Plan Review Details - Permit 18101020
Plan Review Stops For Permit 18101020
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-28 Cont ID  
Sent By lcrespo Date 2019-03-28 Time 16:01 Rev Time 0.00
Received By lcrespo Date 2019-03-26 Time 15:32 Sent To  
Notes
2019-03-27 15:32:41RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-14 Cont ID  
Sent By lcrespo Date 2018-12-14 Time 16:20 Rev Time 0.00
Received By lcrespo Date 2018-12-10 Time 13:17 Sent To  
Notes
2018-12-11 13:17:53PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-28 Cont ID  
Sent By lcrespo Date 2019-03-28 Time 16:01 Rev Time 0.00
Received By lcrespo Date 2019-03-28 Time 16:01 Sent To  
Notes
2019-03-28 16:02:2303/28/19 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By lcrespo Date 2018-12-14 Time 16:20 Rev Time 0.00
Received By lcrespo Date 2018-12-14 Time 16:20 Sent To  
Notes
2018-12-14 16:52:0412/14/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS RES SECS. G2413.4.1, G2413.4.2.
 3. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 ISOMETRIC. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 5. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 RES. SEC. G2413.
 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER 2017 FBC FUEL
 GAS RES. SEC. G2413.4.1.
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS RES. SEC. G2413.2.
 8. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING
 PERMITS VALUATIONS.
 9. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES.
 SECS. G2426 THRU G2429.1
 10. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR TANKLESS GAS EQUIPMENT
 TO VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC.
 G2408.1. PLEASE, MARK UNIT THAT IS BEING USED, THE
 SPECS SUBMITTED DOES NOT MATCH BTU?S ON THE
 SPECIFICATION SHEET.
 11. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
 12. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. IF THE HEATER IS INSIDE HOW IT IT GOING TO BE
 VENTED? WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  