| Plan Review Stops For Permit 18101052 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-01-28 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-01-28 |
Time |
11:40 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2019-12-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-16 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-16 |
Time |
09:34 |
Sent To |
FIRE |
|
| Notes |
| 2019-12-16 14:44:28 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PLAN SHEETS A9.11 & E4.02 MISSING DESIGNERS | | | SIGNATURE AND SEAL. | | | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, | | | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER | | | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE | | | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR | | | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA | | | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED | | | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR | | | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA | | | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2019-12-10 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2019-12-10 |
Time |
14:19 |
Sent To |
P |
|
| Notes |
| 2019-12-10 14:58:56 | PLAN REVIEW - BUILDING | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ORGANIZE ALL PLANS INTO TWO COMPLETE COLLATED SETS | | | FOR REVIEW PER FBC SEC. 107.2.1 WPB. REMOVE ANY SHEETS | | | NOT APPLCABLE AND MARK VOID. | | | | | | 2. MULTIPLE PLAN SHEETS MISSING DESIGNERS SIGNATURE AND | | | SEAL. | | | FBC 107.1 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, | | | INTERIOR DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER | | | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE | | | REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR | | | DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA | | | STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED | | | FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR | | | ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA | | | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | | OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. | | | | | | NO FURTHER REVIEW PERFORMED AT THIS TIME. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-18 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-12-17 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2018-12-18 08:23:02 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DOCUMENTS SUBMITTED FOR REVIEW FROM A DESIGN | | | PROFESSIONAL SHALL BEAR THE ORIGINAL SIGNATURE AND SEAL | | | OF THE DESIGN PROFESSIONAL. | | | THE CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY | | | CHAPTER 471, FLORIDA STATUTES& 61G15 FLORIDA | | | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES& | | | 61G1 FLORIDA ADMINISTRATIVE CODE. | | | | | | 2. PROVIDE SITE PLAN. IDENTIFY LOCATION OF GENERATOR | | | EXHAUST. | | | | | | 3. PROVIDE APPROVAL LETTER FROM PALM BEACH COUNTY | | | ENVIROMENTAL RESOURCES MANAGEMENT FOR THE INSTALLATION | | | OF THE FUEL TANK. | | | | | | 4. TANK PLANS SUBMITTAL INDICATES A 660 GAL. FUEL TANK. | | | PLAN PAGE P5.01 INDICATES A 600 GAL FUEL TANK. PLEASE | | | CLARIFY. | | | | | | 5. PROVIDE DETAIL AND/OR UL DESIGN FOR ANY PIPES | | | PENETRATING A RATED WALL ASSEMBLY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-28 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-28 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2019-12-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-12-16 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-12-16 |
Time |
08:32 |
Sent To |
B |
|
| Notes |
| 2019-12-16 08:32:55 | SEE COMMENTS FROM LAST REVIEW JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2019-11-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2019-11-26 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2019-11-22 |
Time |
17:17 |
Sent To |
FIRE |
|
| Notes |
| 2019-11-22 17:21:51 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) VALUE HAS BEEN ADDRESSED. | | | | | | 2) RISER DIAGRAM SHOWING WIRE SIZES AND DISCONNECT | | | SIZES OCP SIZES. | | | | | | 3) THE DRAWINGS THAT ARE HERE IONLY HAVE ONE SET OF | | | INCOMPLETE PLANS, PLEASE ORGANIZE THE DRAWINGS FOR | | | ELECTRICAL INTO ONE SET SO I DON'T HAVE TO GO THROUGH | | | ALL THE DRAWINGS TO FIND THE ELECTRICAL ONES. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-11-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-11-09 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-11-09 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2018-11-09 17:04:45 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | | 2. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. THIS PERSON MUST BE A LICENSED DESIGN | | | PROFESSIONAL. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; | | | FS 471, 481 | | | 3. PROVIDE RISER DIAGRAM SHOWING ALL DETAILS OF SERVICE | | | AND EMERGENCY SYSTEM. NEC 215.5 | | | 4. PROVIDE LOAD CALCULATION FOR GENERATOR TO CONFIRM | | | SIZING OF GENERATOR AND TRANSFER SWITCH IS SUFFICIENT. | | | NEC 701.4 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | | SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2020-01-24 |
|
|
Cont ID |
|
| Sent By |
sathomas |
Date |
2020-01-24 |
Time |
00:00 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-01-21 |
Time |
00:00 |
Sent To |
B |
|
| Notes |
| 2020-01-21 15:40:48 | PREVIOUS FIRE COMMENTS NOT ADDRESSED IN THIS SUBMITTAL | | | PACKET. | | | | | | SLT 7805 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2019-12-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-19 |
Time |
10:54 |
Sent To |
Z |
|
| Notes |
| 2019-12-19 11:00:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET M2.04 - THERE IS INDICATIONS OF FLAMBAR AND | | | PENETRATIONS THROUGH RATED WALLS WITH NO DAMPERS. | | | | | | PLEAE PROVIDE MANUFACTURES SPEC SHEETS AND FIRE WALL | | | PENETRATION DETAILS PER NFPA COMPLIANCE. | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2019-12-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2019-12-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2019-12-03 |
Time |
11:24 |
Sent To |
B |
|
| Notes |
| 2019-12-03 11:26:31 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE SUBMITTED PLANS ARE UNORGANIZED AND CAN NOT BE | | | DETERMINED NEW VS OLD. | | | | | | PLEASE REVIEW AND CORRECT AND BE SURE TO MARK VOID ON | | | OLD SET AND ORGANIZE THE NEW SETS. | | | | | | | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-12-14 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-12-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-12-14 |
Time |
13:30 |
Sent To |
B |
|
| Notes |
| 2018-12-14 13:43:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY NFPA | | | CODES. | | | | | | THE INSTALLATION SHALL COMPLY WITH : | | | | | | NFPA? 37 STANDARD FOR THE INSTALLATION AND USE OF | | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES 2015 | | | EDITION | | | | | | NFPA? 110 STANDARD FOR EMERGENCY AND STANDBY POWER | | | SYSTEMS 2013 EDITION | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE . | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF WHERE THE EXHAUST OF THE | | | GENERATOR IS BEING LOCATED . | | | | | | PLEASE REVIEW AND PROVIDE IN COMPLAINCE WITH ABOVE | | | NOTED CODES. | | | | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF ANY FIRE RATED LISTINGS | | | FOR ANY BREECHES TO THE FIRE WALLS. | | | | | | PLEASE PROVIDE ALL APPLICABLE LISTINGS FOR EACH FIRE | | | WALL BREECHED BY ANY PIECE OF EQUIPMENT. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-01-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-01-28 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-01-13 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2020-01-14 13:47:33 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-01-07 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-01-07 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2019-12-13 |
Time |
07:57 |
Sent To |
|
|
| Notes |
| 2020-01-07 15:18:33 | ROUTED FROM ZONING TO PERMIT LIBRARIAN 1/7/2020 EL | | 2019-12-16 07:57:45 | ROUTED TO JLEAHY PER SHILL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-12-10 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-11-22 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2019-11-26 07:26:48 | TO JL DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-12-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-12-18 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-10-23 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2018-11-07 16:08:21 | ROUTED FROM ZONING TO LM 11/8/18 | | 2018-10-24 15:46:37 | ROUTED TO ZONING INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2020-01-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-24 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-16 |
Time |
12:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-12-17 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-12-17 |
Time |
10:15 |
Sent To |
P |
|
| Notes |
| 2019-12-17 13:01:32 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #18101052 | | | 12/17/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.04: PLEASE SUBMIT MANUFACTURER'S | | | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE | | | FLAMEBAR HAZARDOUS EXHAUST DUCT.THE SPECS SHALL SHOW | | | HOW THE DUCT IS TO BE ASSEMBLED, SUPPORTED, AND | | | FIRESTOPPED AT RATED WALL PENETRATIONS- SECTION 107.2.1 | | | WPB AND SECTION 510.9 FBC M. | | | | | | 2) M2.04: SEE NOTE #8 AND SUBMIT TWO COPIES OF PLAN | | | SHEET M7.03 SHOWING THE EXHAUST THIMBLE PENETRATION | | | DETAIL- SECTION 107.2.1 WPB. | | | | | | 3) M2.04: PROVIDE THE SEQUENCE OF OPERATION FOR EXHAUST | | | FANS GEF-4.5 & GEF-4.6- SECTION 510.2 FBC M. | | | | | | 4) M2.04: PROVIDE A MIAMI-DADE NOA OR FL. PRODUCT | | | APPROVAL FOR THE RUSHKIN LOUVERS- RULE 9N-3 FAC. NOTE: | | | THE LOUVERS MAY BE A DEFFERRED SUBMITTAL IF REQUESTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2019-11-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2019-11-27 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2019-11-27 |
Time |
11:48 |
Sent To |
FIRE |
|
| Notes |
| 2019-11-27 13:04:19 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18101052 | | | 11/27/2019 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.04: THE GENERATOR WAS NOT REVIEWED UNDER | | | THE MAIN PERMIT PLAN REVISIONS. REVIEW OF THE SHEET | | | INDICATES THESE ISSUES: | | | | | | A) THE HAZARDOUS EXHAUST DUCT FROM THE TANK ROOM SHALL | | | RUN INDEPENDENTLY FROM THE TANK ROOM TO THE EXTERIOR OF | | | THE BUILDING. IT IS NOT PERMITTED TO BE CONNECTED TO | | | THE GENERATOR RADIATOR EXHAUST- SECTIONS 510.2 & | | | 510.6.7 FBC M. | | | | | | B) THE FIRE DAMPER AT THE HAZARDOUS EXHAUST DUCT | | | PENETRATION OF THE FIRE-RATED TANK/GENERATOR ROOM WALL | | | IS NOT ALLOWED- SECTION 510.7.1 FBC M. THE DUCT SHALL | | | BE PROTECTED WITH A FIRE-RATED ENCLOSURE FROM THE POINT | | | OF PENETRATION OF THE RATED WALL TO THE DISCHARGE | | | OUTLET AT THE EXTERIOR WALL- SECTION 510.7.3 FBC M. | | | | | | 2) SUBMIT A CORRECTED M2.04 PLAN SHEET AND ORGANIZE ALL | | | PLAN SHEETS INTO TWO COMPLETE COLLATED SETS FOR REVIEW- | | | SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-12-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-12-11 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-12-11 |
Time |
09:09 |
Sent To |
FIRE |
|
| Notes |
| 2018-12-11 13:22:26 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18101052 | | | 12/11/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS, | | | AND PROVIDE AN EXHAUST PIPE DRAWING SHOWING THE TOTAL | | | SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL | | | COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, AND | | | ANY CONTRACTOR SUPPLIED PIPING. | | | | | | 2) PROVIDE A BACKPRESSURE CALCULATION FOR THE EXHAUST | | | PIPING SYSTEM AND THE SILENCER AS RECOMMENDED BY | | | KOHLER. ACCORDING TO THE KOHLER SPECIFICATIONS, THE | | | CALCULATION SHALL BE PERFORMED BY AN AUTHORIZED | | | DISTRIBUTOR/DEALER OF THE FLEX EXHAUST PIPING. AND | | | SHALL INCLUDE THE FLEX, THE SILENCER, AND ANY | | | CONTRACTOR SUPPLIED PIPING. | | | | | | 3) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND | | | THE FUEL TANK- SECTION 304.1 FBC M. | | | | | | 4) SHEET E2.04 & E4.02: THE PLANS SHOW A SEPARATE FUEL | | | TANK ROOM THAT THE APPROVED PLAN SHEET M2.04 UNDER | | | PERMIT #16061443 DOES NOT SHOW. PLEASE REVISE ALL PLANS | | | FROM THE APPROVED MASTER SET THAT ARE AFFECTED BY THIS | | | CHANGE AND SUBMIT THEM TO THE BUILDING DEPT. FOR REVIEW | | | WITH A REVISION APPLICATION. | | | | | | 5) PROVIDE A MECHANICAL PLAN INDICATING HOW THE NEW | | | TANK ROOM WILL BE VENTILATED- SECTION 415.9.1.5 FBC B, | | | AND SECTION 510 FBC M. | | | | | | 6) PROVIDE A LIST OF STANDBY AND EMERGENCY POWER LOADS | | | THAT THE GENERATOR WILL POWER- SECTIONS 403.4.8.3 & | | | 403.4.8.4 FBC B. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2019-12-17 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-12-17 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-12-17 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2019-12-17 16:56:05 | 12/17/19 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2019-12-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2019-12-10 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2019-12-10 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2019-12-10 18:30:18 | 12/10/19 REVIEWED FOR CODE COMPLIANCE AND NFPA 30 (GAS) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-12-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-12-06 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-12-04 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2018-12-06 09:15:29 | 1) THE GENERATOR SPECIFICATIONS NOTE THAT THE GENERATOR | | | OFFERS A UL 2200 LISTING. SUBMIT A COPY OF THE | | | CERTIFICATE OF COMPLIANCE SHOWING THE UL 2200 LISTING. | | | 2017 FBC-MECH. SEC.915. | | | 2) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA 37 | | | PER 2017 FBC-MECH. SEC. 915. I COULD NOT FIND THIS | | | INFORMATION IN THE SPECIFICATIONS. | | | 3) THE FUEL TANK INSTALLATION SHALL BE APPROVED BY THE | | | PALM BEACH COUNTY OFFICE OF ENVIRONMENTAL RESOURCE | | | MANAGEMENT PER PALM BEACH COUNTY ORDINANCE 2015-008. | | | SUBMIT DOCUMENTATION FROM ERM THAT THIS INSTALLATION | | | HAS BEEN APPROVED. | | | 4) THE SUBMITTED PLANS SHALL BEAR THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL OF RECORD IN ACCORDANCE | | | WITH THE FL. ADMIN. CODE RULE 61G15-23.001. | | | 5) SUBMIT SAFETY DATA SHEETS FOR THE FUEL OIL TO BE | | | USED. WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) INDICATE THE CLASS OF THE FUEL ON THE PLANS IN | | | ACCORDANCE WITH NFPA 30 SEC. 4.3. | | | 7) SPILL CONTROL, CONTAINMENT AND DRAINAGE MAY BE | | | REQUIRED FOR THE FUEL TANK DEPENDING ON THE CLASS OF | | | LIQUID OF THE FUEL. NFPA 30 SEC. 9.13. | | | 8) IN ADDITION TO THE TANK PLANS THAT HAVE BEEN | | | SUBMITTED, SUPPLY ANY ADDITIONAL MANUFACTURER'S | | | SPECIFICATIONS FOR THE FUEL TANK.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 9) THE SUBMITTED TANK PLANS NOTE THE TANK AS 660 | | | GALLONS BUT THE PLANS NOTE THE TANK AS 600 GALLONS. | | | CLARIFY. | | | 10) THE FUEL TANK VENTS SHALL BE 5 FEET FROM BUILDING | | | OPENINGS AND 15 FEET FROM POWERED VENTILATION AIR | | | INTAKES PER NFPA 30-12 SEC.19.5.3.2. | | | 11) A SIGN OR MARKING THAT MEETS THE REQUIREMENTS OF | | | NFPA 704, OR ANOTHER APPROVED SYSTEM, SHALL BE APPLIED | | | TO STORAGE TANKS CONTAINING LIQUIDS PER NFPA 30 | | | SEC.21.7.2.1. | | | 12) EMERGENCY RELIEF VENTING IS REQUIRED FOR THE FUEL | | | TANK PER NFPA 30 SEC.22.7. | | | 13) SHOW ON THE PLAN HOW THE VENT PIPES FROM THE FUEL | | | TANK WILL BE PROTECTED WHERE PASSING THROUGH THE WALLS | | | OF THE STRUCTURE. | | | 14) THE FILL PORT FOR THE FUEL TANK SHALL BE PROVIDED | | | ON AN EXTERIOR WALL OF THE ROOM OR STRUCTURE ENCLOSING | | | THE TANK AT A POINT AT LEAST 24 INCHES FROM ANY | | | BUILDING OPENING AT THE SAME OR LOWER LEVEL PER NFPA | | | 37-15 SEC. 6.6.3.3. SHOW THE LOCATION OF THE FILL PORT | | | ON THE PLANS. | | | 15) THE FUEL TANK SHALL BE LOCATED IN A ROOM WITH A | | | FIRE- RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE | | | THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC | | | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION | | | 903.3.1.1 OR 903.1.2 , THE REQUIERED FIRE-RESISTANCE | | | RATING SHALL BE REDUCED TO ONE HOUR. 2017 FBC-BUILDING | | | SEC.403.4.8.2. | | | 16) THE PLANS SHOW THE FUEL TANK LOCATED IN A SEPARATE | | | ROOM THAT IS NOT SHOWN ON THE ORIGINAL PLANS. A | | | REVISION SHALL BE SUBMITTED SHOWING THE FIRE RATING OF | | | THE ROOM AND DOORS IN WHICH THE FUEL TANK IS LOCATED. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 17) A PLUMBING REVISION SHALL BE SUBMITTED FOR SHT. P | | | 5.01 AS THE FUEL PIPING WAS NOT SHOWN ON THE ORIGINAL | | | PLANS. | | | 18) SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR | | | THE PRYCO FUEL DELIVERY CONTROL STATION FOR REVIEW. WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-01-07 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2020-01-07 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2020-01-07 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2020-01-07 15:17:52 | PROVISO: AN AMENDMENT TO THE SITE PLAN APPROVAL | | | REFLECTING PARKING CHANGES SHALL BE SUBMITTED TO | | | PLANNING AND ZONING PRIOR TO ISSUANCE OF A CO. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2018-11-07 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2018-11-07 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2018-11-07 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2018-11-07 16:02:24 | PROVISO: AN AMENDMENT TO THE SITE PLAN APPROVAL | | | REFLECTING PARKING CHANGES SHALL BE SUBMITTED TO | | | PLANNING AND ZONING PRIOR TO ISSUANCE OF A CO. |
|
|