Plan Review Details - Permit 18101448
Plan Review Stops For Permit 18101448
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 13:08 Rev Time 0.00
Received By shill Date 2018-12-08 Time 13:08 Sent To  
Notes
2018-12-08 13:16:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NO INFORMATION WAS PROVIDED - OCCUPANCY
 CLASSIFICATION FBC B CHAPTER 3, RESISTANCE TO WIND
 (BOTH ANCHORING AND THE PROPOSED STRUCTURE), FBC B
 1609. WHAT WILL BE STORED IN THE SHIPPING CONTAINER?
 SHIPPING CONTAINERS ARE DESIGNED TO BE LOADED WITH
 MATERIAL AND SHIPPED, WHICH DOES NOT APPEAR TO BE THE
 PROPOSED USE UNDER THIS PERMIT. IF THIS IS FOR STORAGE
 OF EQUIPMENT (SUCH AS LAWNMOWERS, OTHER MAINTENANCE
 EQUIPMENT), PROVIDE A PLAN WHICH CLEARLY SHOWS PROPOSED
 USE.
  
 PER FS471, ENGINEERING WILL BE REQUIRED TO DEMONSTRATE
 WIND RESISTANCE. IT IS NOT CLEAR IF A DESIGN
 PROFESSIONAL WILL BE REQUIRED FOR OTHER PLANS AS SCOPE
 HAS NOT BEEN DETERMINED.
  
 A SITE PLAN IS REQUIRED SHOWING DISTANCE TO PROPERTY
 LINE AND ASSUMED PROPERTY LINE, SEE FBC B CHAPTERS 6
 AND 7. BUILDING CONSTRUCTION TYPE, OPENINGS, FIRE
 RESISTANCE (IF APPLICABLE) INFORMATION NOT PROVIDED.
  
 CODE REQUIREMENTS CANNOT BE DETERMINED AT THIS TIME DUE
 TO INSUFFICIENT INFORMATION.
  
 2. THIS WAS SUBMITTED AS "489 EXEMPT". UNTIL IT IS
 DETERMINED THAT NO WORK WILL BE REQUIRED, THE PERMIT
 WILL NOT BE ISSUED AS 489 EXEMPT AND LICENSED
 CONTRACTORS WILL BE REQUIRED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.
  
 3. AN IMPACT FEE ASSESSMENT MAY BE REQUIRED (AND
 BUILDING PERMIT TYPE CHANGED FROM "ZONING" TO
 "BLD-COM").
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By pleduc Date 2018-12-10 Time   Rev Time 0.00
Received By pleduc Date 2018-12-10 Time 11:13 Sent To I
Notes
2018-12-10 11:20:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE INFORMATION PROVIDED IS VERY BASIC AND DOES NOT
 INCLUDE THE PURPOSE AND DURATION OF THE CONTAINERS.
  
 PLEASE PROVIDE A DETAILED NARRATIVE.
  
  
 2) THE INFORMATION PROVIDED DOES NOT INCLUDE DIMENSIONS
 OF THE CONTAINERS, SEPARATION FROM EACH OTHER AND ALL
 BUILDINGS AND PROPERTY LINES.
  
 THE SEPARATION MUST MEET THE REQUIREMENTS OF NFPA.
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 PLEASE PROVDIE DETAILED DIMENSIONS.
  
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-10 Cont ID  
Sent By cpuell Date 2018-12-10 Time 11:29 Rev Time 0.00
Received By cpuell Date 2018-10-31 Time 16:33 Sent To  
Notes
2018-12-08 13:16:2512/8 TO FIRE BOX
  
  
2018-11-01 16:33:13ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By mcruz Date 2018-11-27 Time 13:54 Rev Time 0.00
Received By mcruz Date 2018-11-20 Time 11:35 Sent To B
Notes
2018-11-27 13:54:40ZONING REVIEW FAILED, DUE TO THE FOLLOWING:
  
 1) PROVIDE TOTAL SQUARE FOOTAGE OF CONTAINERS.
 2) PROVIDE SETBACK DIMENSION FROM CONTAINERS TO ALL
 PROPERTY LINES.
 3) PROVIDE SEPARATION DIMENSION FROM CONTAINER TO
 BUILDING, SHOULD BE AT LEAST 6 FEET.
 4) CONTAINERS ARE SHOWN ON STIRE PLAN TO BE LOCATED
 WITHIN A PARKING SPACE. REQUIRED OFF-STREET PARKING
 SPACES SHALL NOT BE REPLACED BY ANY OTHER ON-SITE
 FACILITY UNLESS EQUAL PARKING FACILITIES ARE PROVIDED
 ELSEWHERE. OFF-STREET PARKING SPACES EXISTING ON THE
 EFFECTIVE DATE OF THE ORDINANCE FROM WHICH THIS ARTICLE
 IS DERIVED SHALL NOT BE REDUCED TO AN AMOUNT LESS THAN
 REQUIRED.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]