Plan Review Details - Permit 18101358
Plan Review Stops For Permit 18101358
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-08 Cont ID  
Sent By rmcdouga Date 2019-02-08 Time 18:51 Rev Time 0.00
Received By rmcdouga Date 2019-02-08 Time 18:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By rmcdouga Date 2018-12-13 Time 15:26 Rev Time 0.00
Received By rmcdouga Date 2018-12-13 Time 06:31 Sent To  
Notes
2018-12-13 17:52:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A COPY OF THE RECEIPT FROM THE PALM BEACH
 COUNTY HEALTH DEPARTMENT FOR THE APPLICATION FOR A
 PUBLIC SWIMMING POOL OPERATING PERMIT. FBC 105.1.4
 PUBLIC SWIMMING POOL ; THE LOCAL ENFORCING AGENCY MAY
 NOT ISSUE A BUILDING PERMIT TO CONSTRUCT, DEVELOP, OR
 MODIFY A PUBLIC SWIMMING POOL WITHOUT PROOF OF
 APPLICATION, WHETHER COMPLETE OR INCOMPLETE, FOR AN
 OPERATING PERMIT PURSUANT TO S. 514.031, FLORIDA
 STATUTES.
  
 2) THE CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 ENGINEERING BUSINESS IS REQUIRED TO BE IN THE TITLE
 BLOCK. FAC 61G15-23.002

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-11-28 Cont ID  
Sent By jleahy Date 2018-11-28 Time 18:11 Rev Time 0.00
Received By jleahy Date 2018-11-28 Time 18:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By tklarge Date 2019-01-08 Time 08:47 Rev Time 0.00
Received By tklarge Date 2019-01-08 Time 08:47 Sent To  
Notes
2019-01-08 08:48:01A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-14 Cont ID  
Sent By lmarchan Date 2019-02-14 Time 08:44 Rev Time 0.00
Received By lmarchan Date 2019-02-01 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-08 Cont ID  
Sent By lmarchan Date 2019-01-08 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2018-11-02 Time 11:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By tklarge Date 2019-02-14 Time 07:53 Rev Time 0.00
Received By tklarge Date 2019-02-14 Time 07:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-08 Cont ID  
Sent By tklarge Date 2019-01-08 Time 08:46 Rev Time 0.00
Received By tklarge Date 2019-01-02 Time 09:05 Sent To  
Notes
2019-01-02 09:07:29 
 1) SUBMIT A COPY OF THE RECEIPT FROM THE PALM BEACH
 COUNTY HEALTH DEPARTMENT FOR THE APPLICATION FOR A
 PUBLIC SWIMMING POOL OPERATING PERMIT. FBC 105.1.4
 PUBLIC SWIMMING POOL ; THE LOCAL ENFORCING AGENCY MAY
 NOT ISSUE A BUILDING PERMIT TO CONSTRUCT, DEVELOP, OR
 MODIFY A PUBLIC SWIMMING POOL WITHOUT PROOF OF
 APPLICATION, WHETHER COMPLETE OR INCOMPLETE, FOR AN
 OPERATING PERMIT PURSUANT TO S. 514.031, FLORIDA
 STATUTES.
 2) THE CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 ENGINEERING BUSINESS IS REQUIRED TO BE IN THE TITLE
 BLOCK. FAC 61G15-23.002.
 3) SHT. SP1.07 - POOL PIPING LEGEND - ITEM "G" NOTES
 THE OVERFLOW LINE TO THE STORM DRAINAGE SYSTEM.
 DISCHARGE TO THE STORM DRAINAGE SYSTEM IS NOT PERMITTED
 PER WPB CODE OF ORDINANCES ARTICLE V SECTION 90-203.
 CONTACT THE CITY OF WPB ENGINEERING DEPT.AT
 561-494-1040 FOR FURTHER DIRECTION.
 4) SHT. SP 1.07 - LINE "D" IS NOTED AS A SUCTION LINE
 FROM THE COLLECTOR TANK TO THE PUMP ANDD IS ALSO SHOWN
 AS A RETURN LINE FROM THE PUMP TO THE POOL. CLARIFY.
 5) THE SHOWER TOWER SHALL COMPLY WITH THE 2017 FLORIDA
 ACCESS. CODE SEC.309. THE MODEL SPECIFIED ON SHT. SP
 1.08, DETAILL #11 DOES NOT COMPLY.
 6) SHT. SP 1.08, DETAIL #8 CALLS OUT A 2 INCH MAIN
 DRAIN LINE CONNECTED TO A 4 INCH LINE BUT THE LINE IS
 ALSO SHOWN AS 6 INCH. CLARIFY.
 7) SHT. SP 1.09 - POOL PIPING LEGEND - ITEMS "I" &
 "K"ARE NOTED AS DISCHARGING TO THE SANITARY AND STORM
 SYSTEMS. THIS IS PROHIBITED PER THE CITY OF WPB CODE OF
 ORDINANCES ARTICLE III, SEC. 90-126 (B) (5).DISCHARGE
 TO THE STORM DRAINAGE SYSTEM IS NOT PERMITTED PER WPB
 CODE OF ORDINANCES ARTICLE V SECTION 90-203. CONTACT
 THE CITY OF WPB ENGINEERING DEPT.AT 561-494-1040 FOR
 FURTHER DIRECTION.
 8) SHT.SP 2.01 - THE RPZ SHALL BE INSTALLED AT LEAST 12
 INCHES ABOVE FINISH GRADE.
 9) SHT. SP 2.01 - THE COLLECTOR TANK OVERFLOW CANNOT
 DRAIN TO THE STORM DRAINAGE SYSTEM PER THE CITY OF WPB
 CODE OF ORDINANCES ARTICLE V SECTION 90-203. CONTACT
 THE CITY OF WPB ENGINEERING DEPT.AT 561-494-1040 FOR
 FURTHER DIRECTION.
 10) SHT. SP 3.01 - NOTE #19 REFERS TO BACKWASH TO THE
 TO THE SANITARY SYSTEM. THIS IS PROHIBITED PER THE CITY
 OF WPB CODE OF ORDINANCES ARTICLE III, SEC. 90-126 (B)
 (5).DISCHARGE TO THE STORM DRAINAGE SYSTEM IS NOT
 PERMITTED PER WPB CODE OF ORDINANCES ARTICLE V SECTION
 90-203. CONTACT THE CITY OF WPB ENGINEERING DEPT.AT
 561-494-1040 FOR FURTHER DIRECTION.
 11) SHT.SP 3.01 DETAIL #1 & DETAIL #2 - BACKWASH LINE
 CANNOT DRAIN TO SANITARY AND POOL AND SPA MAINTENANCE
 LINE CANNOT DRAIN TO THE STORM DRAINAGE SYSTEM PER THE
 CITY OF WPB CODE OF ORDINANCES ARTICLE III, SEC. 90-126
 (B) (5).DISCHARGE TO THE STORM DRAINAGE SYSTEM IS NOT
 PERMITTED PER WPB CODE OF ORDINANCES ARTICLE V SECTION
 90-203. CONTACT THE CITY OF WPB ENGINEERING DEPT.AT
 561-494-1040 FOR FURTHER DIRECTION.
 12) SHT. SP 1.08 - GUTTER DETAIL - THIS APPEARS TO BE
 AN "OPEN TYPE GUTTTER". THE MINIMUM WIDTH SHALL BE 12
 INCHES AND SHALL SLOPE 2 INCHES FROM LIP TO DRAIN. 2017
 FBC SEC. 454.1.6.5.3.1.1.
 13) THE POOL COLLECTOR TANK IS SHOWN AS A 435 GALLON
 CAPACITY TANK ON SHT. SP 1.09 AND ON SHT. SP 3.01 THE
 TANK IS LISTED AS 269 GALLONS IN THE POOL PUMP AND
 FILTER EQUIPMENT TABLE. CLARIFY.
 14) THE SPA COLLECTOR TANK IS SHOWN ON SHT. P 2.01 AS
 392 GALLONS BUT THERE IS NO CAPACITY SHOWN IN THE SPA
 PUMP & FILTER EQUIPMENT TABLE ON SHT. SP 3.0.1.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-14 Cont ID  
Sent By tklarge Date 2019-02-14 Time 07:58 Rev Time 0.00
Received By tklarge Date 2019-02-14 Time 07:57 Sent To  
Notes
2019-02-14 07:58:18SIGNATURES OK EXCEPT FOT LANDSCAPE SHT. L-7.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-27 Cont ID  
Sent By shill Date 2018-12-27 Time 15:51 Rev Time 0.00
Received By shill Date 2018-12-27 Time 15:51 Sent To  
Notes
2018-12-27 15:51:39DIGITAL SIGNATURES OK
 NEW SHEETS SUBMITTED NEXT REVIEW CYCLE REQUIRE REVIEW
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By aaponte Date 2018-11-20 Time 15:38 Rev Time 0.00
Received By aaponte Date 2018-11-20 Time 15:38 Sent To  
Notes
***NONE***