| Plan Review Stops For Permit 18101088 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2019-02-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-02-06 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-02-06 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2019-01-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2019-01-19 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-01-14 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2019-01-19 10:45:43 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | THE PENDING ITEMS FROM LAST REVIEW CONTINUE AS NOTED | | | BELOW: | | | | | | 1. VALUATION: THE VALUATION SHOWN ON THE APPLICATION | | | SHOULD BE A TOTAL AND NEEDS TO INCLUDE VALUE OF RELATED | | | SUB PERMITS. | | | | | | 2. THE TIE BEAM DIMENSIONS ARE NOT INCLUDED ON THE | | | LATEST SUBMITTED PLAN. ON THE INITIAL PLAN SUBMITTAL AN | | | 8" X 12" TIE BEAM WAS SHOWN BUT THERE WAS ALSO A DETAIL | | | FOR AN 8" X 8" BOND BEAM. PLEASE CLARIFY. | | | | | | 3. THE WINDOW SCHEDULE IDENTIFICATION "MARKS" DO NOT | | | MATCH THE IDENTIFACATION NUMBERS SHOWN ON THE OPENINGS | | | OF THE FLOOR PLAN. | | | | | | 4. PLEASE PROVIDE A CONNECTOR SCHEDULE FOR THE ROOF | | | TRUSS TO THE TIE BEAM. THE SCHEDULE NEEDS TO INCLUDE | | | THE SPECIFIC CONNECTORS TO BE USED AND NUMBER/SIZE OF | | | FASTENERS. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-12-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-12-20 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-12-20 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2018-12-20 14:52:33 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | 1. THE VALUATION OF THIS JOB APPEARS TO BE VERY LOW, AS | | | THE PLANS INCLUDE: | | | BUILDING: | | | BLOCK WALL(APPROX. 50') TO BE REPLACED. | | | ROOF & FLOOR FRAMING MEMBERS TO BE REPAIRED/REPLACED | | | (INCLUDING SHEATHING). | | | WINDOW/DOOR REPLACEMENT (IMPACT RESISTANT). | | | INTERIOR WALL & DOOR FRAMING TO BE REMOVED/REPLACED. | | | ELECTRIC: AS SHOWN ON PLANS (NO SUB-PERMIT). | | | PLUMBING: AS SHOWN ON PLANS (NO SUB-PERMIT). | | | | | | 2. THE BUILDING PLANS (PAGE A-2) ARE MISSING THE | | | DIMENSIONS OF THE FOOTINGS AND TIE-BEAMS. | | | | | | 3. THERE IS NO SCHEDULE FOR WINDOWS AND DOORS. | | | | | | NOTES: | | | | | | THERE WERE NO PRODUCT APPROVALS (WINDOWS/DOORS AND | | | ROOFING PRODUCTS) SUBMITTED WITH PLANS. | | | THERE IS A DEMO PERMIT THAT IS STILL OPEN. | | | THERE HAVE BEEN NO OTHER PERMITS APPLIED FOR (SUCH AS | | | MECHANICAL AND ROOFING). | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-11-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-11-13 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-11-13 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2018-11-13 16:21:19 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE REQUESTED INFORMATION/RESPONSES | | | (FOR EACH ITEM) FROM LAST REVIEW. | | | | | | FEEL FREE TO CONTACT ME WITH ANY QUESTIONS REGARDING | | | THIS REVIEW. | | | | | | PETER E. VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561 805 6673 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-10-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-10-29 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-10-29 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2018-10-29 17:09:38 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | | | THE EXISTING STRUCTURE DOES NOT APPEAR TO MATCH THE | | | DESCRIBED STRUCTURE ON PLANS. THE EXISTING STRUCTURE | | | APPEARS TO BE TWO STRUCTURES JOINED TOGETHER WITH THE | | | EAST HALF HAVING A SLOPED ROOF, A FRONT PORCH, & | | | SEVERAL WINDOWS. PLEASE PROVIDE MORE DETAILS ON PLAN | | | INCLUDING: | | | | | | 1. FBC EC R503.1.1 LOCATION AND SIZE OF WINDOW/DOOR | | | OPENINGS. | | | 2. FBC EC R503.1.1.1 PROVIDE REPLACEMENT FENESTRATION | | | DETAILS INCLUDING PRODUCT APPROVALS FOR NEW WINDOWS AND | | | DOORS. | | | 3. FBC EB 807.2 CONNECTION DETAILS FOR THE NEW WALL TO | | | EXISTING WALLS. | | | 4. FBC EB 807.2 DETAILS FOR THE ATTACHMENT OF | | | REPLACEMENT JOISTS. | | | 5. FBC EB 807.2 DETAILS FOR THE TIE DOWN ATTACHMENTS OF | | | NEW WALL TO EXISTING ROOF. | | | 6. FBC EB 807.2 DETAILS FOR THE NEW BLOCK WALL FOOTING. | | | (NOTES ON PLAN DO NOT MATCH/PROVIDE FOOTING DETAIL) | | | 7. FBC R 702. DETAILS FOR THE INTERIOR FRAMING: FURRING | | | & INSULATION OF NEW WALL. | | | 8. FBC EB 808.3 PROVIDE AN ELECTRIC SUB PERMIT. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2019-03-15 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-03-15 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-03-15 |
Time |
13:18 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-02-06 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-02-06 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-02-06 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2019-02-06 10:33:09 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. THE DRYER AND LAUNDRY LOAD IS NOT | | | INCLUDED, THE VALUE FOR THE RANGE IS NOT CODE | | | COMPLIANT, AND THERE IS CONFUSION ON THE HVAC SYSTEM - | | | PROVIDE CLARIFICATION. NEC 215.2, 220, 408.30; FBC RE | | | E3602.2 | | | 2. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN | | | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE | | | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 | | | 3. PROVIDE CLARIFICATION FOR HVAC. THE PANEL SCHEDULE | | | SHOWS 5 DIFFERENT UNITS, BUT THE LOAD CALCULATION | | | INCLUDES ONE CALCULATION FOR HEAT AT 65% DEMAND FACTOR, | | | WHICH IS TYPICALLY USED FOR ONE CENTRAL SYSTEM. WHICH | | | IS IT? LOAD CALCULATION SHOULD INCLUDE THE LARGER OF | | | THE AC OR HEAT LOADS, BUT NOT BOTH.WPB FBC 107.2.1; NEC | | | 220; FBC RE E3602.2 | | | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | 5. PROVIDE LOCATION OF ELECTRICAL PANEL AND SERVICE ON | | | PLAN. WPB FBC 107.2.1 | | | 6. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. | | | NEC 110.3, 110.9; FBC RE E3606.3 | | | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 8. CORRECT SYMBOLS ON PLAN TO MATCH LEGEND FOR SMOKE | | | ALARMS. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2019-01-23 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2019-01-23 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2019-01-23 |
Time |
14:30 |
Sent To |
I |
|
| Notes |
| 2019-01-23 15:20:29 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | | IS ADEQUATE. THE DRYER AND LAUNDRY LOAD IS NOT | | | INCLUDED, THE VALUE FOR THE RANGE IS NOT CODE | | | COMPLIANT, AND THERE IS CONFUSION ON THE HVAC SYSTEM - | | | PROVIDE CLARIFICATION. NEC 215.2, 220, 408.30; FBC RE | | | E3602.2 | | | 2. FEED TO INTERIOR PANEL IS REQUIRED TO HAVE AN | | | EQUIPMENT GROUNDING CONDUCTOR, SIZED PER CODE. PROVIDE | | | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 | | | 3. PROVIDE CLARIFICATION FOR HVAC. THE PANEL SCHEDULE | | | SHOWS 5 DIFFERENT UNITS, BUT THE LOAD CALCULATION | | | INCLUDES ONE CALCULATION FOR HEAT AT 65% DEMAND FACTOR, | | | WHICH IS TYPICALLY USED FOR ONE CENTRAL SYSTEM. WHICH | | | IS IT? LOAD CALCULATION SHOULD INCLUDE THE LARGER OF | | | THE AC OR HEAT LOADS, BUT NOT BOTH.WPB FBC 107.2.1; NEC | | | 220; FBC RE E3602.2 | | | 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | 5. PROVIDE LOCATION OF ELECTRICAL PANEL AND SERVICE ON | | | PLAN. WPB FBC 107.2.1 | | | 6. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. | | | NEC 110.3, 110.9; FBC RE E3606.3 | | | 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | | SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC | | | RE E3606.3 | | | 8. CORRECT SYMBOLS ON PLAN TO MATCH LEGEND FOR SMOKE | | | ALARMS. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-03-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-03-12 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2019-03-13 15:27:19 | RESUB ROUTED TO JPEARSON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2019-02-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2019-02-16 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2019-01-25 |
Time |
15:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2019-01-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2019-01-04 |
Time |
12:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-12-20 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-12-20 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-12-18 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2018-12-19 14:32:06 | RESUB ROUTED TO PVALENTI |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-11-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-11-13 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-11-09 |
Time |
14:45 |
Sent To |
I |
|
| Notes |
| 2018-11-13 14:45:56 | RESUB ROUTED TO PVALENTI |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-10-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2018-10-29 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2018-10-23 |
Time |
15:43 |
Sent To |
I |
|
| Notes |
| 2018-10-24 15:43:25 | BLDG MISC 1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-02-05 |
|
|
Cont ID |
|
| Sent By |
jesmith |
Date |
2019-02-05 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
jesmith |
Date |
2019-02-05 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2019-02-05 14:54:30 | | | | APPROVED | | | PLUMBING PROVISO | | | 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S | | | APPROVAL | | | 2. WASHER AND SINK SHALL CONNECT DOWNSTREAM OF BATHROOM | | | PER FBC PL 912.1 AND FBC RES P3108.1 | | | 3. PROVIDE THERMAL EXPANSION CONTROL DEVICE FOR COLD | | | WATER SUPPLY TO TANK TYPE WATER HEATER PER FBC PL 607.3 | | | AND FBC RES P2903.4.2 | | | 4. T & P RELIEF LINE SHALL DISCHARGE THROUGH AN AIR GAP | | | IN THE SAME ROOM AS THE WATER HEATER PER FBC PL 504.6 | | | (2) AND FBC RES P2804.6.1 (2) | | | 5. T & P RELIEF LINE SHALL DISCHARGE TO A POINT THAT IS | | | READILY OBSEVABLE TO THE BUILDING OCCUPANTS PER FBC PL | | | 504.6 (7) AND FBC RES P2804.6.1 (7) | | | 6. T & P RELIEF LINE SHALL NOT BE TRAPPED PER FBC PL | | | 504.6 (8) AND FBC RES P2804.6.1 (8) | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2019-01-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2019-01-22 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2019-01-22 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2019-01-22 17:41:39 | 1ST REVIEW: | | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | | EDITION | | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | | EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE SANITARY ISOMETRIC DRAWING. PER WPB | | | AMEND TO FBC 107.3.5.3(11) | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|