| 2018-12-18 09:51:54 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18101337 |
| | ADD: 1831 PALM BEACH LAKES BLVD. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??????? / KARI NEVILLE |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | |
| | 1ST REVIEW |
| | DATE: MON. DEC. |
| | ACTION: DENIED |
| | |
| | |
| | SHELL BUILDING COMMENTS: |
| | |
| | 1) THERE APPEARS TO BE CONFUSION AS TO WHAT THIS PERMIT |
| | APPLICATION AND PLANS ARE FOR. PLEASE NOTE THE |
| | APPLICATION INDICATES GROUND UP CONSTRUCTION OF TENANT |
| | BUILDING. THIS DESCRIPTION WOULD MAKE IT SOUND A SINGLE |
| | TENANT, WHEREAS THE LIFE SAFETY PLAN 003-LS01 INDICATES |
| | (2) TENANTS. PLEASE ALSO NOTE THE PLAN HEADER STATES |
| | MARKETPLACE AT THE OUTLETS BUILDING D SHELL. PLEASE |
| | NOTE ONE SET OF PLANS CAN BE SUBMITTED AND 3 PERMIT |
| | APPLICATIONS, 1 PERMIT APPLICATION FOR THE SHELL, AND 2 |
| | PERMIT APPLICATIONS FOR EACH OF THE PROPOSED TENANT |
| | BUILD OUTS. WE NEED THIS FOR PERMIT TRACKING. IF AN |
| | EARLY START SHELL/ FOUNDATION PERMIT IS REQUESTED, WE |
| | CAN ISSUE THE SHELL WITH THE TENANT FIT UPS FOLLOWING |
| | AFTER, EACH TENANT FIT UP THEN COULD BE ISSUED |
| | SEPARATELY. THIS IS HOW PHASE 1 AND PHASE 2 OF THE |
| | OUTLET MALL WAS ISSUED. 107.2.1.2. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) SHEET 004-A100 SITE PLAN. PLEASE NOTE THERE IS NO |
| | PROPERTY LINES OR ASSUMED PROPERTY LINES DESIGNATING |
| | WHERE AN ASSUMED PROPERTY LINE WOULD BE ASSUMED FOR |
| | COMPLIANCE WITH 2017 FBC-B TABLE 602 FIRE RESISTANCE |
| | RATING OF EXTERIOR WALLS BASED ON FIRE SEPARATION |
| | DISTANCE AND TABLE 705.8 MAXIMUM ALLOWABLE WINDOW |
| | OPENINGS VERSES FIRE SEPARATION DISTANCE AND DEGREE OF |
| | OPENING PROTECTION. |
| | |
| | 3) SHEET 004-A100 SITE PLAN. WITHOUT THE KNOWLEDGE OF |
| | AN ASSUMED PROPERTY LINE FOR PARKING SPACES COMPLIANCE |
| | WITH THE 2017 FBC-ACCESSIBILITY CODE TABLE 208.2. |
| | |
| | 4) THE PERMIT APPLICATION SUBMITTED 18101338 IS ALSO |
| | FOR THE SAME WORK WITH A DIFFERENT DOLLAR AMOUNT. |
| | PLEASE PROVIDE WHAT VALUE IS FOR THE SHELL BUILDING IS |
| | AND THE VALUE OF EACH TENANT SPACE SO THE BUILDINGS |
| | DOLLAR VALUE CAN BE DETERMINED, SHOW THE DOLLAR AMOUNT |
| | TO BE DEDUCTED FOR FIRE SPRINKLER AND FIRE ALARM |
| | PERMITS. 2017 WEST PALM BEACH ADMINISTRATIVE CODE |
| | 109.3* BUILDING PERMIT VALUATION. |
| | |
| | 5) SHEET 028-S000. GENERAL NOTES. FOUNDATIONS) NOTE # 1 |
| | INDICATES THE FOUNDATION DESIGN WAS BASED ON THE |
| | GEOTECHNICAL REPORT BY ARDAMAN & ASSOCIATES, INC. DATED |
| | JUNE 28, 2016. PLEASE SUBMIT EITHER DIGITAL REPORT WITH |
| | AN ELECTRONIC SIGNATURE OR 1 PAPER REPORT WITH AN |
| | ORIGINAL SIGNATURE, DATE AND SEAL. |
| | 61G15-23.002 ENGINEER SEAL SIGNATURE AND DATE SHALL BE |
| | AFFIXED, (PAPER). |
| | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING |
| | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 6A) SHEET 028-S000. GENERAL NOTES. A PORTION OF THE |
| | WIND DESIGN LOADS ARE GIVEN UNDER GN-DESIGN LOADS. WHAT |
| | IS MISSING IS THE MEAN ROOF HEIGHT SO THE COMPONENTS |
| | AND CLADDING VULT PRESSURES AT THIS TIME ARE ONLY |
| | ASSUMPTIONS, THEY CANNOT BE VERIFIED UNTIL THE MEAN |
| | ROOF HEIGHT IS GIVEN WITH MULTIPLIERS. ) A HEIGHT AND |
| | EXPOSURE ADJUSTMENT COEFFICIENT, * SHALL BE DETERMINED |
| | FROM TABLE 1609.7.2. ASCE 7-10. |
| | NOTE ON SHEET 042-S601 THE WIND DIAGRAM NOTE # 6 DOES |
| | GIVE THE MEAN ROOF HEIGHT OF 18 FEET AND THE ROOF ZONES |
| | 1,2 & 3VULT PRESSURES ARE GIVEN, THE VALUES ARE GIVEN |
| | FOR 10 SQ. FT. TRIBUTARY AREA, HAVE BEEN VERIFIED/ |
| | CORRECT. |
| | |
| | 6B) SHEET 028-S000. GENERAL NOTES. A PORTION OF THE |
| | WIND DESIGN LOADS ARE GIVEN UNDER GN-DESIGN LOADS. THE |
| | COMPONENTS AND CLADDING PRESSURES STATE THEY ARE GIVEN |
| | IN VULT SINCE THEY NEED TO BE MULTIPLIED BY 0.6 FOR THE |
| | SERVICE LOADS. PLEASE CONVERT SO THE PRESSURES CAN BE |
| | VERIFIED, ALL PRODUCT APPROVALS ARE IN VASD. 1609.3.1 |
| | WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 7) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS |
| | (G) EXTERIOR PRE-ENGINEERED A/C STANDS |
| | |
| | 7A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 7B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 7C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 7D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | 7E) 2017 FBC-ACCESSIBILITY CODE. THRESHOLDS ACCESS. |
| | CODE 404.2.5. THRESHOLDS, IF PROVIDED AT DOORWAYS, |
| | SHALL BE 1/2 INCH (13 MM) HIGH MAXIMUM. RAISED |
| | THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS SHALL |
| | COMPLY WITH 302 AND 303. |
| | |
| | 7F) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| | FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| | MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| | COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.3 STRUCTURAL DESIGN. |
| | 1408.4 WEATHER RESISTANCE. |
| | 1408.4.1 EIFS WITH DRAINAGE. |
| | 408.4.1.1 WATER-RESISTIVE BARRIER. |
| | 1408.5 INSTALLATION. EFIS MANUFACTURES INSTRUCTIONS. |
| | |
| | 7G) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 7H) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 8) THE STRUCTURAL SHEET 029-S001 INDICATES A STRUCTURAL |
| | STEEL BUILDING. ON THIS SHEET THERE ARE 35 NOTES |
| | DEALING WITH STEEL CONNECTIONS EITHER BOLTED OR WELDED |
| | CONNECTIONS. THE CITY OF WEST PALM BEACH WILL INSPECT |
| | ALL ASPECTS OF THE BUILDING STRUCTURE WITH THE |
| | EXCEPTION OF THE BOLTED AND WELDED CONNECTIONS. PLEASE |
| | HAVE A 3RD PARTY FLORIDA PROFESSIONAL ENGINEER DO THE |
| | INSPECTIONS ON ALL OF THE BOLTED AND WELDED CONNECTIONS |
| | AND HAVE THE SIGNED AND SEALED AFFIDAVIT ON THE JOBSITE |
| | AT THE TIME OF THE FRAMING INSPECTION. PLEASE ADD NOTE |
| | ON THIS SHEET REQUIRING A 3RD PARTY FLORIDA |
| | PROFESSIONAL ENGINEER TO COMPLETE THE INSPECTIONS FOR |
| | BOLTED AND WELDED CONNECTIONS. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | |
| | 9) SHEETS A320 THROUGH A328 ALL HAVE COMMON KEY NOTES |
| | ON EACH PAGE: |
| | |
| | 9A) NOTES 18, 19, 27, 29, AND 31 ON ALL THE ABOVE |
| | LISTED SHEETS REFER TO 5/8 INCH EXTERIOR PLYWOOD |
| | SHEATHING. ONLY NOTE 28 INDICATES THE EXTERIOR OF THE |
| | BUILDING IS TO HAVE 5/8 INCH FIRE RETARDANT TREATED |
| | PLYWOOD. PLEASE REVIEW THE 2017 FBC-B 603 COMBUSTIBLE |
| | MATERIAL IN TYPES I AND II CONSTRUCTION |
| | 603.1 ALLOWABLE MATERIALS. |
| | (1.) FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.2. NONBEARING EXTERIOR WALLS WHERE |
| | FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED. |
| | PLEASE UPDATE PLANS TO SHOW FIRE-RETARDANT TREATED |
| | PLYWOOD. |
| | |
| | 9B) NOTES 27, 29, & 31 ALL INDICATE A MORTAR BED AND |
| | LATH. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE |
| | OF WIRE LATH THAT IS TO BE INSTALLED ON THE EXTERIOR OF |
| | THE BUILDING. FBC-B TABLE 2507.2 ASTM C 847 |
| | TYPE OF LATH, DIAMOND MESH, FLAT RIB, 3/8 INCH RIB AND |
| | WEIGHT, LB. / YD2. |
| | |
| | 9C) NOTES 27, 29, & 31 ALL INDICATE A MORTAR BED AND |
| | LATH. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE TYPE |
| | OF WATER-RESISTIVE BARRIER AND COMPLIANCE WITH 2017 |
| | FBC-B NOTES 27, 29, & 31 ALL INDICATE A MORTAR BED AND |
| | LATH. PLEASE PROVIDE ADDITIONAL INFORMATION ON THE |
| | TYPE. EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT |
| | IS APPLIED OVER WOOD-BASED SHEATHING HAS A WATER |
| | RESISTANCE EQUAL TO OR GREATER THAN THAT OF A |
| | WATER-RESISTIVE BARRIER COMPLYING WITH ASTM E2556, TYPE |
| | II AND IS SEPARATED FROM THE STUCCO BY AN INTERVENING, |
| | SUBSTANTIALLY NONWATER-ABSORBING LAYER OR DRAINAGE |
| | SPACE. |
| | |
| | 10) SHEETS 009-A300, 024-A800 & 052-P211. ROOF |
| | DRAINAGE. (SHEET P211 STORM PLAN). |
| | |
| | 10A) PLEASE NOTE NONE OF THE STATED ABOVE SHEETS |
| | PROVIDE COMPLIANCE WITH THE 2017 FBC-B/ P CODES. PLEASE |
| | SHOW COMPLIANCE WITH: |
| | 1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO DRAIN |
| | OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF |
| | DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. THERE IS |
| | NO DETERMINATION FOR THE 100-YEAR HOURLY RAINFALL RATE |
| | INDICATED IN FIGURE 1106.1 OR ON OTHER RAINFALL RATES |
| | DETERMINED FROM APPROVED LOCAL WEATHER DATA. |
| | |
| | 10B) THERE IS NO SQUARE FOOT AREA OF ROOF PLUS ? OF THE |
| | HEIGHT OF THE PARAPET AND HOW MANY SQUARE FEET ARE TO |
| | BE APPLIED TO WHICH SCUPPER AND EMERGENCY OVERFLOW |
| | SCUPPER. 107.2.1.2. FBC-B 1503.4 ROOF DRAINAGE. UNLESS |
| | ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, DESIGN AND |
| | INSTALLATION OF ROOF DRAINAGE SYSTEMS SHALL COMPLY WITH |
| | SECTION 1503 AND THE FLORIDA BUILDING CODE, PLUMBING, |
| | CHAPTER 11. |
| | |
| | 10C) THE PLANS DO NOT PROVIDE THE SIZE OF THE SCUPPER |
| | NOR THE SECONDARY/ EMERGENCY OVERFLOW SCUPPERS. |
| | [P]1503.4 ROOF DRAINAGE. UNLESS ROOFS ARE SLOPED TO |
| | DRAIN OVER ROOF EDGES, DESIGN AND INSTALLATION OF ROOF |
| | DRAINAGE SYSTEMS SHALL COMPLY WITH SECTION 1503 AND THE |
| | FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| | |
| | 10D) THE PLANS DO NOT PROVIDE THE MINIMUM SIZE FOR THE |
| | EMERGENCY OVERFLOW SCUPPERS SHOW COMPLIANCE WITH: 2017 |
| | FBC-B 1503.4.2.1 OVERFLOW SCUPPERS. AN OVERFLOW SCUPPER |
| | SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, PLUMBING. |
| | |
| | 11) BEFORE THE SHELL BUILDING CAN HAVE THE PERMIT |
| | ISSUED, THE PLANS WILL NEED TO GO TO PALM BEACH COUNTY. |
| | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS? |
| | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 12) DIGITAL PLANS. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | PERMIT FOR TENANT BUILD OUT 1, |
| | 4,000 SQUARE FEET, OCCUPANCY CLASSIFICATION MERCANTILE. |
| | |
| | 1) SHEET 020-ENLARGED RESTROOM PLAN THE ENTRY DOORS |
| | INTO THE RESTROOMS NEITHER DOOR HAS A DIMENSION ON THE |
| | INTERIOR OF THE DOOR TO THE FINISH WALL, IT IS |
| | DIFFICULT TO KNOW THAT COMPLIANCE WITH THE 2017 |
| | ACCESSIBILITY CODE SECTION . 404.2.4 MANEUVERING |
| | CLEARANCES. DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| | DOORS AND GATES SHALL COMPLY WITH 404.2.4. MANEUVERING |
| | CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY |
| | AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. FIGURE |
| | 404.2.4.1 (A). |
| | 2) SHEET 020-ENLARGED RESTROOM PLAN RESTROOM |
| | ELEVATIONS. PLEASE REVIEW THE HEIGHT REQUIREMENTS FOR |
| | THE WATER CLOSET GRAB BARS. 2017FBC-ACCESSIBILITY CODE |
| | SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| | PLEASE NOTE THE TOILET GRAB BAR IN THE TYPICAL |
| | ACCESSIBLE DETAILS IS SHOWN CORRECTLY, DISCREPANCY IN |
| | THE PLANS. |
| | 3) SHEET 020-ENLARGED RESTROOM PLAN RESTROOM |
| | ELEVATIONS. PLEASE REVIEW ON THE MIRROR WHERE THE |
| | MIRROR IS MEASURED FROM AND COMPLIANCE. 603.3 MIRRORS. |
| | 2017 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES (1015 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. MIRRORS |
| | NOT LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| | INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| | SURFACE 35 INCHES (890 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. PLEASE NOTE THE MIRROR IN THE TYPICAL |
| | ACCESSIBLE DETAILS IS SHOWN CORRECTLY, DISCREPANCY IN |
| | THE PLANS. |
| | 4) THE SHEET 003-LS01 LIFE SAFETY PLAN SHOWS TWO MEANS |
| | OF EGRESS BUT THE PLAN DOES NOT INDICATE THAT THE GRADE |
| | IS LEVEL OR NO MORE THAN ? INCH LOWER THAN FINISH |
| | FLOOR. |
| | 2017 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION |
| | TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT |
| | LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY |
| | WITH 404. 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 |
| | MEANS OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF |
| | THE INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | 5) AS THIS PERMIT IS FOR A TENANT BUILD OUT OF A |
| | MERCANTILE TENANT THERE ARE NO PLANS SUBMITTED SHOWING |
| | COMPLIANCE FOR CHECKOUT COUNTERS AND ACCESSIBILITY. |
| | 5A) 902.1 .WORK SURFACES SHALL COMPLY WITH 902.2 AND |
| | 902.3. ADVISORY 902.1 GENERAL. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS. |
| | 5A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 5A))(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 5A)(3) . 2017 ACCESS. CODE 904.3.3 CHECK WRITING |
| | SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL |
| | COMPLY WITH 902.3. 902.3HEIGHT. |
| | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | 5A)(4) 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS |
| | AND SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR |
| | 904.4.2. THE ACCESSIBLE PORTION OF THE COUNTER TOP |
| | SHALL EXTEND THE SAME DEPTH AS THE SALES OR SERVICE |
| | COUNTER TOP. |
| | 6) DIGITAL REVIEWS. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | PERMIT FOR TENANT BUILDOUT 2 |
| | 2,000 SQUARE FEET/ BUSINESS OCCUPANCY |
| | |
| | 1A) PLEASE NOTE THE TENANT SPACE # 2 IS 2,000 SQ. FT. |
| | AND A PROPOSED BUSINESS OCCUPANCY. PLEASE NOTE THAT FOR |
| | BUSINESS, MERCANTILE AND ASSEMBLY OCCUPANCIES BOTH EXIT |
| | DOORS WILL REQUIRE 2 MEANS OF EGRESS BECAUSE THE COMMON |
| | PATH OF TRAVEL IS EXCEEDED, 75 FEET. TABLE 1006.2.1 OF |
| | THE 2017 FBC-B. PLEASE SHOW 2 ACCESSIBLE MEANS OF |
| | EGRESS. 2017 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS |
| | OF EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| | IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| | ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| | SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| | |
| | 1B) THE SHEET 003-LS01 LIFE SAFETY PLAN SHOWS TWO MEANS |
| | OF EGRESS BUT THE PLAN DOES NOT INDICATE THAT THE GRADE |
| | IS LEVEL OR NO MORE THAN ? INCH LOWER THAN FINISH |
| | FLOOR. |
| | 2017 FBC-ACCESSIBILITY CODE. 403.2 FLOOR OR GROUND |
| | SURFACE. FLOOR OR GROUND SURFACES SHALL COMPLY WITH |
| | 302. |
| | |
| | 2017 ACCESS. CODE. 303.2 VERTICAL. CHANGES IN LEVEL OF |
| | 1/4 INCH (6.4 MM) HIGH MAXIMUM SHALL BE PERMITTED TO BE |
| | VERTICAL. FIGURE 303.2 |
| | |
| | 2017 ACCESS. CODE. VERTICAL CHANGE IN LEVEL. 303.3 |
| | BEVELED. CHANGES IN LEVEL BETWEEN 1/4 INCH (6.4 MM) |
| | HIGH MINIMUM AND 1/2 INCH (13 MM) HIGH MAXIMUM SHALL BE |
| | BEVELED WITH A SLOPE NOT STEEPER THAN 1:2. |
| | |
| | 2A) PLEASE NOTE WITHIN THIS TENANT SPACE THERE IS NO |
| | PLUMBING FOR THE FUTURE RESTROOM OR RESTROOMS NOR FOR |
| | THE DRINKING FOUNTAIN PER 2017 FBC-B TABLE 2901.2.1. |
| | OCCUPANCY BUSINESS. |
| | |
| | 2B) NO TOILET FACILITIES OR FUTURE TOILET FACILITIES |
| | ARE SHOWN FOR THE BUSINESS OCCUPANCY LOCATION OF TOILET |
| | FACILITIES IN OPEN MALLS. 2017 FBC-B 2902.3.3 LOCATION |
| | OF TOILET FACILITIES IN MALLS. IN MALL BUILDINGS, THE |
| | REQUIRED FACILITIES SHALL BE BASED ON TOTAL SQUARE |
| | FOOTAGE (M2) WITHIN A COVERED MALL BUILDING OR WITHIN |
| | THE PERIMETER LINE OF AN OPEN MALL BUILDING, AND |
| | FACILITIES SHALL BE INSTALLED IN EACH INDIVIDUAL STORE |
| | OR IN A CENTRAL TOILET AREA LOCATED IN ACCORDANCE WITH |
| | THIS SECTION. THE MAXIMUM DISTANCE OF TRAVEL TO CENTRAL |
| | TOILET FACILITIES IN MALL BUILDINGS SHALL BE MEASURED |
| | FROM THE MAIN ENTRANCE OF ANY STORE OR TENANT SPACE. IN |
| | MALL BUILDINGS, WHERE EMPLOYEES? TOILET FACILITIES ARE |
| | NOT PROVIDED IN THE INDIVIDUAL STORE, THE MAXIMUM |
| | DISTANCE OF TRAVEL SHALL BE MEASURED FROM THE |
| | EMPLOYEES? WORK AREA OF THE STORE OR TENANT SPACE. |
| | |
| | 3) AS THIS PERMIT IS FOR A TENANT BUILD OUT OF A |
| | BUSINESS TENANT THERE ARE NO PLANS SUBMITTED SHOWING |
| | COMPLIANCE FOR CHECK WRITING COUNTERS AND |
| | ACCESSIBILITY. |
| | |
| | 3A) 902.1 .WORK SURFACES SHALL COMPLY WITH 902.2 AND |
| | 902.3. ADVISORY 902.1 GENERAL. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS. |
| | |
| | 3A)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 3A))(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 3A)(3) . 2017 ACCESS. CODE 904.3.3 CHECK WRITING |
| | SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL |
| | COMPLY WITH 902.3. 902.3HEIGHT. |
| | |
| | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 3A)(4) 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS |
| | AND SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR |
| | 904.4.2. THE ACCESSIBLE PORTION OF THE COUNTER TOP |
| | SHALL EXTEND THE SAME DEPTH AS THE SALES OR SERVICE |
| | COUNTER TOP. |
| | |
| | 4) DIGITAL REVIEWS. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |