Plan Review Details - Permit 18100971
Plan Review Stops For Permit 18100971
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-05 Cont ID  
Sent By lcrespo Date 2018-11-05 Time 13:41 Rev Time 0.00
Received By lcrespo Date 2018-10-31 Time 15:06 Sent To  
Notes
2018-11-01 15:06:47RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By tklarge Date 2018-10-24 Time 08:50 Rev Time 0.00
Received By tklarge Date 2018-10-24 Time 08:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-05 Cont ID  
Sent By lcrespo Date 2018-11-05 Time 13:41 Rev Time 0.00
Received By lcrespo Date 2018-11-02 Time 14:48 Sent To  
Notes
2018-11-05 13:42:5411/05/18 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/BACKFLOW)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  
2018-11-02 14:49:05APPROVED BY PLUMBING. SENT TO UTILITIES FOR REVIEW.TKL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By tklarge Date 2018-10-24 Time 08:50 Rev Time 0.00
Received By tklarge Date 2018-10-24 Time 08:15 Sent To  
Notes
2018-10-24 08:50:121) A PRESSURE VACUUM BREAKER ASSEMBLY IS NOT PERMITTED
 ON A NON-RESIDENTIAL IRRIGATION SYSTEM PER THE CITY OF
 WEST PALM CROSS-CONNECTION CONTROL MANUAL. THE MINIMUM
 LEVEL OF PROTECTION IS A REDUCED PRESSURE ZONE VALVE
 ASSEMBLY.
 2) ALL DEVICES MUST BE LEAD FREE AND APPROVED BY THE
 FOUNDATION FOR CROSS-CONNECTION CONTROL AND HYDRAULIC
 RESEARCH AT THE UNIVERSITY OF SOUTHERN CALIFORNIA.
 3) AS AN FYI - ALL NEW DEVICES MUST BE TESTED AND
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPT.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  