Plan Review Details - Permit 18101272
| Plan Review Stops For Permit 18101272 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-12-10 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-12-07 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-11-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-13 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-13 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-10-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-10-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-10-29 |
Time |
14:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-01-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-12-12 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-10 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2018-12-10 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2018-10-26 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2019-01-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-03 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-03 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2019-01-03 12:03:48 | MECHANICAL PROVISOS: | | | REVISION #18101272 | | | MASTER #15111020 | | | UNIT 18B | | | | | | 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS | | | AND RETURN AIR CLOSETS. | | | | | | 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS. | | | | | | 3) DRYER EXHAUST DUCTS SHALL NOT RUN THROUGH PLENUMS. | | | | | | 4) MANUFACTURER'S SPECIFICATIONS FOR THE COOKING | | | APPLIANCES, KITCHEN HOOD AND EXHAUST DUCT, AND DRYER | | | SHALL BE ONSITE AT TIME OF INSPECTION. | | | A) ELECTRIC COOKING APPLIANCES AND EXHAUST HOODS SHALL | | | BE UL LISTED AND LABELED FOR DOMESTIC USE. | | | B) GAS-FIRED COOKING APPLIANCES SHALL BE LISTED AND | | | LABELED FOR DOMESTIC USE AND SHALL BE TESTED IN | | | ACCORDANCE WITH ANSI Z21.1, Z21.58 OR Z83.11. | | | | | | 5) 505.2 MAKEUP AIR REQUIRED. | | | EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF | | | 400 CFM (0.19 M3/S) SHALL BE PROVIDED WITH MAKEUP AIR | | | AT A RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE. | | | SUCH MAKEUP AIR SYSTEMS SHALL BE EQUIPPED WITH A MEANS | | | OF CLOSURE AND SHALL BE AUTOMATICALLY CONTROLLED TO | | | START AND OPERATE SIMULTANEOUSLY WITH THE EXHAUST | | | SYSTEM. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-11-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-11-21 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-11-21 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2018-11-21 08:33:02 | 1ST REVIEW FBC-2010 MECHANICAL | | | PERMIT #18101272 | | | 11/21/18 | | | | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) BECASUE OF THE SHARED RETURN PLENUM EXCEEDING 2000 | | | CFMS, SMOKE DETECTORS ARE REQUIRED IN BOTH THE SUPPLY | | | AND RETURN SYSTEMS- SECTION 606.2.2 FBC M. PLEASE | | | PROVIDE SYMBOLS ON THE PLANS TO SHOW THE LOCATIONS. | | | | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN | | | EXHAUST HOOD, COOKING APPLIANCES, AND THE CLOTHES | | | DRYER- SECTION 304.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-12-06 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-12-06 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-12-06 |
Time |
13:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2019-01-03 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-01-03 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-01-03 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-11-13 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-13 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-13 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2018-12-06 13:12:19 | PLUMB DIG SIG OK/GPJ 12/6/18 | | 2018-11-13 08:03:45 | EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED | | | BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL | | | PLAN REQUIRES A DIGITAL SIGNATURE. SHEET | | | 328.50-A7-90-18B IS MISSING THE DIGITAL SIGNATURE. ALL | | | OTHER SHEETS OK. PROVIDE CORRECTION. WPB FBC 107.1; FS | | | 471/481 |
|
|
|