Plan Review Details - Permit 18101338
Plan Review Stops For Permit 18101338
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-12-05 Cont ID  
Sent By jleahy Date 2018-12-05 Time 10:22 Rev Time 0.00
Received By jleahy Date 2018-12-05 Time 09:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2018-12-31 Cont ID  
Sent By shill Date 2018-12-31 Time 13:41 Rev Time 0.00
Received By shill Date 2018-12-31 Time 13:41 Sent To  
Notes
2018-12-31 13:42:01PLANS & REVIEW UNDER 18101337

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-10-31 Cont ID  
Sent By scaldero Date 2018-10-31 Time 13:25 Rev Time 0.00
Received By scaldero Date 2018-10-31 Time 12:20 Sent To  
Notes
2018-10-31 13:25:47PERMITS # 18101337 & 18101338
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) IT IS UNCLEAR WHICH TENANT SPACE IS 1831 PBL BLVD.
 AND WHICH ONE IS 1841 PBL BLVD. PLEASE PROPERLY
 IDENTIFY THE TENANT ADDRESSES.
  
 2) THERE ARE NO ENGINEERED CONSTRUCTION DOCUMENTS
 PROVIDED FOR TENANT 2. PLEASE VERIFY AND CONFIRM THAT
 ALL REQUIRED DETAILS UNDER F.A.C. 61G15 ARE PROVIDED
 FOR BOTH THE FIRE ALARM AND FIRE SPRINKLER DOCUMENTS.
  
 ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 3) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND
 WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 4) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 5) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 6) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-17 Cont ID  
Sent By lmarchan Date 2018-12-17 Time 12:15 Rev Time 0.00
Received By lmarchan Date 2018-10-30 Time 16:14 Sent To  
Notes
2018-12-17 12:15:08PLANS UNDER 18101337

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-12-31 Cont ID  
Sent By shill Date 2018-12-31 Time 13:41 Rev Time 0.00
Received By shill Date 2018-12-31 Time 13:41 Sent To  
Notes
2018-12-31 13:41:31PLANS & REVIEW UNDER 18101337

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By ccole Date 2018-12-13 Time 09:44 Rev Time 0.00
Received By ccole Date 2018-12-13 Time 09:44 Sent To  
Notes
2018-12-13 09:44:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101337
 12/13/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC LOAD CALCULATIONS ARE INCORRECTLY LISTING
 MIAMI AS THE PROJECT LOCATION- PLEASE CORRECT.
  
 2) SHEET M200: THE OUTSIDE AIR CALCULATIONS TABLE IS
 INCORRECTLY INDICATING "CORRIDOR' AS THE VENTILATION
 ZONE FOR RTU-3. PLEASE CHANGE THE ZONE TO READ TENANT
 2.
  
 3) M200: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 RTU-S PER SECTION 307.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status N Date 2018-12-31 Cont ID  
Sent By shill Date 2018-12-31 Time 13:40 Rev Time 0.00
Received By shill Date 2018-12-31 Time 13:40 Sent To  
Notes
2018-12-31 13:41:05PLANS & REVIEW UNDER 18101337

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-26 Cont ID  
Sent By eschneid Date 2018-11-26 Time 14:24 Rev Time 0.50
Received By eschneid Date 2018-11-26 Time 14:24 Sent To  
Notes
2018-11-26 14:38:55FAILED
  
 1) PLEASE EXPLAIN WHY YOU HAVE TURNED IN TWO SEPARATE
 PERMITS (18101337 & 18101338) FOR ONE BUILDING SHELL,
 WITH PARTIAL INTERIOR BUILD OUTS, AS IF EACH TENANT
 SPACE IS A SEPARATE BUILDING. IF YOU ARE MOVING FORWARD
 WITH THIS SPLITTING OF PERMITS, YOU NEED TO CLEARLY
 MARK OUT THE PORTION OF THE BUILDING (TO INCLUDE ROOF
 TOP MECHANICAL, ELEVATIONS, STOREFRONT, ETC.) THAT IS
 NOT COVERED UNDER THIS SPECIFIC PERMIT.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. DUMPSTER ENCLOSURE.
 B. LANDSCAPE.
 C. PARKING LOT CHANGES.
 D. AWNINGS.
  
 3) PROVIDE VERIFICATION THAT THE PROPOSED ROOFTOP
 MECHANICAL EQUIPMENT IS SCREENED IN ACCORDANCE WITH THE
 PALM BEACH OUTLETS DESIGN GUIDELINES.
  