| 2018-11-13 10:41:04 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18101440 |
| | REVIEWED: NOVEMBER 13, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC 1505.1]PLEASE PROVIDE THE TYPE OF CONSTRUCTION |
| | AND THE FIRE CLASSIFICATION OF NEW ROOF SYSTEM. (UL |
| | LISTING?)IF CONSTRUCTION TYPE IS UNKNOWN A CLASS A OR B |
| | WILL SATISFY REQUIREMENTS. |
| | |
| | 2. [FBC 1503.4]ROOF DRAINAGE |
| | PROVIDE ROOF DRAIN CALCULATIONS AND DESIGN TO COMPLY |
| | WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| | HOW DOES DRAINAGE WORK FOR EXISTING ROOF? WHAT IS THE |
| | PROPOSED SLOPE? |
| | FORM 100 SAYS 3/12, BUT THIS IS A FLAT ROOF. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |