Plan Review Details - Permit 18110020
Plan Review Stops For Permit 18110020
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-22 Cont ID  
Sent By rmcdouga Date 2019-01-22 Time 15:51 Rev Time 0.00
Received By rmcdouga Date 2019-01-22 Time 15:51 Sent To E
Notes
2019-01-22 15:53:23PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.)
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR
 THE PREFABRICATED GENERATOR PAD THAT IS SPECIFIC TO THE
 MAKE AND MODEL OF GENERATOR THAT WILL BE INSTALLED. FBC
 1609.1
  
 2) SPECIFY THE TYPE, NUMBER AND LOCATION OF ANCHORS
 THAT WILL BE USED TO SECURE THE GENERATOR TO THE
 GENERATOR PAD TO RESIST WIND LOADS. FBC 107.2.1
  
 3) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION
 MANUAL FOR THE GENERATOR. FBC 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By rmcdouga Date 2018-12-10 Time 17:11 Rev Time 0.00
Received By rmcdouga Date 2018-12-10 Time 17:11 Sent To FIRE
Notes
2018-12-10 17:22:44PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF SIGNED AND SEALED ENGINEERING FOR
 THE PREFABRICATED GENERATOR PAD THAT IS SPECIFIC TO THE
 MAKE AND MODEL OF GENERATOR THAT WILL BE INSTALLED. FBC
 1609.1
  
 2) SPECIFY THE TYPE, NUMBER AND LOCATION OF ANCHORS
 THAT WILL BE USED TO SECURE THE GENERATOR TO THE
 GENERATOR PAD TO RESIST WIND LOADS. FBC 107.2.1
  
 3) SUBMIT TWO SETS OF THE MANUFACTURER'S INSTALLATION
 MANUAL FOR THE GENERATOR. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-24 Cont ID  
Sent By jleahy Date 2019-01-24 Time 08:51 Rev Time 0.00
Received By jleahy Date 2019-01-24 Time 08:50 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-21 Cont ID  
Sent By jleahy Date 2018-11-21 Time 08:53 Rev Time 0.00
Received By jleahy Date 2018-11-21 Time 08:53 Sent To  
Notes
2018-11-21 08:54:28RAISED VALUE OF WORK TO $16,500 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 16:37 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 16:37 Sent To  
Notes
2018-11-09 16:37:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. THIS INCLUDES
 SHEETS PROVIDED FOR LOAD CALCULATION, ETC. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THERE ARE TWO DIFFERENT LOAD CALCULATIONS
 PROVIDED IN PACKAGE THAT HAVE DIFFERENT TOTALS. BOTH
 LOAD CALCULATIONS USE DEMAND FACTORS THAT ARE ONLY
 PERMITTED FOR RESIDENTIAL CALCULATIONS AND CANNOT BE
 USED FOR THIS PROJECT. PROVIDE COMMERCIAL LOAD
 CALCULATION. NEC 220
 4. PROVIDE GENERATOR AND TRANSFER SWITCH SIZED TO
 HANDLE THE LOAD CALCULATED IN COMMENT 3. NEC 701.4
 5. PROVIDE ACCURATE RISER DIAGRAM. THE RISER CURRENTLY
 SHOWS A 200 AMP METER/MAIN WITH TWO 100 AMP BREAKERS
 AND ONE 50 AMP BREAKER. WHAT ARE THESE ITEMS FEEDING
 AND HOW WILL A 200 AMP TRANSFER SWITCH BE TIED INTO
 THESE CIRCUITS? WILL THE TRANSFER SWITCH BE THE MAIN?
 IS IT SERVICE ENTRANCE RATED? NEED MORE DETAIL IN RISER
 DIAGRAM. NEC 215.5, NEC 701.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-01-17 Cont ID  
Sent By pleduc Date 2019-01-17 Time   Rev Time 0.00
Received By pleduc Date 2019-01-17 Time 13:29 Sent To B
Notes
2019-01-17 13:38:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 ALL PREVIOUS FIRE COMMENTS WERE NOT ADDRESSED:
  
 PLEASE ADDRESS ALL FIRE COMMENTS NOT COMPLIED WITH.
  
  
 1) COMPLIED
  
 THIS INSTALLATION SHALL MEET THE REQUIREMENTS OF NFPA
 37. STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION
  
 THERE ARE NO INDICATION OR DIMENSIONS OF THE OPENINGS
 ALONG THE WALL OF THE STRUCTURE.
  
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
  
 PLEASE INDICATED THE LOCATION AND DIMENSION FROM ALL
 OPENINGS ALONG THE WALL OF THE STRUCTURE.
  
  
  
  
 2) NOT COMPLIED
  
 THERE IS NO INDICATION OR DIMESNION FROM THE PROPERTY
 LINE OR STRUCTURE IN THE ADJACENT STRUCTURE AND THE
 OPEINGS ALONG THAT STRUCTURE.
  
 PLEASE PROVIDE DETAILS OF THE ADJACENT PROPERTY.
  
  
  
  
 3) NOT COMPLIED
  
 THERE IS NO INDICATION OF ANY OVERHANG OR SOFFITT AREA
 OVER THE GENERATOR OF THE COMMERCIAL STRUCTURE IT IS
 NEXT TO.
  
 EXHAUST FUMES MAY ACCUMULATE AND ENTER THE STRUCTURE
 FROM THE OVERHANG OR SOFFITT AREA,
  
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) NOT COMPLIED
  
 THERE IS NO INDICATION IF THE SYSTEM WILL BE SUPPLY
 POWER TO THE EXISTING FIRE ALARM OR FIRE SPRINKLER
 ALARM SYSTEMS.
  
 IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION
  
 WILL THIS SYSTEM SUPPLY POWER TO A FIRE ALARM SYSTEM?
  
 PLEASE PROVIDE DETAILS AS TO WHAT CLASS THIS SYSTEM IS
 AND ENSURE COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 ADDITIONAL COMMENT:
  
  
 7) THERE IS NO ADDRESS ATTACHED TO THE SUBMITTED
 SURVEY.
  
 PLEASE PROVIDE THE CORRECT ADDRESS TO THE SUBMITTED
 SURVEY AND ENSURE ONE FOR COPY EACH SET.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By pleduc Date 2018-12-11 Time   Rev Time 0.00
Received By pleduc Date 2018-12-11 Time 11:43 Sent To I
Notes
2018-12-11 11:55:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THIS INSTALLATION SHALL ME THE REQUIREMENTS OF NFPA
 37. STANDARD FOR THE INSTALLATION AND USE OF STATIONARY
 COMBUSTION ENGINES AND GAS TURBINES, 2015 EDITION
  
 THERE ARE NO INDICATION OR DIMENSIONS OF THE OPENINGS
 ALONG THE WALL OF THE STRUCTURE.
  
 4.1.4 ENGINES LOCATED OUTDOORS. ENGINES, AND THEIR
 WEATHERPROOF
 HOUSINGS, IF PROVIDED, THAT ARE INSTALLED OUTDOORS
 SHALL
 BE LOCATED AT LEAST 1.5 M (5 FT) FROM OPENINGS IN WALLS
 AND AT
 LEAST 1.5 M (5 FT) FROM STRUCTURES HAVING COMBUSTIBLE
 WALLS. A
 MINIMUM SEPARATION SHALL NOT BE REQUIRED WHERE EITHER
 OF THE
 FOLLOWING CONDITIONS EXIST:
 (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 1.5
 M (5 FT)
 FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE RATING
 OF
 AT LEAST 1 HOUR.
 (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NONCOMBUSTIBLE
 MATERIALS AND IT HAS BEEN DEMONSTRATED THAT A FIRE
 WITHIN THE ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS
 OUTSIDE THE ENCLOSURE.
  
  
 PLEASE INDICATED THE LOCATION AND DIMENSION FROM ALL
 OPENINGS ALONG THE WALL OF THE STRUCTURE.
  
  
  
  
 2) THERE IS NO INDICATION OR DIMESNION FROM THE
 PROPERTY LINE OR STRUCTURE IN THE ADJACENT STRUCTURE
 AND THE OPEINGS ALONG THAT STRUCTURE.
  
 PLEASE PROVIDE DETAILS OF THE ADJACENT PROPERTY.
  
  
  
  
 3) THERE IS NO INDICATION OF ANY OVERHANG OR SOFFITT
 AREA OVER THE GENERATOR OF THE COMMERCIAL STRUCTURE IT
 IS NEXT TO.
  
 EXHAUST FUMES MAY ACCUMULATE AND ENTER THE STRUCTURE
 FROM THE OVERHANG OR SOFFITT AREA,
  
  
 8.2.3 EXHAUST SYSTEM TERMINATION.
 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE
 STRUCTURE
 AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF
 COMBUSTION
 WILL DISCHARGE TO A SAFE LOCATION.
 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE
 DIRECTED TOWARD
 COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES
 CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR
 COMBUSTIBLE
 DUSTS.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THERE IS NO INDICATION IF THE SYSTEM WILL BE SUPPLY
 POWER TO THE EXISTING FIRE ALARM OR FIRE SPRINKLER
 ALARM SYSTEMS.
  
 IF SO, IT SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS, 2013 EDITION
  
 PLEASE PROVIDE DETAILS AS TO WHAT CLASS THIS SYSTEM IS
 AND ENSURE COMPLIANCE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-01-25 Cont ID  
Sent By tklarge Date 2019-01-25 Time 10:35 Rev Time 0.00
Received By tklarge Date 2019-01-25 Time 06:25 Sent To I
Notes
2019-01-25 10:27:021) PLANS DRAWN IN PENCIL ARE UNACCEPTABLE. WPB AMEND.
 TO FBC SEC. 107.2.1. THERE ARE STILL PLANS IN THE
 PACKAGE THAT ARE DONE IN PENCIL. REMOVE THESE PLANS
 FROM THE SUBMITTAL PACKAGE.2ND REQUEST.
 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.2ND REQUEST.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, AND
 ALL PIPE SIZES. WPB AMENDMENTS TO FBC SEC.107.2.1. 2ND
 REQUEST.
 4.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).2ND REQUEST.
 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1,
 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
 2ND REQUEST.
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 2ND REQUEST.
 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. 2ND REQUEST.
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. 2ND REQUEST.
 9) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS DO NOT SHOW SHOW AN EXISTING GAS SYSTEM FOR
 THIS ADDRESS. THE EXISTING SYSTEM MUST BE PERMITTED.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. 2ND
 REQUEST. 2ND REQUEST.
 10) THE GENERATOR EXHAUST SHALL BE LOCATED IN
 ACCORDANCE WITH THE INSTALLATION MANUAL IN RELATION TO
 BUILDING OPENINGS INCLUDING SOFFITT VENTS. SHOW THE
 DISTANCE ON THE PLANS. 2017 FBC-FUEL GAS SEC. 616.1.
 2ND REQUEST.
 11) ONE COPY OF A SURVEY THAT HAS BEEN SUBMITTED SHOWS
 THE GENERATOR UP NEAR THE HOUSE NEXT TO THE A/C UNIT
 AND ANOTHER SURVEY SHOWS THE GENERATOR IN A DIFFERENT
 LOCATION BUT DOES NOT SHOW THE DISTANCE FROM THE
 EXTERIOR WALL OF THE STRUCTURE. CLARIFY. WPB AMEND. TO
 FBC SEC. 107.2.1. .
 12) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA
 37. THE GENERATOR SPECS DO NOT INDICATE COMPLIANCE.
  
 NOTE: ONLY ONE COMMENT FROM THE PREVIOUS REVIEW HAS
 BEEN ADDRESSED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By tklarge Date 2018-11-27 Time 09:58 Rev Time 0.00
Received By tklarge Date 2018-11-27 Time 09:12 Sent To  
Notes
2018-11-27 09:34:571) PLANS DRAWN IN PENCIL ARE UNACCEPTABLE. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, AND
 ALL PIPE SIZES. WPB AMENDMENTS TO FBC SEC.107.2.1.
 4.) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 5.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER) TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2017 FBC-FUEL GAS SEC.402.4.1,
 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 9) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS DO NOT SHOW SHOW AN EXISTING GAS SYSTEM FOR
 THIS ADDRESS. THE EXISTING SYSTEM MUST BE PERMITTED.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
 10) THE GENERATOR EXHAUST SHALL BE LOCATED IN
 ACCORDANCE WITH THE INSTALLATION MANUAL IN RELATION TO
 BUILDING OPENINGS INCLUDING SOFFITT VENTS. SHOW THE
 DISTANCE ON THE PLANS. 2017 FBC-FUEL GAS SEC. 616.1.
 11) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL
 2200. 2017 FBC-FUEL GAS SEC.616.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-25 Cont ID  
Sent By tklarge Date 2019-01-25 Time 10:35 Rev Time 0.00
Received By tklarge Date 2019-01-08 Time 15:47 Sent To  
Notes
2019-01-11 09:54:19ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/11/19 EL
2019-01-08 15:47:45RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By cpuell Date 2018-12-11 Time 14:12 Rev Time 0.00
Received By cpuell Date 2018-11-01 Time 13:10 Sent To  
Notes
2018-11-08 12:04:05ROUTED FROM ZONING TO LM 11/8/18
2018-11-02 13:10:30ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status F Date 2019-01-11 Cont ID  
Sent By elevesqu Date 2019-01-11 Time 09:53 Rev Time 0.00
Received By elevesqu Date 2019-01-11 Time 09:52 Sent To FIRE
Notes
2019-01-11 09:53:47PREVIOUS COMMENTS NOT ADDRESSED:
  
 PLEASE PROVIDE A CERTIFIED BOUNDARY SURVEY.
  
 PLEASE SHOW SETBACK OF GENERATOR FROM PROPERTY LINE.
 GENERATOR CANNOT PROJECT MORE THAN FOUR FEET INTO THE
 REQUIRED REAR SETBACK OF 5'.
  
 GENERATOR MUST BE SCREEND WITH LANDSCAPE ON AT LEAST
 THREE SIDE, MOST IMPORTANTLY FROM THE ROW. PLEASE
 INDICATE LOCATION OF PROPOSED LANDSCAPING.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-08 Cont ID  
Sent By elevesqu Date 2018-11-08 Time 12:03 Rev Time 0.00
Received By elevesqu Date 2018-11-08 Time 09:46 Sent To  
Notes
2018-11-08 12:03:08PLEASE PROVIDE A CERTIFIED BOUNDARY SURVEY.
  
 PLEASE PROVIDE DIMENSIONS OF GENERATOR ON SURVEY AND
 SHOW SETBACK OF GENERATOR FROM PROPERTY LINE. GENERATOR
 CANNOT PROJECT MORE THAN FOUR FEET INTO THE REQUIRED
 REAR SETBACK OF 5'.
  
 GENERATOR MUST BE SCREEND WITH LANDSCAPE ON AT LEAST
 THREE SIDE, MOST IMPORTANTLY FROM THE ROW.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426