| 2018-10-25 10:30:21 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18101097 |
| | REVIEWED: OCTOBER 25, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | [FBC 107.5.2]PROVIDE DIAGRAM TO SHOW LOCATION OF ROOF |
| | AREA TO BE REPLACED. |
| | ADD ROOF PITCH TO DIAGRAM TO SHOW DRAINAGE. |
| | |
| | PROVISO: (NO RESPONSE REQUIRED) |
| | PROVIDE NAILING TO BRING THE SHEATHING UP TO CURRENT |
| | FBC 2017 STANDARDS AS PROVIDED BELOW FOR THE SHEATHING |
| | APPLICATION THAT APPLIES TO YOUR PROJECT. |
| | |
| | [FBC R908.7.1.1] |
| | ROOF DECKING CONSISTING OF SAWN LUMBER OR WOOD PLANKS |
| | UP TO 12 INCHES WIDE AND SECURED WITH AT LEAST TWO |
| | NAILS (MINIMUM SIZE 8D) TO EACH ROOF FRAMING MEMBER IT |
| | CROSSES SHALL BE DEEMED TO BE SUFFICIENTLY CONNECTED. |
| | SAWN LUMBER OR WOOD PLANK DECKING SECURED WITH SMALLER |
| | FASTENERS THAN 8D NAILS OR WITH FEWER THAN TWO NAILS |
| | (MINIMUM SIZE 8D) TO EACH FRAMING MEMBER IT CROSSES |
| | SHALL BE DEEMED SUFFICIENTLY CONNECTED IF FASTENERS ARE |
| | ADDED SUCH THAT TWO CLIPPED HEAD, ROUND HEAD, OR RING |
| | SHANK NAILS (MINIMUM SIZE 8D) ARE IN PLACE ON EACH |
| | FRAMING MEMBER IT CROSSES. |
| | |
| | R908.7.1.2 |
| | FOR ROOF DECKING CONSISTING OF WOOD STRUCTURAL PANELS, |
| | FASTENERS AND SPACING REQUIRED IN COLUMNS 3 AND 4 OF |
| | TABLE R908.7.1.2 ARE DEEMED TO COMPLY WITH THE |
| | INDICATED DESIGN WIND SPEED RANGE. WOOD STRUCTURAL |
| | PANEL CONNECTIONS RETROFITTED WITH A TWO PART URETHANE |
| | BASED CLOSED CELL ADHESIVE SPRAYED ONTO THE JOINT |
| | BETWEEN THE SHEATHING AND FRAMING MEMBERS ARE DEEMED TO |
| | COMPLY PROVIDED TESTING USING THE MANUFACTURER?S |
| | RECOMMENDED APPLICATION ON PANELS CONNECTED WITH 6D |
| | SMOOTH SHANK NAILS AT NO MORE THAN A 6-INCH EDGE AND |
| | 12-INCH FIELD SPACING DEMONSTRATE AN UPLIFT RESISTANCE |
| | OF A MINIMUM OF 200 PSF. |
| | |
| | |
| | |
| | |