Plan Review Details - Permit 18101088
Plan Review Stops For Permit 18101088
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-02-06 Cont ID  
Sent By pvalenti Date 2019-02-06 Time 09:35 Rev Time 0.00
Received By pvalenti Date 2019-02-06 Time 09:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-01-19 Cont ID  
Sent By pvalenti Date 2019-01-19 Time 10:13 Rev Time 0.00
Received By pvalenti Date 2019-01-14 Time 08:35 Sent To  
Notes
2019-01-19 10:45:43****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 THE PENDING ITEMS FROM LAST REVIEW CONTINUE AS NOTED
 BELOW:
  
 1. VALUATION: THE VALUATION SHOWN ON THE APPLICATION
 SHOULD BE A TOTAL AND NEEDS TO INCLUDE VALUE OF RELATED
 SUB PERMITS.
  
 2. THE TIE BEAM DIMENSIONS ARE NOT INCLUDED ON THE
 LATEST SUBMITTED PLAN. ON THE INITIAL PLAN SUBMITTAL AN
 8" X 12" TIE BEAM WAS SHOWN BUT THERE WAS ALSO A DETAIL
 FOR AN 8" X 8" BOND BEAM. PLEASE CLARIFY.
  
 3. THE WINDOW SCHEDULE IDENTIFICATION "MARKS" DO NOT
 MATCH THE IDENTIFACATION NUMBERS SHOWN ON THE OPENINGS
 OF THE FLOOR PLAN.
  
 4. PLEASE PROVIDE A CONNECTOR SCHEDULE FOR THE ROOF
 TRUSS TO THE TIE BEAM. THE SCHEDULE NEEDS TO INCLUDE
 THE SPECIFIC CONNECTORS TO BE USED AND NUMBER/SIZE OF
 FASTENERS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-12-20 Cont ID  
Sent By pvalenti Date 2018-12-20 Time 13:50 Rev Time 0.00
Received By pvalenti Date 2018-12-20 Time 13:50 Sent To  
Notes
2018-12-20 14:52:33****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. THE VALUATION OF THIS JOB APPEARS TO BE VERY LOW, AS
 THE PLANS INCLUDE:
 BUILDING:
 BLOCK WALL(APPROX. 50') TO BE REPLACED.
 ROOF & FLOOR FRAMING MEMBERS TO BE REPAIRED/REPLACED
 (INCLUDING SHEATHING).
 WINDOW/DOOR REPLACEMENT (IMPACT RESISTANT).
 INTERIOR WALL & DOOR FRAMING TO BE REMOVED/REPLACED.
 ELECTRIC: AS SHOWN ON PLANS (NO SUB-PERMIT).
 PLUMBING: AS SHOWN ON PLANS (NO SUB-PERMIT).
  
 2. THE BUILDING PLANS (PAGE A-2) ARE MISSING THE
 DIMENSIONS OF THE FOOTINGS AND TIE-BEAMS.
  
 3. THERE IS NO SCHEDULE FOR WINDOWS AND DOORS.
  
 NOTES:
  
 THERE WERE NO PRODUCT APPROVALS (WINDOWS/DOORS AND
 ROOFING PRODUCTS) SUBMITTED WITH PLANS.
 THERE IS A DEMO PERMIT THAT IS STILL OPEN.
 THERE HAVE BEEN NO OTHER PERMITS APPLIED FOR (SUCH AS
 MECHANICAL AND ROOFING).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-13 Cont ID  
Sent By pvalenti Date 2018-11-13 Time 16:14 Rev Time 0.00
Received By pvalenti Date 2018-11-13 Time 16:14 Sent To  
Notes
2018-11-13 16:21:19****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE REQUESTED INFORMATION/RESPONSES
 (FOR EACH ITEM) FROM LAST REVIEW.
  
 FEEL FREE TO CONTACT ME WITH ANY QUESTIONS REGARDING
 THIS REVIEW.
  
 PETER E. VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561 805 6673

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By pvalenti Date 2018-10-29 Time 15:47 Rev Time 0.00
Received By pvalenti Date 2018-10-29 Time 15:47 Sent To  
Notes
2018-10-29 17:09:38****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 THE EXISTING STRUCTURE DOES NOT APPEAR TO MATCH THE
 DESCRIBED STRUCTURE ON PLANS. THE EXISTING STRUCTURE
 APPEARS TO BE TWO STRUCTURES JOINED TOGETHER WITH THE
 EAST HALF HAVING A SLOPED ROOF, A FRONT PORCH, &
 SEVERAL WINDOWS. PLEASE PROVIDE MORE DETAILS ON PLAN
 INCLUDING:
  
 1. FBC EC R503.1.1 LOCATION AND SIZE OF WINDOW/DOOR
 OPENINGS.
 2. FBC EC R503.1.1.1 PROVIDE REPLACEMENT FENESTRATION
 DETAILS INCLUDING PRODUCT APPROVALS FOR NEW WINDOWS AND
 DOORS.
 3. FBC EB 807.2 CONNECTION DETAILS FOR THE NEW WALL TO
 EXISTING WALLS.
 4. FBC EB 807.2 DETAILS FOR THE ATTACHMENT OF
 REPLACEMENT JOISTS.
 5. FBC EB 807.2 DETAILS FOR THE TIE DOWN ATTACHMENTS OF
 NEW WALL TO EXISTING ROOF.
 6. FBC EB 807.2 DETAILS FOR THE NEW BLOCK WALL FOOTING.
 (NOTES ON PLAN DO NOT MATCH/PROVIDE FOOTING DETAIL)
 7. FBC R 702. DETAILS FOR THE INTERIOR FRAMING: FURRING
 & INSULATION OF NEW WALL.
 8. FBC EB 808.3 PROVIDE AN ELECTRIC SUB PERMIT.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-03-15 Cont ID  
Sent By jpearson Date 2019-03-15 Time 13:18 Rev Time 0.00
Received By jpearson Date 2019-03-15 Time 13:18 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-06 Cont ID  
Sent By jpearson Date 2019-02-06 Time 10:33 Rev Time 0.00
Received By jpearson Date 2019-02-06 Time 10:33 Sent To  
Notes
2019-02-06 10:33:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. THE DRYER AND LAUNDRY LOAD IS NOT
 INCLUDED, THE VALUE FOR THE RANGE IS NOT CODE
 COMPLIANT, AND THERE IS CONFUSION ON THE HVAC SYSTEM -
 PROVIDE CLARIFICATION. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 2. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 3. PROVIDE CLARIFICATION FOR HVAC. THE PANEL SCHEDULE
 SHOWS 5 DIFFERENT UNITS, BUT THE LOAD CALCULATION
 INCLUDES ONE CALCULATION FOR HEAT AT 65% DEMAND FACTOR,
 WHICH IS TYPICALLY USED FOR ONE CENTRAL SYSTEM. WHICH
 IS IT? LOAD CALCULATION SHOULD INCLUDE THE LARGER OF
 THE AC OR HEAT LOADS, BUT NOT BOTH.WPB FBC 107.2.1; NEC
 220; FBC RE E3602.2
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PROVIDE LOCATION OF ELECTRICAL PANEL AND SERVICE ON
 PLAN. WPB FBC 107.2.1
 6. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 8. CORRECT SYMBOLS ON PLAN TO MATCH LEGEND FOR SMOKE
 ALARMS. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2019-01-23 Cont ID  
Sent By jpearson Date 2019-01-23 Time 15:20 Rev Time 0.00
Received By jpearson Date 2019-01-23 Time 14:30 Sent To I
Notes
2019-01-23 15:20:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. THE DRYER AND LAUNDRY LOAD IS NOT
 INCLUDED, THE VALUE FOR THE RANGE IS NOT CODE
 COMPLIANT, AND THERE IS CONFUSION ON THE HVAC SYSTEM -
 PROVIDE CLARIFICATION. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 2. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN
 EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE
 CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1
 3. PROVIDE CLARIFICATION FOR HVAC. THE PANEL SCHEDULE
 SHOWS 5 DIFFERENT UNITS, BUT THE LOAD CALCULATION
 INCLUDES ONE CALCULATION FOR HEAT AT 65% DEMAND FACTOR,
 WHICH IS TYPICALLY USED FOR ONE CENTRAL SYSTEM. WHICH
 IS IT? LOAD CALCULATION SHOULD INCLUDE THE LARGER OF
 THE AC OR HEAT LOADS, BUT NOT BOTH.WPB FBC 107.2.1; NEC
 220; FBC RE E3602.2
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PROVIDE LOCATION OF ELECTRICAL PANEL AND SERVICE ON
 PLAN. WPB FBC 107.2.1
 6. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC
 RE E3606.3
 8. CORRECT SYMBOLS ON PLAN TO MATCH LEGEND FOR SMOKE
 ALARMS. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2019-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-03-12 Time 15:27 Sent To  
Notes
2019-03-13 15:27:19RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-02-16 Cont ID  
Sent By shill Date 2019-02-16 Time 09:41 Rev Time 0.00
Received By shill Date 2019-01-25 Time 15:27 Sent To  
Notes
2019-01-28 15:27:27B04

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-01-23 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-04 Time 12:42 Sent To  
Notes
2019-01-04 12:42:42B09

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-20 Cont ID  
Sent By pvalenti Date 2018-12-20 Time 14:53 Rev Time 0.00
Received By pvalenti Date 2018-12-18 Time 14:31 Sent To  
Notes
2018-12-19 14:32:06RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-13 Cont ID  
Sent By pvalenti Date 2018-11-13 Time 16:21 Rev Time 0.00
Received By pvalenti Date 2018-11-09 Time 14:45 Sent To I
Notes
2018-11-13 14:45:56RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By pvalenti Date 2018-10-29 Time 17:09 Rev Time 0.00
Received By pvalenti Date 2018-10-23 Time 15:43 Sent To I
Notes
2018-10-24 15:43:25BLDG MISC 1

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-05 Cont ID  
Sent By jesmith Date 2019-02-05 Time 14:56 Rev Time 0.00
Received By jesmith Date 2019-02-05 Time 14:54 Sent To  
Notes
2019-02-05 14:54:30 
 APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL
 2. WASHER AND SINK SHALL CONNECT DOWNSTREAM OF BATHROOM
 PER FBC PL 912.1 AND FBC RES P3108.1
 3. PROVIDE THERMAL EXPANSION CONTROL DEVICE FOR COLD
 WATER SUPPLY TO TANK TYPE WATER HEATER PER FBC PL 607.3
 AND FBC RES P2903.4.2
 4. T & P RELIEF LINE SHALL DISCHARGE THROUGH AN AIR GAP
 IN THE SAME ROOM AS THE WATER HEATER PER FBC PL 504.6
 (2) AND FBC RES P2804.6.1 (2)
 5. T & P RELIEF LINE SHALL DISCHARGE TO A POINT THAT IS
 READILY OBSEVABLE TO THE BUILDING OCCUPANTS PER FBC PL
 504.6 (7) AND FBC RES P2804.6.1 (7)
 6. T & P RELIEF LINE SHALL NOT BE TRAPPED PER FBC PL
 504.6 (8) AND FBC RES P2804.6.1 (8)
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-22 Cont ID  
Sent By gjohnson Date 2019-01-22 Time 17:21 Rev Time 0.00
Received By gjohnson Date 2019-01-22 Time 15:56 Sent To  
Notes
2019-01-22 17:41:391ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB
 AMEND TO FBC 107.3.5.3(11)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved