Plan Review Details - Permit 18101094
| Plan Review Stops For Permit 18101094 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-04 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-04 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2018-12-04 14:41:56 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | FAILED | | | | | | THE DRAWINGS DO NOT CONTAIN ADEQUATE INFORMATION IN | | | TERMS OF UNDERSTANDING THE LEVEL OF ALTERATION | | | PROPOSED. PLEASE PROVIDE THE EXISTING FLOOR PLAN IN | | | ORDER TO DETEMINE THE ALTERATION PROPOSED AND PROVIDE | | | CODE DATA AS APPLICABLE ALSO PROVIDE A WALL SECTION TO | | | SHOW THE MATERIALS TO BE USED AND DETAILS OF ANY NEW | | | WALLS.. IT APPEARS THE CODE REFERENCE SHOULD BE AS | | | FOLLOWS: | | | | | | FBC 2017 EXISTING BUILDING | | | ALTERATION LEVEL II | | | TYPE V COSTRUCTION | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-06 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-06 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2018-11-06 10:56:28 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN THAT IS LEGIBLE AND TO | | | PROPER SCALE. BUILDING PLANS SHALL BE DRAWN TO A | | | MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR | | | OTHER ACCEPTABLE MEDIUM. WPB FBC 107.2.1.3 | | | 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902; FBC EX | | | 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. | | | 3. PROVIDE DEDICATED 20 AMP CIRCUIT FOR GFCI PROTECTED | | | RECEPTACLE OUTLET LOCATED WITHIN 3 FEET OF BASIN. NEC | | | 210.11(C)(3), 210.52(D); FBC RE E3703.4, E3901.6 | | | 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING | | | ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS | | | NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC | | | 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-04 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-04 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2018-12-04 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2018-12-04 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2018-12-04 13:59:48 | 1ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL | | | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | | | MECHANICAL FAILED. | | | | | | THERE IS NO INFORMATION PRESENTED TO SHOW THE VENTING | | | FOR THE DRYER OR IT'S LOCATION. IF NEW PLEASE PROVIDE | | | THIS IF EXISTING, PLEASE SHOW AS EXISTING. | | | | | | FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER | | | EXHAUST., | | | | | | | | | STEVEN KENNEDY, CBO | | | ASSISTANT BUILDING OFFICIAL | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2018-12-04 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2018-12-04 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2018-12-04 15:10:07 | 1ST REVIEW | | | COMMENTS: DENIED | | | | | | 1. A SANITARY RISER DIAGRAM IS REQUIRED PER WPB FBC | | | 107.2.1. | | | 2. PROVIDE AN EXISTING FLOOR PLAN SHOWING ORIGINAL | | | CONFIGURATION IN THE FOOTPRINT OF THE NEW WORK PER WPB | | | FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | | | | JERALD SMITH | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | EMAIL [email protected] | | | PHONE 561-805-6715 | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION | | | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION | | | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION | | | FAC= FLORIDA ADMINISTRATIVE CODE | | | FS = FLORIDA STATUTES |
|
|
|