Plan Review Details - Permit 18101205
Plan Review Stops For Permit 18101205
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-05 Cont ID  
Sent By cthroop Date 2018-11-05 Time 09:40 Rev Time 0.00
Received By cthroop Date 2018-11-05 Time 09:15 Sent To  
Notes
2018-11-05 09:40:59GEO TECH. REPORT REQUIRED PER KC. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-26 Cont ID  
Sent By cthroop Date 2018-10-26 Time 11:04 Rev Time 0.00
Received By cthroop Date 2018-10-26 Time 11:04 Sent To  
Notes
2018-10-26 11:22:51BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: THIS IS NOT A THRESHOLD BUILDING AND DOES NOT
 FALL UNDER THE REQUIREMENTS OF FS 553.79.
  
 1. PROVIDE LETTER FROM OWNER/CONTRACTOR REQUETING THE
 USE OF A RESIDENT INSPECTOR. STATE THE REASON WHY YOU
 ARE REQUESRTING THESE SERVICES.
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION
 OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION
 553.73, FLORIDA STATUTES, WITHOUT DUPLICATIVE
 INSPECTION BY THE BUILDING DEPARTMENT. THE BUILDING
 OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON
 CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR
 UNDER CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS
 OF THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5),
 FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
  
 2. RESIDENT INSPECTOR AGREEMENT SHALL BE COMPLETED AND
 SUBMITTED IN TRIPLICATE. - COMPLETED
 YOU MAY OBTAIN A COPY OF THE CURRENT R.I. FORM @
 ONESTOPSHOP.WPBGOV.COM.
 3. PROVIDE RESUME OF JOB INSPECTOR (P.E., ARCH. OR 468
 INSPECTOR).
 4. PROVIDE LIST OF SIMILAR PROJECTS COMPLETED BY
 CONTRACTOR.
 5. PROVIDE STRUCTURAL INSPECTION PLAN.
 6. FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECTS. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-05 Cont ID  
Sent By cthroop Date 2018-11-05 Time 09:40 Rev Time 0.00
Received By cthroop Date 2018-10-30 Time 13:24 Sent To  
Notes
2018-11-02 13:24:59RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-26 Cont ID  
Sent By cthroop Date 2018-10-26 Time 12:23 Rev Time 0.00
Received By cthroop Date 2018-10-26 Time 11:04 Sent To  
Notes
***NONE***