Plan Review Details - Permit 18101052
Plan Review Stops For Permit 18101052
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-01-28 Cont ID  
Sent By pleduc Date 2020-01-28 Time 13:27 Rev Time 0.00
Received By cthroop Date 2020-01-28 Time 11:40 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-12-16 Cont ID  
Sent By cthroop Date 2019-12-16 Time 14:43 Rev Time 0.00
Received By cthroop Date 2019-12-16 Time 09:34 Sent To FIRE
Notes
2019-12-16 14:44:28PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN SHEETS A9.11 & E4.02 MISSING DESIGNERS
 SIGNATURE AND SEAL.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-12-10 Cont ID  
Sent By cthroop Date 2019-12-10 Time 14:47 Rev Time 0.00
Received By cthroop Date 2019-12-10 Time 14:19 Sent To P
Notes
2019-12-10 14:58:56PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ORGANIZE ALL PLANS INTO TWO COMPLETE COLLATED SETS
 FOR REVIEW PER FBC SEC. 107.2.1 WPB. REMOVE ANY SHEETS
 NOT APPLCABLE AND MARK VOID.
  
 2. MULTIPLE PLAN SHEETS MISSING DESIGNERS SIGNATURE AND
 SEAL.
 FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT,
 INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
  
 NO FURTHER REVIEW PERFORMED AT THIS TIME.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-18 Cont ID  
Sent By cthroop Date 2018-12-18 Time 08:10 Rev Time 0.00
Received By cthroop Date 2018-12-17 Time 16:35 Sent To  
Notes
2018-12-18 08:23:02BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS SUBMITTED FOR REVIEW FROM A DESIGN
 PROFESSIONAL SHALL BEAR THE ORIGINAL SIGNATURE AND SEAL
 OF THE DESIGN PROFESSIONAL.
 THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES&
 61G1 FLORIDA ADMINISTRATIVE CODE.
  
 2. PROVIDE SITE PLAN. IDENTIFY LOCATION OF GENERATOR
 EXHAUST.
  
 3. PROVIDE APPROVAL LETTER FROM PALM BEACH COUNTY
 ENVIROMENTAL RESOURCES MANAGEMENT FOR THE INSTALLATION
 OF THE FUEL TANK.
  
 4. TANK PLANS SUBMITTAL INDICATES A 660 GAL. FUEL TANK.
 PLAN PAGE P5.01 INDICATES A 600 GAL FUEL TANK. PLEASE
 CLARIFY.
  
 5. PROVIDE DETAIL AND/OR UL DESIGN FOR ANY PIPES
 PENETRATING A RATED WALL ASSEMBLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-01-28 Cont ID  
Sent By jleahy Date 2020-01-28 Time 13:39 Rev Time 0.00
Received By jleahy Date 2020-01-28 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-12-16 Cont ID  
Sent By jleahy Date 2019-12-16 Time 08:32 Rev Time 0.00
Received By jleahy Date 2019-12-16 Time 08:32 Sent To B
Notes
2019-12-16 08:32:55SEE COMMENTS FROM LAST REVIEW JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-11-26 Cont ID  
Sent By jleahy Date 2019-11-26 Time 17:17 Rev Time 0.00
Received By jleahy Date 2019-11-22 Time 17:17 Sent To FIRE
Notes
2019-11-22 17:21:51FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE HAS BEEN ADDRESSED.
  
 2) RISER DIAGRAM SHOWING WIRE SIZES AND DISCONNECT
 SIZES OCP SIZES.
  
 3) THE DRAWINGS THAT ARE HERE IONLY HAVE ONE SET OF
 INCOMPLETE PLANS, PLEASE ORGANIZE THE DRAWINGS FOR
 ELECTRICAL INTO ONE SET SO I DON'T HAVE TO GO THROUGH
 ALL THE DRAWINGS TO FIND THE ELECTRICAL ONES.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 17:04 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 17:04 Sent To  
Notes
2018-11-09 17:04:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS PERSON MUST BE A LICENSED DESIGN
 PROFESSIONAL. PROVIDE CORRECTION. WPB FBC 107.1, 107.2;
 FS 471, 481
 3. PROVIDE RISER DIAGRAM SHOWING ALL DETAILS OF SERVICE
 AND EMERGENCY SYSTEM. NEC 215.5
 4. PROVIDE LOAD CALCULATION FOR GENERATOR TO CONFIRM
 SIZING OF GENERATOR AND TRANSFER SWITCH IS SUFFICIENT.
 NEC 701.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2020-01-24 Cont ID  
Sent By sathomas Date 2020-01-24 Time 00:00 Rev Time 0.00
Received By pleduc Date 2020-01-21 Time 00:00 Sent To B
Notes
2020-01-21 15:40:48PREVIOUS FIRE COMMENTS NOT ADDRESSED IN THIS SUBMITTAL
 PACKET.
  
 SLT 7805

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2019-12-19 Cont ID  
Sent By pleduc Date 2019-12-19 Time   Rev Time 0.00
Received By pleduc Date 2019-12-19 Time 10:54 Sent To Z
Notes
2019-12-19 11:00:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET M2.04 - THERE IS INDICATIONS OF FLAMBAR AND
 PENETRATIONS THROUGH RATED WALLS WITH NO DAMPERS.
  
 PLEAE PROVIDE MANUFACTURES SPEC SHEETS AND FIRE WALL
 PENETRATION DETAILS PER NFPA COMPLIANCE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2019-12-03 Cont ID  
Sent By pleduc Date 2019-12-03 Time   Rev Time 0.00
Received By pleduc Date 2019-12-03 Time 11:24 Sent To B
Notes
2019-12-03 11:26:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS ARE UNORGANIZED AND CAN NOT BE
 DETERMINED NEW VS OLD.
  
 PLEASE REVIEW AND CORRECT AND BE SURE TO MARK VOID ON
 OLD SET AND ORGANIZE THE NEW SETS.
  
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By pleduc Date 2018-12-14 Time   Rev Time 0.00
Received By pleduc Date 2018-12-14 Time 13:30 Sent To B
Notes
2018-12-14 13:43:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA
 CODES.
  
 THE INSTALLATION SHALL COMPLY WITH :
  
 NFPA? 37 STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES 2015
 EDITION
  
 NFPA? 110 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS 2013 EDITION
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE .
  
  
  
 2) THERE ARE NO INDICATIONS OF WHERE THE EXHAUST OF THE
 GENERATOR IS BEING LOCATED .
  
 PLEASE REVIEW AND PROVIDE IN COMPLAINCE WITH ABOVE
 NOTED CODES.
  
  
  
  
 3) THERE ARE NO INDICATIONS OF ANY FIRE RATED LISTINGS
 FOR ANY BREECHES TO THE FIRE WALLS.
  
 PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR EACH FIRE
 WALL BREECHED BY ANY PIECE OF EQUIPMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-01-28 Cont ID  
Sent By jleahy Date 2020-01-28 Time 13:39 Rev Time 0.00
Received By jleahy Date 2020-01-13 Time 13:47 Sent To  
Notes
2020-01-14 13:47:33RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-01-07 Cont ID  
Sent By cpuell Date 2020-01-07 Time 16:55 Rev Time 0.00
Received By cpuell Date 2019-12-13 Time 07:57 Sent To  
Notes
2020-01-07 15:18:33ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/7/2020 EL
2019-12-16 07:57:45ROUTED TO JLEAHY PER SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-12-10 Cont ID  
Sent By lcrespo Date 2019-12-10 Time 18:28 Rev Time 0.00
Received By lcrespo Date 2019-11-22 Time 16:28 Sent To  
Notes
2019-11-26 07:26:48TO JL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-18 Cont ID  
Sent By cthroop Date 2018-12-18 Time 08:25 Rev Time 0.00
Received By cthroop Date 2018-10-23 Time 15:46 Sent To  
Notes
2018-11-07 16:08:21ROUTED FROM ZONING TO LM 11/8/18
2018-10-24 15:46:37ROUTED TO ZONING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-01-24 Cont ID  
Sent By ccole Date 2020-01-24 Time 13:47 Rev Time 0.00
Received By ccole Date 2020-01-16 Time 12:21 Sent To  
Notes
2020-01-21 14:15:13 
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-12-17 Cont ID  
Sent By ccole Date 2019-12-17 Time 12:49 Rev Time 0.00
Received By ccole Date 2019-12-17 Time 10:15 Sent To P
Notes
2019-12-17 13:01:322ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18101052
 12/17/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.04: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 FLAMEBAR HAZARDOUS EXHAUST DUCT.THE SPECS SHALL SHOW
 HOW THE DUCT IS TO BE ASSEMBLED, SUPPORTED, AND
 FIRESTOPPED AT RATED WALL PENETRATIONS- SECTION 107.2.1
 WPB AND SECTION 510.9 FBC M.
  
 2) M2.04: SEE NOTE #8 AND SUBMIT TWO COPIES OF PLAN
 SHEET M7.03 SHOWING THE EXHAUST THIMBLE PENETRATION
 DETAIL- SECTION 107.2.1 WPB.
  
 3) M2.04: PROVIDE THE SEQUENCE OF OPERATION FOR EXHAUST
 FANS GEF-4.5 & GEF-4.6- SECTION 510.2 FBC M.
  
 4) M2.04: PROVIDE A MIAMI-DADE NOA OR FL. PRODUCT
 APPROVAL FOR THE RUSHKIN LOUVERS- RULE 9N-3 FAC. NOTE:
 THE LOUVERS MAY BE A DEFFERRED SUBMITTAL IF REQUESTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-11-27 Cont ID  
Sent By ccole Date 2019-11-27 Time 12:39 Rev Time 0.00
Received By ccole Date 2019-11-27 Time 11:48 Sent To FIRE
Notes
2019-11-27 13:04:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101052
 11/27/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.04: THE GENERATOR WAS NOT REVIEWED UNDER
 THE MAIN PERMIT PLAN REVISIONS. REVIEW OF THE SHEET
 INDICATES THESE ISSUES:
  
 A) THE HAZARDOUS EXHAUST DUCT FROM THE TANK ROOM SHALL
 RUN INDEPENDENTLY FROM THE TANK ROOM TO THE EXTERIOR OF
 THE BUILDING. IT IS NOT PERMITTED TO BE CONNECTED TO
 THE GENERATOR RADIATOR EXHAUST- SECTIONS 510.2 &
 510.6.7 FBC M.
  
 B) THE FIRE DAMPER AT THE HAZARDOUS EXHAUST DUCT
 PENETRATION OF THE FIRE-RATED TANK/GENERATOR ROOM WALL
 IS NOT ALLOWED- SECTION 510.7.1 FBC M. THE DUCT SHALL
 BE PROTECTED WITH A FIRE-RATED ENCLOSURE FROM THE POINT
 OF PENETRATION OF THE RATED WALL TO THE DISCHARGE
 OUTLET AT THE EXTERIOR WALL- SECTION 510.7.3 FBC M.
  
 2) SUBMIT A CORRECTED M2.04 PLAN SHEET AND ORGANIZE ALL
 PLAN SHEETS INTO TWO COMPLETE COLLATED SETS FOR REVIEW-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By ccole Date 2018-12-11 Time 12:53 Rev Time 0.00
Received By ccole Date 2018-12-11 Time 09:09 Sent To FIRE
Notes
2018-12-11 13:22:261ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18101052
 12/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS,
 AND PROVIDE AN EXHAUST PIPE DRAWING SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL
 COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, AND
 ANY CONTRACTOR SUPPLIED PIPING.
  
 2) PROVIDE A BACKPRESSURE CALCULATION FOR THE EXHAUST
 PIPING SYSTEM AND THE SILENCER AS RECOMMENDED BY
 KOHLER. ACCORDING TO THE KOHLER SPECIFICATIONS, THE
 CALCULATION SHALL BE PERFORMED BY AN AUTHORIZED
 DISTRIBUTOR/DEALER OF THE FLEX EXHAUST PIPING. AND
 SHALL INCLUDE THE FLEX, THE SILENCER, AND ANY
 CONTRACTOR SUPPLIED PIPING.
  
 3) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND
 THE FUEL TANK- SECTION 304.1 FBC M.
  
 4) SHEET E2.04 & E4.02: THE PLANS SHOW A SEPARATE FUEL
 TANK ROOM THAT THE APPROVED PLAN SHEET M2.04 UNDER
 PERMIT #16061443 DOES NOT SHOW. PLEASE REVISE ALL PLANS
 FROM THE APPROVED MASTER SET THAT ARE AFFECTED BY THIS
 CHANGE AND SUBMIT THEM TO THE BUILDING DEPT. FOR REVIEW
 WITH A REVISION APPLICATION.
  
 5) PROVIDE A MECHANICAL PLAN INDICATING HOW THE NEW
 TANK ROOM WILL BE VENTILATED- SECTION 415.9.1.5 FBC B,
 AND SECTION 510 FBC M.
  
 6) PROVIDE A LIST OF STANDBY AND EMERGENCY POWER LOADS
 THAT THE GENERATOR WILL POWER- SECTIONS 403.4.8.3 &
 403.4.8.4 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-12-17 Cont ID  
Sent By lcrespo Date 2019-12-17 Time 16:55 Rev Time 0.00
Received By lcrespo Date 2019-12-17 Time 16:55 Sent To  
Notes
2019-12-17 16:56:0512/17/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-12-10 Cont ID  
Sent By lcrespo Date 2019-12-10 Time 18:20 Rev Time 0.00
Received By lcrespo Date 2019-12-10 Time 18:20 Sent To  
Notes
2019-12-10 18:30:1812/10/19 REVIEWED FOR CODE COMPLIANCE AND NFPA 30 (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-06 Cont ID  
Sent By tklarge Date 2018-12-06 Time 11:56 Rev Time 0.00
Received By tklarge Date 2018-12-04 Time 12:41 Sent To  
Notes
2018-12-06 09:15:291) THE GENERATOR SPECIFICATIONS NOTE THAT THE GENERATOR
 OFFERS A UL 2200 LISTING. SUBMIT A COPY OF THE
 CERTIFICATE OF COMPLIANCE SHOWING THE UL 2200 LISTING.
 2017 FBC-MECH. SEC.915.
 2) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA 37
 PER 2017 FBC-MECH. SEC. 915. I COULD NOT FIND THIS
 INFORMATION IN THE SPECIFICATIONS.
 3) THE FUEL TANK INSTALLATION SHALL BE APPROVED BY THE
 PALM BEACH COUNTY OFFICE OF ENVIRONMENTAL RESOURCE
 MANAGEMENT PER PALM BEACH COUNTY ORDINANCE 2015-008.
 SUBMIT DOCUMENTATION FROM ERM THAT THIS INSTALLATION
 HAS BEEN APPROVED.
 4) THE SUBMITTED PLANS SHALL BEAR THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL OF RECORD IN ACCORDANCE
 WITH THE FL. ADMIN. CODE RULE 61G15-23.001.
 5) SUBMIT SAFETY DATA SHEETS FOR THE FUEL OIL TO BE
 USED. WPB AMEND. TO FBC SEC. 107.2.1.
 6) INDICATE THE CLASS OF THE FUEL ON THE PLANS IN
 ACCORDANCE WITH NFPA 30 SEC. 4.3.
 7) SPILL CONTROL, CONTAINMENT AND DRAINAGE MAY BE
 REQUIRED FOR THE FUEL TANK DEPENDING ON THE CLASS OF
 LIQUID OF THE FUEL. NFPA 30 SEC. 9.13.
 8) IN ADDITION TO THE TANK PLANS THAT HAVE BEEN
 SUBMITTED, SUPPLY ANY ADDITIONAL MANUFACTURER'S
 SPECIFICATIONS FOR THE FUEL TANK.WPB AMEND. TO FBC SEC.
 107.2.1.
 9) THE SUBMITTED TANK PLANS NOTE THE TANK AS 660
 GALLONS BUT THE PLANS NOTE THE TANK AS 600 GALLONS.
 CLARIFY.
 10) THE FUEL TANK VENTS SHALL BE 5 FEET FROM BUILDING
 OPENINGS AND 15 FEET FROM POWERED VENTILATION AIR
 INTAKES PER NFPA 30-12 SEC.19.5.3.2.
 11) A SIGN OR MARKING THAT MEETS THE REQUIREMENTS OF
 NFPA 704, OR ANOTHER APPROVED SYSTEM, SHALL BE APPLIED
 TO STORAGE TANKS CONTAINING LIQUIDS PER NFPA 30
 SEC.21.7.2.1.
 12) EMERGENCY RELIEF VENTING IS REQUIRED FOR THE FUEL
 TANK PER NFPA 30 SEC.22.7.
 13) SHOW ON THE PLAN HOW THE VENT PIPES FROM THE FUEL
 TANK WILL BE PROTECTED WHERE PASSING THROUGH THE WALLS
 OF THE STRUCTURE.
 14) THE FILL PORT FOR THE FUEL TANK SHALL BE PROVIDED
 ON AN EXTERIOR WALL OF THE ROOM OR STRUCTURE ENCLOSING
 THE TANK AT A POINT AT LEAST 24 INCHES FROM ANY
 BUILDING OPENING AT THE SAME OR LOWER LEVEL PER NFPA
 37-15 SEC. 6.6.3.3. SHOW THE LOCATION OF THE FILL PORT
 ON THE PLANS.
 15) THE FUEL TANK SHALL BE LOCATED IN A ROOM WITH A
 FIRE- RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE
 THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.1.2 , THE REQUIERED FIRE-RESISTANCE
 RATING SHALL BE REDUCED TO ONE HOUR. 2017 FBC-BUILDING
 SEC.403.4.8.2.
 16) THE PLANS SHOW THE FUEL TANK LOCATED IN A SEPARATE
 ROOM THAT IS NOT SHOWN ON THE ORIGINAL PLANS. A
 REVISION SHALL BE SUBMITTED SHOWING THE FIRE RATING OF
 THE ROOM AND DOORS IN WHICH THE FUEL TANK IS LOCATED.
 WPB AMEND. TO FBC SEC. 107.2.1.
 17) A PLUMBING REVISION SHALL BE SUBMITTED FOR SHT. P
 5.01 AS THE FUEL PIPING WAS NOT SHOWN ON THE ORIGINAL
 PLANS.
 18) SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR
 THE PRYCO FUEL DELIVERY CONTROL STATION FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-07 Cont ID  
Sent By elevesqu Date 2020-01-07 Time 15:17 Rev Time 0.00
Received By elevesqu Date 2020-01-07 Time 15:17 Sent To  
Notes
2020-01-07 15:17:52PROVISO: AN AMENDMENT TO THE SITE PLAN APPROVAL
 REFLECTING PARKING CHANGES SHALL BE SUBMITTED TO
 PLANNING AND ZONING PRIOR TO ISSUANCE OF A CO.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-07 Cont ID  
Sent By elevesqu Date 2018-11-07 Time 16:07 Rev Time 0.00
Received By elevesqu Date 2018-11-07 Time 16:01 Sent To  
Notes
2018-11-07 16:02:24PROVISO: AN AMENDMENT TO THE SITE PLAN APPROVAL
 REFLECTING PARKING CHANGES SHALL BE SUBMITTED TO
 PLANNING AND ZONING PRIOR TO ISSUANCE OF A CO.