Plan Review Details - Permit 18101272
Plan Review Stops For Permit 18101272
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-10 Cont ID  
Sent By shill Date 2018-12-10 Time 08:55 Rev Time 0.00
Received By dbattles Date 2018-12-07 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-11-13 Cont ID  
Sent By jpearson Date 2018-11-13 Time 08:21 Rev Time 0.00
Received By jpearson Date 2018-11-13 Time 08:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By pleduc Date 2018-10-29 Time   Rev Time 0.00
Received By pleduc Date 2018-10-29 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2019-01-03 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-12 Time 10:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-10 Cont ID  
Sent By dbattles Date 2018-12-10 Time 08:55 Rev Time 0.00
Received By dbattles Date 2018-10-26 Time 15:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By ccole Date 2019-01-03 Time 12:00 Rev Time 0.00
Received By ccole Date 2019-01-03 Time 10:50 Sent To  
Notes
2019-01-03 12:03:48MECHANICAL PROVISOS:
 REVISION #18101272
 MASTER #15111020
 UNIT 18B
  
 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS
 AND RETURN AIR CLOSETS.
  
 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS.
  
 3) DRYER EXHAUST DUCTS SHALL NOT RUN THROUGH PLENUMS.
  
 4) MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES, KITCHEN HOOD AND EXHAUST DUCT, AND DRYER
 SHALL BE ONSITE AT TIME OF INSPECTION.
 A) ELECTRIC COOKING APPLIANCES AND EXHAUST HOODS SHALL
 BE UL LISTED AND LABELED FOR DOMESTIC USE.
 B) GAS-FIRED COOKING APPLIANCES SHALL BE LISTED AND
 LABELED FOR DOMESTIC USE AND SHALL BE TESTED IN
 ACCORDANCE WITH ANSI Z21.1, Z21.58 OR Z83.11.
  
 5) 505.2 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CFM (0.19 M3/S) SHALL BE PROVIDED WITH MAKEUP AIR
 AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE.
 SUCH MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH A MEANS
 OF CLOSURE AND SHALL BE AUTOMATICALLY CONTROLLED TO
 START AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST
 SYSTEM.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-21 Cont ID  
Sent By ccole Date 2018-11-21 Time 08:15 Rev Time 0.00
Received By ccole Date 2018-11-21 Time 07:26 Sent To  
Notes
2018-11-21 08:33:021ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18101272
 11/21/18
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) BECASUE OF THE SHARED RETURN PLENUM EXCEEDING 2000
 CFMS, SMOKE DETECTORS ARE REQUIRED IN BOTH THE SUPPLY
 AND RETURN SYSTEMS- SECTION 606.2.2 FBC M. PLEASE
 PROVIDE SYMBOLS ON THE PLANS TO SHOW THE LOCATIONS.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN
 EXHAUST HOOD, COOKING APPLIANCES, AND THE CLOTHES
 DRYER- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By gjohnson Date 2018-12-06 Time 13:10 Rev Time 0.00
Received By gjohnson Date 2018-12-06 Time 13:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By ccole Date 2019-01-03 Time 12:05 Rev Time 0.00
Received By ccole Date 2019-01-03 Time 12:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-13 Cont ID  
Sent By jpearson Date 2018-11-13 Time 08:03 Rev Time 0.00
Received By jpearson Date 2018-11-13 Time 08:03 Sent To  
Notes
2018-12-06 13:12:19PLUMB DIG SIG OK/GPJ 12/6/18
2018-11-13 08:03:45EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE. SHEET
 328.50-A7-90-18B IS MISSING THE DIGITAL SIGNATURE. ALL
 OTHER SHEETS OK. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481