Plan Review Details - Permit 18101310
Plan Review Stops For Permit 18101310
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-11-08 Cont ID  
Sent By jgomez Date 2018-11-08 Time 17:09 Rev Time 0.00
Received By jgomez Date 2018-11-08 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-11-08 Cont ID  
Sent By jgomez Date 2018-11-08 Time 10:49 Rev Time 0.00
Received By jgomez Date 2018-11-08 Time 10:04 Sent To  
Notes
2018-11-08 10:59:05RECEIVED E-MAIL FROM PANCHO SANCHEZ
 FLAME SPREAD TEST AND BUILDING SECTION SHOWING 6"
 CONCRETE SLAB.
  
  
  
 RESIDENTIAL (R2) FLOORING, THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 1- NOW WE KNOW FOR SURE THAT THE BUILDING HAS 6"
 CONCRETE SLABS AND COPY OF THE TEST FOR THE FLAME AND
 SMOKE SPREAD SUBMITTED IS OK. IT SHOWS THAT THE TEST
 WAS DONE ON WOOD FLOORING WHICH IS THE PROPOSED FINISH
 FLOORING.
 BUT, WE STILL NEED COPIES OF THE STC (SOUND
 TRANSMISSION) AND IIC (IMPACT SOUND TRANSMISSION) TESTS
 DONE WITH WOOD FLOORING . THE TESTS SUBMITTED ARE FOR
 PORCELAIN TILE.
 SEE ORIGINAL COMMENTS BELOW:
  
  
  
  
 FLOORING UNDERLAYMENT
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR
 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING.
 TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS
 IN THESE BUILDINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-05 Cont ID  
Sent By jgomez Date 2018-11-05 Time 14:38 Rev Time 0.00
Received By jgomez Date 2018-11-05 Time 13:56 Sent To  
Notes
2018-11-05 14:42:02RESIDENTIAL (R2) FLOORING, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 1- THE COPIES OF THE TESTS YOU SUBMITTED ARE THE KIND
 OF INFORMATION WE NEED. THE ONLY THING IS THAT WE NEED
 COPIES OF THE TESTS DONE FOR WOOD FLOORING. THE TESTS
 SUBMITTED ARE FOR PORCELAIN TILE.
 ALSO, WE NEED THE COPY OF THE FLAME SPREAD TEST FOR
 FLOORING ASSEMBLY WITH WOOD FINISH AS PER YOUR PROPOSED
 INSTALLATION. SEE ORIGINAL COMMENTS BELOW:
  
  
  
  
  
 FLOORING UNDERLAYMENT
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR
 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING.
 TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS
 IN THESE BUILDINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-31 Cont ID  
Sent By jgomez Date 2018-10-31 Time 18:27 Rev Time 0.00
Received By jgomez Date 2018-10-31 Time 18:21 Sent To  
Notes
2018-10-31 18:28:24RESIDENTIAL (R2)
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 FLOORING UNDERLAYMENT
 1- SOUND INSULATION MATERIAL SUBMITTED:
 A) PROVIDE 2 COPIES OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 6TH EDITION
 (2017).
  
 B) PROVIDE 2 COPIES OF THE SOUND TRANSMISSION CLASS
 (STC) TEST DONE IN ACCORDANCE WITH ASTM E 90 AS
 REQUIRED BY SEC. 1207.2 OF FBC 6TH EDITION (2017).
  
 NOTE: TEST SAMPLE TO MATCH BUILDING CONSTRUCTION. THERE
 ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH OR WITHOUT
 ACOUSTICAL CEILING.
  
 C) PROVIDE 2 COPIES OF THE IMPACT INSULATION CLASS
 (IIC) TEST DONE IN ACCORDANCE WITH ASTM E 492 AS
 REQUIRED BY SEC. 1207.3 OF FBC 6TH EDITION (2017).
  
  
 NOTE: TEST SAMPLES TO MATCH BUILDING CONSTRUCTION AND
 PROPOSED FLOOR FINISH. ALSO, THERE ARE TESTS FOR 6" OR
 8" CONCRETE SLABS WITH OR WITHOUT ACOUSTICAL CEILING.
 TYPICALLY THERE ARE NOT SUSPENDED ACOUSTICAL CEILINGS
 IN THESE BUILDINGS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-08 Cont ID  
Sent By jgomez Date 2018-11-08 Time 17:10 Rev Time 0.00
Received By jgomez Date 2018-11-08 Time 15:26 Sent To I
Notes
2018-11-08 15:27:24RECEIVED ANOTHER E-MAIL FROM PANCHO SANCHEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-08 Cont ID  
Sent By jgomez Date 2018-11-08 Time 10:59 Rev Time 0.00
Received By jgomez Date 2018-11-08 Time 10:04 Sent To  
Notes
2018-11-08 10:04:59RECEIVED E-MAIL FROM PANCHO SANCHEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-05 Cont ID  
Sent By jgomez Date 2018-11-05 Time 14:42 Rev Time 0.00
Received By jgomez Date 2018-11-05 Time 13:55 Sent To  
Notes
2018-11-05 13:56:09RECEIVED E-MAIL FROM PANCHO SANCHEZ.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-31 Cont ID  
Sent By jgomez Date 2018-10-31 Time 18:37 Rev Time 0.00
Received By jgomez Date 2018-10-29 Time 14:03 Sent To I
Notes
2018-10-30 14:06:49BLDG <5K