Plan Review Details - Permit 18101195
Plan Review Stops For Permit 18101195
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-12 Cont ID  
Sent By shill Date 2019-01-12 Time 16:25 Rev Time 0.00
Received By shill Date 2019-01-12 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 15:38 Rev Time 0.00
Received By shill Date 2018-12-08 Time 15:38 Sent To  
Notes
2018-12-08 15:43:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE 2010
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SHEET A2.2, REVISE PLAN AT KITCHEN TO SHOW DIMENSION
 FROM FACE OF APPLIANCES OR COUNTER TOP TO OPPOSING
 COUNTERTOP OR APPLIANCES; FBC A FAIR HOUSING ACT DESIGN
 MANUAL CHAPTER 7, 40" MINIMUM REQUIRED.
  
 2. SEE PLUMBING FAIR HOUSING COMMENTS; APPLICABLE FOR
 BUILDING REVIEW.
  
 3. AS DISCUSSED, PLEASE RESUBMIT AS A DIGITAL SUBMITTAL
 SO WE CAN BETTER EXPEDITE YOUR REVIEWS. AS THE
 ARCHITECT DOES NOT HAVE A DIGITAL SIGNATURE, ONE SIGNED
 AND SEALED ORIGINAL SET OF ARCHITECTURAL PAGES CAN BE
 SUBMITTED (PAPER) AFTER REVIEWS HAVE PASSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By jpearson Date 2019-01-22 Time 15:46 Rev Time 0.00
Received By jpearson Date 2019-01-22 Time 15:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By jpearson Date 2018-12-03 Time 15:45 Rev Time 0.00
Received By jpearson Date 2018-12-03 Time 14:18 Sent To  
Notes
2018-12-03 15:45:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IN THE CLOTHES CLOSETS, THERE IS A LIGHTING SYMBOL
 USED THAT DOES NOT APPEAR IN THE LIGHTING LEGEND. THIS
 APPEARS TO BE A PENDANT TYPE FIXTURE. PER CODE,
 LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND
 PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE
 PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC
 410.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-02 Cont ID  
Sent By pleduc Date 2019-01-02 Time   Rev Time 0.00
Received By pleduc Date 2019-01-02 Time 14:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By pleduc Date 2018-10-29 Time   Rev Time 0.00
Received By pleduc Date 2018-10-29 Time 13:47 Sent To  
Notes
2018-10-29 13:53:59THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET FA 2.2 - ALL FIRE ALARM EQUIPMENT INSTALLATION
 SHALL BE UNDER SEPARATE SHOP DRAWINGS SUBMITTAL, BY A
 LICENSED FA CONTRACTOR.
  
 PLEASE ENSURE THAT SHOP DRAWINGS ARE SUBMITTED FOR
 APPROVAL.
  
  
  
 2) SHEET FP 2.2 - THERE APPEARS TO BE TWO FIRE
 SPRINKLER HEAD MISSING FROM THE PROPOSED. ONE IN THE
 MASTER HALL AND THE OTHER IN THE AV CLOSET.
  
 IN AN EFFORT TO MOVE THIS PROJECT FORWARD THIS PROVISO
 IS BEING MADE SO THAT SHOP DRAWINGS CAN BE DEVELOPED TO
 ENSURE FIRE SPRINKLER COVERAGE IN THESE AREAS.
  
 PLEASE REVIEW AND CORRECT WITH SHOP DRAWINGS OR JUSTIFY
 WITH SPECIFIC FIRE SPRINKLER CODE REFERENCES.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-04-04 Cont ID  
Sent By tklarge Date 2020-04-04 Time 10:15 Rev Time 0.00
Received By tklarge Date 2020-04-04 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-25 Cont ID  
Sent By gjohnson Date 2019-01-25 Time 10:46 Rev Time 0.00
Received By gjohnson Date 2018-12-28 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 15:43 Rev Time 0.00
Received By shill Date 2018-10-25 Time 15:11 Sent To  
Notes
2018-10-26 15:11:21C24

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-03-01 Cont ID  
Sent By ccole Date 2019-03-01 Time 11:44 Rev Time 0.00
Received By ccole Date 2019-03-01 Time 10:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-01-22 Cont ID  
Sent By ccole Date 2019-01-22 Time 12:27 Rev Time 0.00
Received By ccole Date 2019-01-22 Time 09:55 Sent To  
Notes
2019-01-22 12:32:002ND REVIEW FBC-2010 MECHANICAL
 PERMIT #18101195
 12/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REQUIRED DUCT SMOKE DETECTORS IN THE SUPPLY
 SYSTEMS NOT SHOWN- SEE SECTION 606.2.2 FBC M AND 1ST
 REVIEW COMMENT #5) SHEET M2.2-9D: BECAUSE OF THE SHARED
 RETURN PLENUM EXCEEDING 2000 CFMS, SMOKE DETECTORS ARE
 REQUIRED IN BOTH THE SUPPLY AND RETURN SYSTEMS OF THE
 NEW HEAT PUMPS- SECTION 606.2.2 FBC M. PLEASE PROVIDE
 SYMBOLS ON THE PLANS TO SHOW THE LOCATIONS.
  
 2) THE SUBMITTED SPECS FOR THE MIELE APPLIANCES DO NOT
 PROVIDE ANY LISTING AND LABELING DOCUMENTATION- SEE
 SECTIONS 917.1 AND 917.2 FBC M AND 1ST REVIEW COMMENT
 #6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 KITCHEN EXHAUST HOOD, COOKING APPLIANCES, AND THE
 CLOTHES DRYER- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-03 Cont ID  
Sent By ccole Date 2018-12-03 Time 09:17 Rev Time 0.00
Received By ccole Date 2018-11-30 Time 17:14 Sent To  
Notes
2018-12-03 09:51:061ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18101195
 12/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW HEAT PUMP SYSTEMS- SECTION 503.2.1 FBC ENERGY
 CONSERVATION.
  
 2) PROVIDE REVISED ENERGY CALCULATIONS FOR THE PROPOSED
 TENANT BUILDOUT- SECTION 103.2.1.2 FBC ENERGY
 CONSERVATION.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-10 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 4) SHEET M2.2-9D: INDICATE HOW OUTDOOR AIR IS BEING
 PROVIDED TO THE APARTMENT- SECTION 401.2- FBC M.
  
 5) SHEET M2.2-9D: BECAUSE OF THE SHARED RETURN PLENUM
 EXCEEDING 2000 CFMS, SMOKE DETECTORS ARE REQUIRED IN
 BOTH THE SUPPLY AND RETURN SYSTEMS OF THE NEW HEAT
 PUMPS- SECTION 606.2.2 FBC M. PLEASE PROVIDE SYMBOLS ON
 THE PLANS TO SHOW THE LOCATIONS.
  
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN
 EXHAUST HOOD, COOKING APPLIANCES, AND THE CLOTHES
 DRYER- SECTION 304.1 FBC M.
  
 7) M2.2-9D: THE PLAN SHOWS DUCTWORK IN THE MAIN
 BUILDING CORE. CLARIFY IF THIS IS NEW OR EXISTING
 DUCTWORK BY SHADING THE AREA OR PLACING NOTES ON THE
 PLAN. OTHERWISE IT WILL BE ASSUMED TO BE NEW OR ALTERED
 DUCTWORK THAT IS SUBJECT TO REVIEW AND INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-25 Cont ID  
Sent By gjohnson Date 2019-01-25 Time 10:46 Rev Time 0.00
Received By gjohnson Date 2019-01-25 Time 07:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By gjohnson Date 2018-12-06 Time 17:35 Rev Time 0.00
Received By gjohnson Date 2018-12-06 Time 13:40 Sent To  
Notes
2018-12-06 17:36:021ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
 1. THIS PROJECT IS ALL DIGITAL WHEN YOU RESUBMIT IT
 SHALL BE A DIGITAL RESUBMITAL.
 2. PLEASE INDICATE ON THE PLAN WHAT DOCUMENT WAS USED
 TO COMPLY WITH FHA.
 3. SHOW CLEAR FLOOR SPACE FOR KITCHEN TO COMPLY WITH
 FHA REQUIREMENT #7
 4. 40" CLEARANCE SHALL BE MAINTAINED AROUND THE ISLAND
 IN THE KITCHEN FHA REQUIREMENT #7
 5. PROVIDE NOT E OR DETAIL WITH THE HEIGHT AND WIDTH OF
 THE LAVATORY VANITY. FHA REQUIREMENT #7
 6. THE KNEE WALL NEXT TO TOILET SHALL BE A MAX OF 24"
 FHA REQUIREMENT #7
 7. GRAB BAR BACKING IS REQUIRED IN ALL BATHROOMS SHOW
 LOCATION AND A DETAIL WITH HEIGHT DIMENSIONS FHA
 REQUIREMENT #6
 8. PLEASE PROVIDE ISOMETRIC DRAWING FOR SANITARY, WATER
 AND GAS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-03-07 Cont ID  
Sent By dbattles Date 2019-03-07 Time 14:16 Rev Time 0.00
Received By dbattles Date 2019-03-07 Time 14:16 Sent To  
Notes
2019-03-07 14:17:21HARD COPIES OF A-SHEETS BROUGHT IN AND SENT TO FILE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-03-01 Cont ID  
Sent By ccole Date 2019-03-01 Time 11:45 Rev Time 0.00
Received By ccole Date 2019-03-01 Time 11:45 Sent To  
Notes
2019-03-01 12:01:21MECH ELECTRONIC SEALS AND SIGNATURES GOOD.
 SEE SIGNATURE REVIEW BY SHILL DATED 1/12/2019

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2019-01-12 Cont ID  
Sent By shill Date 2019-01-12 Time 16:25 Rev Time 0.00
Received By shill Date 2019-01-12 Time 16:25 Sent To  
Notes
2019-01-12 16:26:54A SHEETS ARE NOT DIGITALLY SIGNED (APPLICANT TO PROVIDE
 ONE PAPER ORIGINAL AFTER REVIEWS HAVE PASSED,
 "SUBMITTAL" FORM, DESCRIPTION "SIGNATURE DOCUMENTS")
  
 FMEP OK
  
  