Plan Review Details - Permit 18101099
Plan Review Stops For Permit 18101099
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 12:40 Rev Time 0.00
Received By shill Date 2018-12-08 Time 12:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jpearson Date 2018-12-18 Time 15:34 Rev Time 0.00
Received By jpearson Date 2018-12-18 Time 15:34 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 14:26 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 12:27 Sent To  
Notes
2018-11-06 14:26:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. NOTE 15 AND BLOCK NOTE FOR AFCI PROTECTION SHOWN IS
 NOT CODE COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12; FBC
 RE E3902; FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS
 APPLICABLE.
 3. GFCI RECEPTACLE IS REQUIRED FOR GARAGE. NEC 210.8;
 FBC RE E3902.2
 4. LIGHT IN CLOSET IS SHOWN CLOSE TO THE CLOSET STORAGE
 SPACE. PROVIDE CORRECTION. NEC 410.16; FBC RE E4003.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-12-18 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-14 Time 16:24 Sent To  
Notes
2018-12-17 16:24:41RESUB ROUTED TO JESMITH

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 13:45 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 13:45 Sent To  
Notes
2018-12-08 12:40:4012/8 REMOVED FROM BOARD; ROUTED TO JES DESK / S.HILL
  
2018-10-25 15:11:48R17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-06 Cont ID  
Sent By cmontell Date 2018-11-06 Time 11:21 Rev Time 0.00
Received By cmontell Date 2018-11-06 Time 11:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jesmith Date 2018-12-18 Time 11:09 Rev Time 0.00
Received By jesmith Date   Time   Sent To  
Notes
2018-12-18 11:09:07PLUMBING COMMEMTS: APPROVED
  
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By jesmith Date 2018-12-11 Time 13:44 Rev Time 0.00
Received By jesmith Date 2018-12-11 Time 13:44 Sent To  
Notes
2018-12-11 13:44:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 1. R: WATER HEATER DETAIL, SHOW THERMAL EXPANSION
 RELIEF COMPLYING WITH THE REQUIREMENTS OF FBC PL 607.3
 2. MASTER BATH LAVATORY AND NEW BATH LAVATORY EACH
 REQUIRS A VENT. PROVIDE INDIVIDUAL VENT OR AIR
 ADMITTANCE VALVE IN ACCORDANCE WITH P3106.1 AND
 P3104.1.
 3. THE VENT CONNECTED TO THE NEW BATH TUB FIXTURE DRAIN
 SHALL NOT TRAVEL HORIZONTALLY. IT MUST RISE VERTICALLY
 TO A POINT 6? ABOVE THE FIXTURE FLOOD LEVEL RIM BEFORE
 OFFSETTING HORIZONTALLY. SEE P3104.3 AND P3104.
  
 END OF COMMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  