Plan Review Details - Permit 18101244
| Plan Review Stops For Permit 18101244 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-11-14 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-11-14 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-10-30 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-10-30 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2018-10-30 18:17:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER | | | SHEET WHICH SHOWS THE APPROVAL NUMBER AND STATUS, FBC R | | | 301. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-11-07 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-07 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-07 |
Time |
06:54 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-01 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-11-01 |
Time |
07:09 |
Sent To |
I |
|
| Notes |
| 2018-11-01 07:16:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NO ELECTRICAL PLAN PROVIDED FOR REVIEW. PROVIDE | | | ELECTRICAL PLAN FOR REVIEW, SIGNED AND SEALED BY A | | | LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-657-1653 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-11-14 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-11-14 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-11-02 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2018-11-06 12:39:57 | RESUB ROUTED TO FGIAQUINTO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-11-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-11-01 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-10-26 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2018-10-30 18:18:48 | 10/30 TO ELEC BOX | | | | | 2018-10-29 10:49:19 | SHILL |
|
|
|