Plan Review Details - Permit 18101050
Plan Review Stops For Permit 18101050
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 15:17 Rev Time 0.00
Received By shill Date 2019-06-14 Time 15:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-05-13 Cont ID  
Sent By rmcdouga Date 2019-05-13 Time 13:13 Rev Time 0.00
Received By rmcdouga Date 2019-05-13 Time 11:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 09:29 Rev Time 0.00
Received By shill Date 2019-05-06 Time 09:29 Sent To  
Notes
2019-05-06 09:34:00SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2014, BUILDING
  
 COMMENT FROM PREVIOUS TWO REVIEWS:
  
 5) NOT COMPLIED. SIGNED AND SEALED CALCULATIONS AS
 REQUESTED WERE NOT PROVIDED. SUBMIT THE TEST REPORTS OF
 THE FOAM FOR THE FLAME SPREAD AND SMOKE DEVELOPED (ASTM
 E84 OR UL 723). PROVIDE DETAILS ON THE PLANS OF HOW THE
 FOAM WILL BE ENCASED IN CONCRETE AS REQUIRED BY FBC
 603.1.
 STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW THE
 POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING THE
 POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS FOAM
 WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO SHOW
 THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED POOL.
 FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II BUILDINGS IS
 REQUIRED TO BE ENCASED IN CONCRETE. FBC 603.1
  
 3RD REVIEW:
  
 THE RESPONSE LETTER FROM THE POOL CONTRACTOR STATES
 THAT CALCULATIONS ARE ATTACHED. EXHIBIT A STRUCTURAL
 FOAM CALC WAS NOT PREPARED BY AN ENGINEER, FS471. AS
 DELEGATED ENGINEERING, THE CALCULATIONS SHOULD BE
 PREPARED BY THE POOL ENGINEER AND REVIEWED BY
 STRUCTURAL ENGINEER OF RECORD.
  
 THE FOAM SPECS STATE THAT AN ASTM TEST WILL BE DONE
 UPON ACCEPTANCE OF THE ORDER. PLEASE PROVIDE.
  
 ***THIS PERMIT WILL BE ISSUED WITH PROVISO - THE
 NANAWALL IS SHOWN AS A POOL BARRIER. THIS IS NOT A
 COMPLIANT POOL BARRIER; ARCHITECT AND OWNER HAVE BEEN
 ADVISED REGARDING THIS ISSUE***
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-11 Cont ID  
Sent By rmcdouga Date 2019-03-11 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2019-03-11 Time 15:39 Sent To I
Notes
2019-03-11 15:39:56PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) NOT COMPLIED. SIGNED AND SEALED CALCULATIONS AS
 REQUESTED WERE NOT PROVIDED. SUBMIT THE TEST REPORTS OF
 THE FOAM FOR THE FLAME SPREAD AND SMOKE DEVELOPED (ASTM
 E84 OR UL 723). PROVIDE DETAILS ON THE PLANS OF HOW THE
 FOAM WILL BE ENCASED IN CONCRETE AS REQUIRED BY FBC
 603.1.
 STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW THE
 POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING THE
 POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS FOAM
 WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO SHOW
 THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED POOL.
 FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II BUILDINGS IS
 REQUIRED TO BE ENCASED IN CONCRETE. FBC 603.1
  
 NOTE: WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-11 Cont ID  
Sent By rmcdouga Date 2018-12-11 Time 11:07 Rev Time 0.00
Received By rmcdouga Date 2018-12-11 Time 11:07 Sent To  
Notes
2018-12-11 11:46:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN
 REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY
 ONE SET OF SUBMITTALS. THE ELECTRONICALLY SUBMITTED
 PLANS REQUIRE THE ENGINEER'S DIGITAL SIGNATURE. FAC
 61G15-23.003
  
 2) THE ELECTRICAL PLAN SHEET E1.0 THAT IS LISTED IN THE
 TABLE OF CONTENTS ON SHEET P1.0 WAS NOT UPLOADED. WITH
 THIS SUBMITTAL. FBC 107.2.1
  
 3) SHOW HOW COMPLIANCE WITH FBC 454.1.3.1.9 WILL BE
 MET. ALL PUBLIC POOLS SHALL BE SURROUNDED BY A MINIMUM
 48 INCH (1219 MM) HIGH FENCE OR OTHER APPROVED
 SUBSTANTIAL BARRIER. THE FENCE SHALL BE CONTINUOUS
 AROUND THE PERIMETER OF THE POOL AREA THAT IS NOT
 OTHERWISE BLOCKED OR OBSTRUCTED BY ADJACENT BUILDINGS
 OR STRUCTURES AND SHALL ADJOIN WITH ITSELF OR ABUT TO
 THE ADJACENT MEMBERS. ACCESS THROUGH THE BARRIER OR
 FENCE FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS,
 MOTEL ROOMS AND HOTEL ROOMS, SHALL BE THROUGH
 SELF-CLOSING, SELF-LATCHING LOCKABLE GATES OF 48 INCH
 (1219 MM) MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH
 THE LATCH LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM
 THE BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM)
 BELOW THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. DOORED ACCESS POINTS FROM PUBLIC ROOMS
 SUCH AS LOBBIES OR CLUB HOUSES NEED NOT BE THROUGH
 GATES IF THE DOOR(S) MEET THE SAME SELF-CLOSING,
 SELF-LATCHING REQUIREMENTS AS A GATE. GATES SHALL OPEN
 OUTWARD AWAY FROM THE POOL AREA. A LATCHED, LOCKABLE
 GATE SHALL BE PLACED IN THE FENCE WITHIN 10 FEET (3048
 MM) OF THE CLOSEST POINT BETWEEN THE POOL AND THE
 EQUIPMENT AREA FOR SERVICE ACCESS.
  
 4) 454.1.2.3.5 RULES AND REGULATIONS SIGNAGE. ITEM #8
 WAS NOT INCLUDED ON YOUR SIGNAGE 8.IF THE POOL INCLUDES
 A SUN SHELF, "WARNING: DROP OFF AT SUN SHELF EDGE IS
 _X_ FEET DEEP" IN 4-INCH (102 MM) LETTERS.
  
 5) STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW
 THE POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING
 THE POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS
 FOAM WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO
 SHOW THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED
 POOL. FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II
 BUILDINGS IS REQUIRED TO BE ENCASED IN CONCRETE. FBC
 603.1
  
 NOTE: WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2019-07-10 Cont ID  
Sent By jpearson Date 2019-07-10 Time 08:10 Rev Time 0.00
Received By jpearson Date 2019-07-10 Time 08:10 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2019-06-12 Cont ID  
Sent By jpearson Date 2019-06-12 Time 11:08 Rev Time 0.00
Received By jpearson Date 2019-06-12 Time 11:08 Sent To  
Notes
2019-06-12 10:17:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LIGHT FIXTURE SCHEDULE FOR LIGHTING IN POOL
 AND POOL AREA. SOME OF THE FIXTURES SPECIFIED ARE NOT
 ON THE ORIGINAL LIGHT FIXTURE SCHEDULE. BE ADVISED THAT
 FIXTURE RL2 IS SHOWN IN ORIGINAL LIGHT FIXTURE SCHEDULE
 AS A 277 VOLT FIXTURE. SHEET E-104 SHOWS IT BEING FED
 FROM A 120/208 VOLT PANEL. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 2. SHEET E-104 SHOWS FIXTURE RL2 LOCATED APPROXIMATELY
 54 INCHES FROM POOL. NO LIGHT FIXTURE SHALL BE
 INSTALLED LOWER THAN 12 FEET WHEN WITHIN 5 FEET OF THE
 POOL. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC
 680.22(B)(1)
 3. SHEET P2.0 SHOWS ONLY FIXTURE TYPE FL1 IN THE
 PLANTERS. SHEET E-104 SHOWS FL2 IN THE PLANTER, AND FL1
 SURROUNDING THE PLANTER. PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1
 4. SHEET E-104 IN A BLOCK NOTE STATES THAT ALL CIRCUITS
 WITHIN 5-10 FEET OF POOL SHALL BE PROTECTED BY A GFCI
 BREAKER. THE PANEL SCHEDULES FOR THESE CIRCUITS DO NOT
 REFLECT THIS REQUIREMENT. SOME OF THE PANEL SCHEDULES
 FOR LIGHTING IN THE POOL AREA ARE NOT INCLUDED IN THIS
 SUBMISSION. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 680.22(B)(4)
 5. LIGHT FIXTURE B IS SHOWN IN SEVERAL LOCATIONS. WHAT
 ARE THESE FIXTURES? SHOW COMPLIANCE WITH FBC 454.1.4.2
 FOR MINIMUM LIGHTING LEVELS, AND NEC 680.22 OR 680.23
 AS APPLICABLE FOR VOLTAGE/GFCI PROTECTION AS REQUIRED.
 6. SHEET P2.0 QUOTES THE REQUIREMENT FOR UNDERWATER
 LIGHTING STATING THAT IT IS FROM THE 2017 FBC. THIS
 CODE SECTION QUOTED, FBC 454.1.4.2.3, IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. WPB FBC 107.2.1; FBC
 454.1.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2019-05-14 Cont ID  
Sent By jpearson Date 2019-05-14 Time 10:24 Rev Time 0.00
Received By jpearson Date 2019-05-14 Time 10:24 Sent To  
Notes
2019-05-14 10:24:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE ONLY ELECTRICAL SHEETS PROVIDED ARE 2 SHEETS
 WITH PANEL SCHEDULES. THESE SHEETS BOTH SHOW THE SAME
 PANEL, PANEL PP1, WHICH IS A 3 PHASE PANEL FED FROM
 PANEL K8L. HOWEVER, THE LOAD SPECIFIED ON THESE TWO
 PANEL SCHEDULES IS DIFFERENT, AND NEITHER OF THEM MATCH
 THE EQUIPMENT REQUIREMENTS/LOAD SHOWN ON SHEET P3.0.
 ADDITIONALLY, THERE ARE NO DETAILS, WIRING DIAGRAMS,
 FLOOR PLANS, ETC., THAT SHOW THE ELECTRICAL WIRING AND
 MATERIALS, INCLUDING THE PREVIOUSLY REQUESTED RATING OF
 ENCLOSURES IN THE ELECTRICAL ROOM PER NEC TABLE 110.28.
 THEREFORE, A COMPLETE REVIEW IS NOT POSSIBLE AT THIS
 TIME. PROVIDE ELECTRICAL PLAN FOR REVIEW. WPB FBC
 107.1, 107.2.1
 2. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE $5,185.00
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2019-04-30 Cont ID  
Sent By jpearson Date 2019-04-30 Time 07:45 Rev Time 0.00
Received By jpearson Date 2019-04-30 Time 07:45 Sent To  
Notes
2019-04-30 07:45:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL PLAN PROVIDED FOR REVIEW. PLANS
 SUBMITTED IN THE DIGITAL FORMAT MUST INCLUDE ALL OF THE
 PLAN SHEETS DIGITALLY. WE DO NOT HAVE A HYBRID SYSTEM
 WHERE SOME PLANS ARE PAPER AND SOME ARE DIGITAL.
 PROVIDE CORRECTION. WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-03-05 Cont ID  
Sent By jpearson Date 2019-03-05 Time 15:13 Rev Time 0.00
Received By jpearson Date 2019-03-05 Time 15:13 Sent To  
Notes
2019-03-05 15:13:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH PROPER
 THIRD PARTY VERIFICATION. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481 (THE ONLY TWO ELECTRICAL SHEETS
 SUPPLIED WERE NOT SIGNED/SEALED.)
 2. ON SHEET P1.0, TABLE OF CONTENTS, IT SHOWS SHEET
 E1.0. THIS SHEET IS NOT INCLUDED IN SUBMISSION. PROVIDE
 FOR REVIEW. WPB FBC 107.1, 107.2.1 (COMMENT RESPONSE
 STATES THAT ELECTRICAL PLAN WILL BE PROVIDED BY
 ENGINEER. THE ONLY TWO SHEETS PROVIDED WERE PANEL
 SCHEDULES AND THEY WERE NOT SIGNED/SEALED.)
 3. PROVIDE ENCLOSURE FOR ELECTRICAL PANEL THAT MEETS
 THE REQUIREMENTS OF NEC FOR EXPOSURE TO CORROSIVE
 AGENTS. NEC TABLE 110.28 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By jpearson Date 2018-11-27 Time 14:39 Rev Time 0.00
Received By jpearson Date 2018-11-27 Time 14:39 Sent To  
Notes
2018-11-27 14:39:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE
 CORRECTION. WPB FBC 107.1; FS 471/481
 2. ON SHEET P1.0, TABLE OF CONTENTS, IT SHOWS SHEET
 E1.0. THIS SHEET IS NOT INCLUDED IN SUBMISSION. PROVIDE
 FOR REVIEW. WPB FBC 107.1, 107.2.1
 3. PROVIDE ENCLOSURE FOR ELECTRICAL PANEL THAT MEETS
 THE REQUIREMENTS OF NEC FOR EXPOSURE TO CORROSIVE
 AGENTS. NEC TABLE 110.28
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-01-02 Cont ID  
Sent By tklarge Date 2019-01-02 Time 06:57 Rev Time 0.00
Received By tklarge Date 2019-01-02 Time 06:57 Sent To  
Notes
2019-01-02 06:58:55A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT IS REQUIRED FOR A
 CONTRACTOR TO PERFORM THE RELATED WORK. PROVIDE
 COMPLETE PLANS THAT REFLECT THE ENTIRE SCOPE OF GAS
 WORK TO BE DONE. WPB AMEND. TO FBC SEC.107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2019-07-10 Time   Rev Time 0.00
Received By lmarchan Date 2019-06-26 Time 10:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 15:57 Rev Time 0.00
Received By shill Date 2019-06-11 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-05-16 Cont ID  
Sent By shill Date 2019-05-16 Time 07:25 Rev Time 0.00
Received By shill Date 2019-05-10 Time 17:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-05-06 Cont ID  
Sent By shill Date 2019-05-06 Time 13:47 Rev Time 0.00
Received By shill Date 2019-04-11 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-15 Cont ID  
Sent By lmarchan Date 2019-03-15 Time 12:33 Rev Time 0.00
Received By lmarchan Date 2019-02-19 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2019-01-02 Cont ID  
Sent By lmarchan Date 2019-01-02 Time 09:53 Rev Time 0.00
Received By lmarchan Date 2018-11-01 Time 08:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-06-12 Cont ID  
Sent By tklarge Date 2019-06-12 Time 07:05 Rev Time 0.00
Received By tklarge Date 2019-06-12 Time 07:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-05-14 Cont ID  
Sent By tklarge Date 2019-05-14 Time 10:28 Rev Time 0.00
Received By tklarge Date 2019-05-14 Time 09:18 Sent To  
Notes
2019-05-14 09:55:011) THE CORRECT ADDRESS FOR THIS PROJECT SHALL BE NOTED
 ON ALL SUBMITTED SHEETS. "NARCISSUS AVENUE AND BANYAN
 BLVD. IS INADEQUATE. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THERE ARE ADDITIONAL PLUMBING DRAWINGS THAT HAVE
 BEEN UPLOADED INTO THIS FOLDER THAT HAVE NOTHING TO DO
 WITH THE SWIMMING POOL. THEY ARE PLUMBING DRAWINGS FOR
 THE BUILDING.REMOVE THESE DRAWINGS FROM THE FOLDER AND
 SUBMIT THE DRAWINGS THAT ARE APPLICABLE TO THE POOL
 ONLY. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-05-02 Cont ID  
Sent By tklarge Date 2019-05-02 Time 10:40 Rev Time 0.00
Received By tklarge Date 2019-04-29 Time 11:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-03-12 Cont ID  
Sent By tklarge Date 2019-03-12 Time 10:12 Rev Time 0.00
Received By tklarge Date 2019-03-12 Time 08:33 Sent To  
Notes
2019-03-12 08:36:071) A REDUCED PRESSURE ZONE BACKFLOW PREVENTER IS
 REQUIRED ON THE WATER SUPPLY TO THE COLLECTOR TANK PER
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.2ND REQUEST.
 2) THE OPERABLE PARTS OF THE RINSE SHOWER SHALL COMPLY
 WITH 2017 FBC-ACCESS SECS. 308 & 309. 2ND REQUEST.
 3) THERE ARE ADDITIONAL PLUMBING DRAWINGS THAT HAVE
 BEEN UPLOADED INTO THIS FOLDER THAT HAVE NOTHING TO DO
 WITH THE SWIMMING POOL. THEY ARE PLUMBING DRAWINGS FOR
 THE BUILDING.REMOVE THESE DRAWINGS FROM THE FOLDER AND
 SUBMIT THE DRAWINGS THAT ARE APPLICABLE TO THE POOL
 ONLY. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE UPLOADED DRAWINGS HAVE NAMING CONVENTIONS THAT
 DO NOT IDENTIFY THE DRAWING NUMBER. ALMOST EVERY SHEET
 HAS TO BE OPENED TO SEE WHICH SHEET IT IS. PLEASE
 CORRECT THIS ISSUE.
 5) MANUFACTURER'S SPECIFICATIONS HAVE BEEN SUBMITTED
 FOR THE CONDENSATE DRAINS. PLEASE REFER TO MY ORIGINAL
 PLAN REVIEW COMMENT. I REQUESTED THAT THE SIZE AND THE
 TERMINATION POINT OF THE CONDENSATE DRAINS BE SHOWN ON
 THE PLANS. THIS DOES NOT APPEAR TO HAVE BEEN DONE
 COMPLY WITH ORIGINAL COMMENT.
 6) SIGNED AND SEALED CALCULATIONS AS REQUESTED WERE NOT
 PROVIDED. SUBMIT THE TEST REPORTS OF THE FOAM FOR THE
 FLAME SPREAD AND SMOKE DEVELOPED (ASTM E84 OR UL 723).
 PROVIDE DETAILS ON THE PLANS OF HOW THE FOAM WILL BE
 ENCASED IN CONCRETE AS REQUIRED BY FBC 603.1.
 STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW THE
 POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING THE
 POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS FOAM
 WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO SHOW
 THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED POOL.
 FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II BUILDINGS IS
 REQUIRED TO BE ENCASED IN CONCRETE. FBC 603.1
  
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2019-01-02 Cont ID  
Sent By tklarge Date 2019-01-02 Time 06:57 Rev Time 0.00
Received By tklarge Date 2018-12-26 Time 10:34 Sent To  
Notes
2018-12-26 10:44:12PLAN REVIEW COMMENTS
  
 1) THE ELECTRICAL PLAN SHEET E1.0 THAT IS LISTED IN THE
 TABLE OF CONTENTS ON SHEET P1.0 WAS NOT UPLOADED. WITH
 THIS SUBMITTAL. FBC 107.2.1
 2) STRUCTURAL FOAM FILL IS SHOWN ON SHEET P2.2 BELOW
 THE POOL. IT APPEARS THAT THIS FOAM WILL BE SUPPORTING
 THE POOL. SUBMIT THE PRODUCT SPECIFICATIONS FOR THIS
 FOAM WITH SIGNED AND SEALED ENGINEERED CALCULATIONS TO
 SHOW THAT THE STRUCTURAL FOAM WILL SUPPORT THE FILLED
 POOL. FBC 107.2.1.2 NOTE: FOAM IN TYPE I AND II
 BUILDINGS IS REQUIRED TO BE ENCASED IN CONCRETE. FBC
 603.1.
 3) SHT. P2.1 - THE EQUALIZER IS SHOWN AS 2 INCH AND
 ALSO AS 4 INCH. CLARIFY.
 4) THE PLANS SHALL BE DIGITALLY SIGNED AND SEALED PER
 FL. ADMIN. CODE RULE 61G15-23.003,
 5) A VAPOR RETARDANT COVER ON OR AT THE WATER SURFACE
 OR A LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT
 LOSS SHALL BE PROVIDED PER THE 2017 FBC-ENERGY SEC.
 C404.9.3.
 6) THE EQUIPMENT ROOM SHALL HAVE EITHER FORCED DRAFT OR
 CROSS VENTILATION PER 2017 FBC SEC. 4541.5.4. PROVIDE
 DDETAILS.
 7) SHT. P2.2 - SHOW THE SIZE AND TERMINATION POINT OF
 THE CONDENSATE DRAINS.
 8) SHT. P2.3 - TYPICAL MAIN DRAIN DETAILS CALLS OUT 3
 MAIN DRAINS BUT SHT. P2.1 SHOWS 4. CLARIFY.
 9) SHT.P2.0 - POOL MATERIALS & EQUIPMENT
 LIST/PLUMBING/EQUIPMENT ROOM REFERS TO SHT. P4.0 FOR
 COMPLETE SPECS. THERE IS NO SHT. P4.0 IN THIS
 SUBMITTAL. CLARIFY.
 10) A REDUCED PRESSURE ZONE BACKFLOW PREVENTER IS
 REQUIRED ON THE WATER SUPPLY TO THE COLLECTOR TANK PER
 CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.
 11) THE OPERABLE PARTS OF THE RINSE SHOWER SHALL
 CCOMPLY WITH THE 2017 FBC-ACCESS. SEC.309.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2019-07-09 Cont ID  
Sent By shill Date 2019-07-09 Time 10:58 Rev Time 0.00
Received By shill Date 2019-07-09 Time 10:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2019-06-14 Cont ID  
Sent By shill Date 2019-06-14 Time 15:12 Rev Time 0.00
Received By shill Date 2019-06-12 Time 06:21 Sent To  
Notes
2019-06-12 06:46:44SIGNATURES OK ON ALL PLUMBING DRAWINGS. T.LARGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2019-05-14 Cont ID  
Sent By shill Date 2019-05-14 Time 09:21 Rev Time 0.00
Received By shill Date 2019-05-14 Time 09:13 Sent To  
Notes
2019-05-16 07:26:25DIGITAL SIGNATURE OK BUT PLANS WILL BE REPLACED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-05-02 Cont ID  
Sent By tklarge Date 2019-05-02 Time 10:43 Rev Time 0.00
Received By tklarge Date 2019-05-02 Time 10:40 Sent To  
Notes
2019-05-02 10:40:37SIGNATURES OK ON ALL SHEETS. TKL.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-03-19 Cont ID  
Sent By shill Date 2019-03-19 Time 10:56 Rev Time 0.00
Received By shill Date 2019-03-19 Time 10:56 Sent To  
Notes
2019-03-19 10:57:34DIGITAL SIGNATURES FOR THE PAGES WHICH ARE DIGITALLY
 SIGNED ARE OK. HOWEVER, NAMING CONVENTION IS NOT
 CORRECT, MAKING PLAN REVIEW EXTREMELY DIFFICULT AND
 TIME CONSUMING. REMOVAL OF ALL SHEETS AND UPLOADING OF
 PROPERLY NAMED DIGITALLY SIGNED PAGES IS REQUIRED;
 EMAILED APPLICANT.
  
 [email protected], 561-805-6724
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-27 Cont ID  
Sent By jpearson Date 2018-11-27 Time 14:26 Rev Time 0.00
Received By jpearson Date 2018-11-27 Time 14:26 Sent To  
Notes
2018-11-27 14:26:48EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE. PROVIDE CORRECTION.
 WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 4 Status P Date 2019-06-14 Cont ID  
Sent By aaponte Date 2019-06-14 Time 15:54 Rev Time 0.00
Received By aaponte Date 2019-06-14 Time 15:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-05-09 Cont ID  
Sent By aaponte Date 2019-05-09 Time 15:11 Rev Time 0.00
Received By aaponte Date 2019-05-09 Time 15:11 Sent To  
Notes
2019-05-09 15:11:54PROVISO: A MINOR SITE PLAN AMENDMENT SHALL BE SUBMITTED
 TO REFLECT THE CHANGES FROM SITE PLAN APPROVAL.
2019-05-06 13:47:33ZONING WILL BE DONE NEXT REVIEW CYCLE PER AA
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-03-15 Cont ID  
Sent By aaponte Date 2019-03-15 Time 11:54 Rev Time 0.00
Received By aaponte Date 2019-03-15 Time 11:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-12-06 Cont ID  
Sent By aaponte Date 2018-12-06 Time 09:44 Rev Time 0.00
Received By aaponte Date 2018-12-06 Time 09:44 Sent To  
Notes
***NONE***