | 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR | | | WEATHERPROOF | | | HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS | | | SHALL | | | BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS | | | AND AT | | | LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE | | | WALLS. A | | | MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER | | | OF THE | | | FOLLOWING CONDITIONS EXIST: | | | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5 | | | M (5 FT) | | | FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING | | | OF | | | AT LEAST 1 HOUR. | | | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NONCOMBUSTIBLE | | | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE | | | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS | | | OUTSIDE THE ENCLOSURE. | | | | | | | | | PLEASE INDICATED THE LOCATION AND DIMENSION FROM ALL | | | OPENINGS ALONG THE WALL OF THE STRUCTURE. | | | | | | | | | | | | | | | 2) NOT COMPLIED | | | | | | THERE IS NO INDICATION OR DIMESNION FROM THE PROPERTY | | | LINE OR STRUCTURE IN THE ADJACENT STRUCTURE AND THE | | | OPEINGS ALONG THAT STRUCTURE. | | | | | | PLEASE PROVIDE DETAILS OF THE ADJACENT PROPERTY. | | | | | | | | | | | | | | | 3) NOT COMPLIED | | | | | | THERE IS NO INDICATION OF ANY OVERHANG OR SOFFITT AREA | | | OVER THE GENERATOR OF THE COMMERCIAL STRUCTURE IT IS | | | NEXT TO. | | | | | | EXHAUST FUMES MAY ACCUMULATE AND ENTER THE STRUCTURE | | | FROM THE OVERHANG OR SOFFITT AREA, | | | | | | | | | 8.2.3 EXHAUST SYSTEM TERMINATION. | | | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE | | | STRUCTURE | | | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF | | | COMBUSTION | | | WILL DISCHARGE TO A SAFE LOCATION. | | | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE | | | DIRECTED TOWARD | | | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES | | | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR | | | COMBUSTIBLE | | | DUSTS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 4) NOT COMPLIED | | | | | | THERE IS NO INDICATION IF THE SYSTEM WILL BE SUPPLY | | | POWER TO THE EXISTING FIRE ALARM OR FIRE SPRINKLER | | | ALARM SYSTEMS. | | | | | | IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR | | | EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION | | | | | | WILL THIS SYSTEM SUPPLY POWER TO A FIRE ALARM SYSTEM? | | | | | | PLEASE PROVIDE DETAILS AS TO WHAT CLASS THIS SYSTEM IS | | | AND ENSURE COMPLIANCE. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | ADDITIONAL COMMENT: | | | | | | | | | 7) THERE IS NO ADDRESS ATTACHED TO THE SUBMITTED | | | SURVEY. | | | | | | PLEASE PROVIDE THE CORRECT ADDRESS TO THE SUBMITTED | | | SURVEY AND ENSURE ONE FOR COPY EACH SET. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-12-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-12-11 |
Time |
11:43 |
Sent To |
I |
|
| Notes |
| 2018-12-11 11:55:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THIS INSTALLATION SHALL ME THE REQUIREMENTS OF NFPA | | | 37. STANDARD FOR THE INSTALLATION AND USE OF STATIONARY | | | COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION | | | | | | THERE ARE NO INDICATION OR DIMENSIONS OF THE OPENINGS | | | ALONG THE WALL OF THE STRUCTURE. | | | | | | 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR | | | WEATHERPROOF | | | HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS | | | SHALL | | | BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS | | | AND AT | | | LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE | | | WALLS. A | | | MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER | | | OF THE | | | FOLLOWING CONDITIONS EXIST: | | | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5 | | | M (5 FT) | | | FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING | | | OF | | | AT LEAST 1 HOUR. | | | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NONCOMBUSTIBLE | | | MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE | | | WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS | | | OUTSIDE THE ENCLOSURE. | | | | | | | | | PLEASE INDICATED THE LOCATION AND DIMENSION FROM ALL | | | OPENINGS ALONG THE WALL OF THE STRUCTURE. | | | | | | | | | | | | | | | 2) THERE IS NO INDICATION OR DIMESNION FROM THE | | | PROPERTY LINE OR STRUCTURE IN THE ADJACENT STRUCTURE | | | AND THE OPEINGS ALONG THAT STRUCTURE. | | | | | | PLEASE PROVIDE DETAILS OF THE ADJACENT PROPERTY. | | | | | | | | | | | | | | | 3) THERE IS NO INDICATION OF ANY OVERHANG OR SOFFITT | | | AREA OVER THE GENERATOR OF THE COMMERCIAL STRUCTURE IT | | | IS NEXT TO. | | | | | | EXHAUST FUMES MAY ACCUMULATE AND ENTER THE STRUCTURE | | | FROM THE OVERHANG OR SOFFITT AREA, | | | | | | | | | 8.2.3 EXHAUST SYSTEM TERMINATION. | | | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE | | | STRUCTURE | | | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF | | | COMBUSTION | | | WILL DISCHARGE TO A SAFE LOCATION. | | | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE | | | DIRECTED TOWARD | | | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES | | | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR | | | COMBUSTIBLE | | | DUSTS. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 4) THERE IS NO INDICATION IF THE SYSTEM WILL BE SUPPLY | | | POWER TO THE EXISTING FIRE ALARM OR FIRE SPRINKLER | | | ALARM SYSTEMS. | | | | | | IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR | | | EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION | | | | | | PLEASE PROVIDE DETAILS AS TO WHAT CLASS THIS SYSTEM IS | | | AND ENSURE COMPLIANCE. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2019-01-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-01-25 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-01-25 |
Time |
06:25 |
Sent To |
I |
|
| Notes |
| 2019-01-25 10:27:02 | 1) PLANS DRAWN IN PENCIL ARE UNACCEPTABLE. WPB AMEND. | | | TO FBC SEC. 107.2.1. THERE ARE STILL PLANS IN THE | | | PACKAGE THAT ARE DONE IN PENCIL. REMOVE THESE PLANS | | | FROM THE SUBMITTAL PACKAGE.2ND REQUEST. | | | 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE | | | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 | | | FBC-R SEC. G2413.4.1, G2413.4.2.2ND REQUEST. | | | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, AND | | | ALL PIPE SIZES. WPB AMENDMENTS TO FBC SEC.107.2.1. 2ND | | | REQUEST. | | | 4.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21).2ND REQUEST. | | | 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND / | | | OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1, | | | 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2. | | | 2ND REQUEST. | | | 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | | 2ND REQUEST. | | | 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | | SEC.G2408.1. 2ND REQUEST. | | | 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | | G2413.1, G2413.2, & G2413.3. 2ND REQUEST. | | | 9) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS DO NOT SHOW SHOW AN EXISTING GAS SYSTEM FOR | | | THIS ADDRESS. THE EXISTING SYSTEM MUST BE PERMITTED. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. 2ND | | | REQUEST. 2ND REQUEST. | | | 10) THE GENERATOR EXHAUST SHALL BE LOCATED IN | | | ACCORDANCE WITH THE INSTALLATION MANUAL IN RELATION TO | | | BUILDING OPENINGS INCLUDING SOFFITT VENTS. SHOW THE | | | DISTANCE ON THE PLANS. 2017 FBC-FUEL GAS SEC. 616.1. | | | 2ND REQUEST. | | | 11) ONE COPY OF A SURVEY THAT HAS BEEN SUBMITTED SHOWS | | | THE GENERATOR UP NEAR THE HOUSE NEXT TO THE A/C UNIT | | | AND ANOTHER SURVEY SHOWS THE GENERATOR IN A DIFFERENT | | | LOCATION BUT DOES NOT SHOW THE DISTANCE FROM THE | | | EXTERIOR WALL OF THE STRUCTURE. CLARIFY. WPB AMEND. TO | | | FBC SEC. 107.2.1. . | | | 12) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA | | | 37. THE GENERATOR SPECS DO NOT INDICATE COMPLIANCE. | | | | | | NOTE: ONLY ONE COMMENT FROM THE PREVIOUS REVIEW HAS | | | BEEN ADDRESSED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-11-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-11-27 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-11-27 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2018-11-27 09:34:57 | 1) PLANS DRAWN IN PENCIL ARE UNACCEPTABLE. WPB AMEND. | | | TO FBC SEC. 107.2.1. | | | 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE | | | PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 | | | FBC-R SEC. G2413.4.1, G2413.4.2. | | | 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, AND | | | ALL PIPE SIZES. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | 4.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL | | | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | | G2413.4 (1 ) THROUGH G2413.4 (21). | | | 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | | METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND / | | | OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1, | | | 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2. | | | 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | | 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, | | | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND | | | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES | | | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS | | | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT | | | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. | | | SEC.G2408.1. | | | 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | | G2413.1, G2413.2, & G2413.3. | | | 9) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | | RECORDS DO NOT SHOW SHOW AN EXISTING GAS SYSTEM FOR | | | THIS ADDRESS. THE EXISTING SYSTEM MUST BE PERMITTED. | | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. | | | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR | | | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. | | | 10) THE GENERATOR EXHAUST SHALL BE LOCATED IN | | | ACCORDANCE WITH THE INSTALLATION MANUAL IN RELATION TO | | | BUILDING OPENINGS INCLUDING SOFFITT VENTS. SHOW THE | | | DISTANCE ON THE PLANS. 2017 FBC-FUEL GAS SEC. 616.1. | | | 11) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL | | | 2200. 2017 FBC-FUEL GAS SEC.616.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-01-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2019-01-25 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2019-01-08 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2019-01-11 09:54:19 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/11/19 EL | | 2019-01-08 15:47:45 | RESUB ROUTED TO ZONING INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2018-12-11 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2018-11-01 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2018-11-08 12:04:05 | ROUTED FROM ZONING TO LM 11/8/18 | | 2018-11-02 13:10:30 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2019-01-11 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2019-01-11 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2019-01-11 |
Time |
09:52 |
Sent To |
FIRE |
|
| Notes |
| 2019-01-11 09:53:47 | PREVIOUS COMMENTS NOT ADDRESSED: | | | | | | PLEASE PROVIDE A CERTIFIED BOUNDARY SURVEY. | | | | | | PLEASE SHOW SETBACK OF GENERATOR FROM PROPERTY LINE. | | | GENERATOR CANNOT PROJECT MORE THAN FOUR FEET INTO THE | | | REQUIRED REAR SETBACK OF 5'. | | | | | | GENERATOR MUST BE SCREEND WITH LANDSCAPE ON AT LEAST | | | THREE SIDE, MOST IMPORTANTLY FROM THE ROW. PLEASE | | | INDICATE LOCATION OF PROPOSED LANDSCAPING. | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | 561 822 1426 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-11-08 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2018-11-08 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2018-11-08 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2018-11-08 12:03:08 | PLEASE PROVIDE A CERTIFIED BOUNDARY SURVEY. | | | | | | PLEASE PROVIDE DIMENSIONS OF GENERATOR ON SURVEY AND | | | SHOW SETBACK OF GENERATOR FROM PROPERTY LINE. GENERATOR | | | CANNOT PROJECT MORE THAN FOUR FEET INTO THE REQUIRED | | | REAR SETBACK OF 5'. | | | | | | GENERATOR MUST BE SCREEND WITH LANDSCAPE ON AT LEAST | | | THREE SIDE, MOST IMPORTANTLY FROM THE ROW. | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | 561 822 1426 |
|
|
|